  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 1
    Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems A Dell Technical White Paper Dell │ Datacenter Infrastructure Engineering By Riyad Moe and Jose L. Flores November 2009
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 2
    ANY KIND. © 2009 Dell Inc. All rights reserved. Reproduction of this material in any manner whatsoever without the express written permission of Dell Inc. is strictly forbidden. For more information, contact Dell. Dell, the DELL logo, the DELL badge, and PowerEdge are trademarks of Dell Inc. Page ii
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 3
    1.5 Left-Side Mounting Instructions ...4 1.6 Right-Side Mounting Instructions ...5 Section 2: Cabling a Dell™ PowerEdge™ R510 System Without a CMA 6 2.1 Routing the Cables...6 2.2 Removing the CMA Brackets for Shallow Racks 7 Section 3: Replacing a Power Supply on a PowerEdge™ R510 System With
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 4
    Practices Guide for Rack Enclosure white paper. Section 1: Cabling a Dell™ PowerEdge™ R510 With a Cable Management Arm (CMA) This section details how to cable a PowerEdge™ R510 system using a CMA. If you are cabling the system without the optional CMA, refer to Section 2. Follow the instructions
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 5
    Dell™ PowerEdge™ R510 Systems 1.2 Installing the Inner CMA Attachment Bracket As described in the Rack Installation Instructions power cables through the strain reliefs located on the power supply handles as shown in figure 3. Figure 3: Routing Power of the power supplies (left-side mount) is recommended;
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 6
    Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems NOTE: For guidelines on how to route cables within the rack, refer to the Dell Best Practices Guide for Rack Enclosures white paper. 1.5 Left-Side Mounting Instructions 1. Install the CMA on the rear left side of the rails by attaching both
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 7
    Dell™ PowerEdge™ R510 Systems Figure 5: Left-Side Mounted CMA Installation 1.6 Right-Side Mounting Instructions CMA as this may restrict the ability of the CMA to support full extension of the rails without causing damage to the dongle. out of the rack to verify that there is sufficient slack in the cables on both
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 8
    Dell™ PowerEdge™ R510 systems is optional. Without the CMA installed, the system must be powered down and all cables disconnected before it can be removed from the rack the Rack Installation Instructions. See Figure 7 for an example of data cables secured to the left CMA bracket and power cables
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 9
    Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Figure 7: Cable Routing Without a CMA 2.2 Removing the CMA Brackets for Shallow Racks If you are installing the system into a shallow rack (less than 1 meter deep) and you will not be installing a CMA, the outer CMA brackets may be removed
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 10
    as described in the CMA Installation Instructions provided with the CMA kit. If the top power supply must be replaced, this step can be skipped. 2. Swing the CMA to its service position. 3. Disconnect the inner CMA bracket from the rail as shown in Figure 9. 4. While supporting the CMA with one hand
  • Dell PowerEdge Rack Enclosure 4820 | Cabling PowerEdge R510 - Page 11
    the Power Supply Section 4: Cabling a PowerEdge™ R510 System Installed in Static Rails NOTE: The CMA is compatible with the sliding rails only, not the static rails. 1. Follow the instructions contained in the Rack Installation Instructions found in the static rail kit to install the server into
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11

Cable Routing Procedures
for Dell™ PowerEdge™
R510 Systems
A Dell Technical White Paper
Dell
│ Datacenter Infrastructure Engineering
By Riyad Moe and Jose L. Flores
November 2009