Tripp Lite SU6000RTMB SU6000RTMB runtime chart

Tripp Lite SU6000RTMB Manual

Tripp Lite SU6000RTMB manual content summary:

  • Tripp Lite SU6000RTMB | SU6000RTMB runtime chart - Page 1
    UPS SU6000RTMB SU6000RTMB SU6000RTMB SU6000RTMB SU6000RTMB SU6000RTMB Estimated Runtime Extended Battery Module Internal batteries BP180RT BP180RT BP180RT BP180RT EBM QTY 0 1 2 3 4 CONNECTED EQUIPMENT LOAD IN WATTS 540 945 1,350 2,025 2,700 3,375 4,050 57.0 39.0 22.0 15.0 8.5 6.0 4.5
  • 1

Extended
Battery Module
540
945
1,350
2,025
2,700
3,375
4,050
4,725
5,400
SU6000RTMB
Internal batteries
0
57.0
39.0
22.0
15.0
8.5
6.0
4.5
3.7
3.0
SU6000RTMB
BP180RT
1
203.0
144.0
85.0
61.0
38.0
31.0
24.0
20.0
16.0
SU6000RTMB
BP180RT
2
399.0
273.0
147.0
109.0
71.0
58.0
45.0
36.0
28.0
SU6000RTMB
BP180RT
3
554.0
384.0
214.0
159.0
104.0
83.0
62.0
54.0
47.0
SU6000RTMB
BP180RT
4
755.0
521.0
287.0
210.0
133.0
111.0
90.0
74.0
58.0
SU6000RTMB Estimated Runtime
UPS
EBM
QTY
CONNECTED EQUIPMENT LOAD IN WATTS
All runtime values are shown in minutes.