Tripp Lite SU3000RTXL3UHV Runtime Chart for UPS Model SU3000RTXL3UHV

Tripp Lite SU3000RTXL3UHV Manual

Tripp Lite SU3000RTXL3UHV manual content summary:

  • 1

SU3000RTXL3UHV Estimated Runtime
Load in Watts
UPS
Battery Pack
500W
1,000W
1,100W
1,200W
1,300W
1,400W
1,500W
1,600W
1,700W
1,800W
1,900W
2,000W
2,200W
2,400W
All runtime values are in minutes.
SU3000RTXL3UHV
Internal Batteries
39
17
15
14
12
11
10
9.2
8.4
7.8
7.2
6.7
5.9
5.0
SU3000RTXL3UHV
1 BP72V15-2U
111
51
45
41
37
34
31
29
26
25
23
21
19
17
SU3000RTXL3UHV
1 BP72V28RT-3U
204
96
86
78
70
64
59
55
51
47
44
41
37
33
SU3000RTXL3UHV
2 BP72V28RT-3U
395
193
174
158
144
132
122
113
105
98
92
86
77
69
SU3000RTXL3UHV
3 BP72V28RT-3U
587
294
266
242
221
203
188
175
163
152
143
135
120
108
SU3000RTXL3UHV
4 BP72V28RT-3U
779
396
359
327
300
276
256
238
222
208
196
185
166
150
SU3000RTXL3UHV
5 BP72V28RT-3U
968
498
452
413
379
350
325
302
283
265
250
236
212
192
SU3000RTXL3UHV
6 BP72V28RT-3U
1,154
600
545
499
459
424
394
367
344
323
304
287
258
234
SU3000RTXL3UHV
7 BP72V28RT-3U
1,339
702
639
585
538
498
463
432
405
381
359
339
305
277
SU3000RTXL3UHV
8 BP72V28RT-3U
1,521
803
731
671
618
572
532
497
466
438
414
391
353
321
SU3000RTXL3UHV
9 BP72V28RT-3U
1,700
903
824
756
697
646
601
562
527
496
468
443
400
364
SU3000RTXL3UHV
10 BP72V28RT-3U
1,877
1,003
915
841
776
719
670
626
588
554
523
496
448
408