Tripp Lite SU6000RTMB SU6000RTMB runtime chart
Tripp Lite SU6000RTMB Manual
View all Tripp Lite SU6000RTMB manuals
Add to My Manuals
Save this manual to your list of manuals |
Tripp Lite SU6000RTMB manual content summary:
- Tripp Lite SU6000RTMB | SU6000RTMB runtime chart - Page 1
UPS SU6000RTMB SU6000RTMB SU6000RTMB SU6000RTMB SU6000RTMB SU6000RTMB Estimated Runtime Extended Battery Module Internal batteries BP180RT BP180RT BP180RT BP180RT EBM QTY 0 1 2 3 4 CONNECTED EQUIPMENT LOAD IN WATTS 540 945 1,350 2,025 2,700 3,375 4,050 57.0 39.0 22.0 15.0 8.5 6.0 4.5
Extended
Battery Module
540
945
1,350
2,025
2,700
3,375
4,050
4,725
5,400
SU6000RTMB
Internal batteries
0
57.0
39.0
22.0
15.0
8.5
6.0
4.5
3.7
3.0
SU6000RTMB
BP180RT
1
203.0
144.0
85.0
61.0
38.0
31.0
24.0
20.0
16.0
SU6000RTMB
BP180RT
2
399.0
273.0
147.0
109.0
71.0
58.0
45.0
36.0
28.0
SU6000RTMB
BP180RT
3
554.0
384.0
214.0
159.0
104.0
83.0
62.0
54.0
47.0
SU6000RTMB
BP180RT
4
755.0
521.0
287.0
210.0
133.0
111.0
90.0
74.0
58.0
SU6000RTMB Estimated Runtime
UPS
EBM
QTY
CONNECTED EQUIPMENT LOAD IN WATTS
All runtime values are shown in minutes.