- Tripp Lite SU5000RT | SU5000RT runtime chart - Page 1
UPS SU5000RT SU5000RT SU5000RT SU5000RT SU5000RT SU5000RT Estimated Runtime Extended Battery Module Internal batteries BP180RT BP180RT BP180RT BP180RT EBM QTY 0 1 2 3 4 CONNECTED EQUIPMENT LOAD IN WATTS 450 787 1,125 1,687 2,250 2,812 3,375 73.0 50.0 27.0 19.0 11.0 8.0 5.3 246.0 174.0
Extended
Battery Module
450
787
1,125
1,687
2,250
2,812
3,375
3,937
4,500
SU5000RT
Internal batteries
0
73.0
50.0
27.0
19.0
11.0
8.0
5.3
4.0
3.2
SU5000RT
BP180RT
1
246.0
174.0
103.0
75.0
48.0
37.0
27.0
23.0
20.0
SU5000RT
BP180RT
2
485.0
330.0
175.0
131.0
88.0
70.0
53.0
45.0
38.0
SU5000RT
BP180RT
3
661.0
461.0
262.0
192.0
123.0
103.0
83.0
68.0
54.0
SU5000RT
BP180RT
4
935.0
656.0
377.0
272.0
167.0
138.0
109.0
94.0
80.0
SU5000RT Estimated Runtime
UPS
EBM
QTY
CONNECTED EQUIPMENT LOAD IN WATTS
All runtime values are shown in minutes.