Tripp Lite SU5000RT SU5000RT runtime chart

Tripp Lite SU5000RT Manual

Tripp Lite SU5000RT manual content summary:

  • Tripp Lite SU5000RT | SU5000RT runtime chart - Page 1
    UPS SU5000RT SU5000RT SU5000RT SU5000RT SU5000RT SU5000RT Estimated Runtime Extended Battery Module Internal batteries BP180RT BP180RT BP180RT BP180RT EBM QTY 0 1 2 3 4 CONNECTED EQUIPMENT LOAD IN WATTS 450 787 1,125 1,687 2,250 2,812 3,375 73.0 50.0 27.0 19.0 11.0 8.0 5.3 246.0 174.0
  • 1

Extended
Battery Module
450
787
1,125
1,687
2,250
2,812
3,375
3,937
4,500
SU5000RT
Internal batteries
0
73.0
50.0
27.0
19.0
11.0
8.0
5.3
4.0
3.2
SU5000RT
BP180RT
1
246.0
174.0
103.0
75.0
48.0
37.0
27.0
23.0
20.0
SU5000RT
BP180RT
2
485.0
330.0
175.0
131.0
88.0
70.0
53.0
45.0
38.0
SU5000RT
BP180RT
3
661.0
461.0
262.0
192.0
123.0
103.0
83.0
68.0
54.0
SU5000RT
BP180RT
4
935.0
656.0
377.0
272.0
167.0
138.0
109.0
94.0
80.0
SU5000RT Estimated Runtime
UPS
EBM
QTY
CONNECTED EQUIPMENT LOAD IN WATTS
All runtime values are shown in minutes.