Tripp Lite SU750XL Runtime Chart for UPS Model SU750XL

Tripp Lite SU750XL Manual

Tripp Lite SU750XL manual content summary:

  • Tripp Lite SU750XL | Runtime Chart for UPS Model SU750XL - Page 1
    Runtime Load in Watts UPS SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL SU750XL Battery Pack Internal Batteries 1 BP24V15RT2U 1 BP24V28-2U 1 BP24V70-3U 2 BP24V70-3U 3 BP24V70-3U 4 BP24V70-3U 5 BP24V70-3U 6 BP24V70-3U 7 BP24V70-3U 8 BP24V70
  • 1

SU750XL Estimated Runtime
Load in Watts
UPS
Battery Pack
20W
40W
60W
80W
100W
140W
200W
260W
300W
340W
400W
460W
500W
600W
All runtime values are in minutes.
SU750XL
Internal Batteries
121
81
60
47
38
27
18
13
11
9.7
8.1
6.9
6.3
4.0
SU750XL
1 BP24V15RT2U
562
384
288
228
187
136
94
70
60
51
42
35
31
25
SU750XL
1 BP24V28-2U
957
666
505
404
335
246
173
131
112
96
79
66
60
47
SU750XL
1 BP24V70-3U
2,082
1,484
1,147
931
781
587
422
325
281
244
202
172
156
125
SU750XL
2 BP24V70-3U
4,661
3,445
2,726
2,252
1,916
1,470
1,084
851
744
652
549
472
432
353
SU750XL
3 BP24V70-3U
6,375
4,815
3,863
3,222
2,760
2,141
1,596
1,263
1,109
977
827
715
655
540
SU750XL
4 BP24V70-3U
7,845
6,034
4,898
4,118
3,550
2,778
2,088
1,663
1,465
1,294
1,100
954
876
725
SU750XL
5 BP24V70-3U
9,118
7,126
5,844
4,949
4,290
3,383
2,563
2,051
1,811
1,604
1,368
1,190
1,094
909
SU750XL
6 BP24V70-3U
10,232
8,109
6,712
5,722
4,985
3,959
3,019
2,428
2,149
1,908
1,630
1,422
1,309
1,090
SU750XL
7 BP24V70-3U
11,214
8,999
7,511
6,443
5,638
4,507
3,459
2,793
2,478
2,204
1,888
1,650
1,521
1,270
SU750XL
8 BP24V70-3U
12,088
9,809
8,250
7,116
6,254
5,030
3,883
3,148
2,798
2,493
2,141
1,874
1,729
1,447
SU750XL
9 BP24V70-3U
12,869
10,549
8,934
7,746
6,835
5,529
4,292
3,493
3,110
2,776
2,388
2,094
1,934
1,622
SU750XL
10 BP24V70-3U
13,572
11,227
9,570
8,337
7,384
6,006
4,687
3,828
3,415
3,052
2,631
2,310
2,136
1,794