Tripp Lite SU3000RTXR3U Runtime Chart for UPS Model SU3000RTXR3U

Tripp Lite SU3000RTXR3U Manual

Tripp Lite SU3000RTXR3U manual content summary:

  • 1

SU3000RTXR3U Estimated Runtime
Load in Watts
UPS
Battery Pack
500W
1,000W
1,100W
1,200W
1,300W
1,400W
1,500W
1,600W
1,700W
1,800W
1,900W
2,000W
2,200W
2,400W
All runtime values are in minutes.
SU3000RTXR3U
Internal Batteries
82
37
33
30
27
25
22
21
19
18
17
15
14
12
SU3000RTXR3U
1 BP72V15-2U
157
73
65
59
53
49
45
41
38
36
33
31
28
25
SU3000RTXR3U
1 BP72V28RT-3U
251
120
107
97
88
81
74
69
64
59
56
52
46
42
SU3000RTXR3U
2 BP72V28RT-3U
443
218
197
179
163
150
138
128
119
111
104
98
88
79
SU3000RTXR3U
3 BP72V28RT-3U
635
319
289
263
241
222
205
190
178
166
156
147
132
119
SU3000RTXR3U
4 BP72V28RT-3U
826
421
382
349
320
295
273
254
237
223
209
197
177
160
SU3000RTXR3U
5 BP72V28RT-3U
1,015
524
475
435
399
369
342
319
298
280
263
249
223
202
SU3000RTXR3U
6 BP72V28RT-3U
1,201
626
569
521
479
443
411
383
359
337
318
300
270
245
SU3000RTXR3U
7 BP72V28RT-3U
1,385
727
662
607
558
516
480
448
420
395
373
352
317
288
SU3000RTXR3U
8 BP72V28RT-3U
1,566
828
754
692
638
590
549
513
481
453
427
404
365
331
SU3000RTXR3U
9 BP72V28RT-3U
1,745
928
847
777
717
664
618
578
542
511
482
456
412
375
SU3000RTXR3U
10 BP72V28RT-3U
1,921
1,028
938
862
795
737
687
643
603
568
537
509
459
418