HP Monitored PDU HP Monitored Power Distribution Unit User's Guide Abstract This document is for the person who installs and maintains HP PDU products. HP assumes you are qualified in the installation of electrical equipment - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 2
associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions. This symbol indicates that you should not discard waste electrical or electronic equipment - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 3
25 Configuring the Network with a DHCP Server 25 Configuring the Network without a DHCP Server 26 Verify Web Operation After Configuration 27 HP Monitored PDU User's Guide P-164000281-Rev 1 i - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 4
Settings 52 Network 52 Access Privileges 53 SuperUser Administrator 53 Local or Remote Administrator 54 PDU-User 54 Session Management 55 HP Monitored PDU User's Guide P-164000281-Rev 1 ii - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 5
62 Communications Card Configuration 63 Perform Firmware Upgrade 63 PDU Configuration 64 Date &Time 64 Manually Configure the Date and Time 64 Automatically Configure the Date and Time 65 TCP/IP /Disable FTP 70 Set Authentication Mode 70 HP Monitored PDU User's Guide P-164000281-Rev 1 iii - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 6
Global Parameters 72 Modify LDAP Server Settings 72 8 SERIAL INTERFACE OPERATION 73 Supported Commands 73 ? command 74 info command 75 quit command 76 get command 111 Environmental and Safety 112 Regulatory Model Numbers 113 11 SUPPORT AND OTHER RESOURCES 114 Before You Contact HP 114 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 7
, depending on the model. Figure 1 shows an example of a PDU installed in a rack. Figure 1. HP Monitored PDU Installed (Bottom Entry Method) HP Monitored PDU User's Guide P-164000281-Rev 1 1 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 8
DV (dual voltage) models. NOTE The WW market includes both INTL and NA models. The PDU models support 1Ph or 3Ph applications and provide between 12 and 36 outlets. All models feature an LCD window, a . Figure 2. 1U Example Model (D9N43A 1Ph Model) HP Monitored PDU User's Guide P-164000281-Rev 1 2 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 9
INTL (no circuit breakers) Figure 4 shows an example of a 36U form factor PDU model. Figure 4. 36U Example Model (D9N47A 1Ph Model) HP Monitored PDU User's Guide P-164000281-Rev 1 3 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 10
3Ph 30 outlets NA Figure 5 shows an example of a 42U form factor PDU model. Figure 5. 42U Example Model (D9N61A 3Ph Model) HP Monitored PDU User's Guide P-164000281-Rev 1 4 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 11
higher visibility on local alarms l External connections to allow remote management by network and serial communications (RS-232 or RJ-45 connector) l Firmware network stack supports both IPv4 and IPv6 HP Monitored PDU User's Guide P-164000281-Rev 1 5 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 12
and permission control l Local and remote configuration functions available through onboard LCD display of menu selections, Web interface, or CLI interface HP Monitored PDU User's Guide P-164000281-Rev 1 6 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 13
all instructions before operating the equipment and save this manual for support/Safety-Compliance-EnterpriseProducts). DANGER This PDU contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE Guide P-164000281-Rev 1 7 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 14
confirm to PDU On/Off position, install the PDU according to installation instructions provided. l This product has been designed to conform to the latest , ensure that used batteries are disposed of according to the instructions. For more information, contact your local recycling/reuse or hazardous - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 15
to the provided installation instructions. Installation Precautions Before you install or connect the PDU in a rack cabinet, observe the following precautions: l Only a competent service person should install, always off when they are unplugged. HP Monitored PDU User's Guide P-164000281-Rev 1 9 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 16
of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative. Installation Overview NOTE 1 Power cords for the devices that you connect to the PDU are M6 cage nut insertion tool l T-25 TORX driver HP Monitored PDU User's Guide P-164000281-Rev 1 10 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 17
racks SEE NOTE 1 3 For 22U, 36U, and 42U models only. Keyhole mounting buttons for mounting in Intelligent series racks SEE NOTE 1 HP Monitored PDU User's Guide P-164000281-Rev 1 11 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 18
centers, for maintenance, or for checks in a warehouse setting. Larger data center customers may choose to use their own network cable. HP Monitored PDU User's Guide P-164000281-Rev 1 12 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 19
installed using the manufacturer's instruction manual. ! IMPORTANT Follow all installation and operation safety information provided in the manufacturer's instruction manual for the EMP equipment. for Transporting an Enterprise PDU in the Rack HP Monitored PDU User's Guide P-164000281-Rev 1 13 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 20
is secure when the top lip snaps up into position. I Figure 7. Installing Cage Nuts in Square-hole Racks (Cage Nut Tool) HP Monitored PDU User's Guide P-164000281-Rev 1 14 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 21
be installed on each Enterprise PDU to install it vertically. The mounting buttons are then inserted into the corresponding keyhole slot. HP Monitored PDU User's Guide P-164000281-Rev 1 15 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 22
earth bonding screw. To ground the PDU, connect a grounding cable (not supplied) from earth to the grounding screw shown in Figure 9. HP Monitored PDU User's Guide P-164000281-Rev 1 16 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 23
of your PDU model (see Figure 10). Connect the DB9 end of the cable to the serial connector on the computer. HP Monitored PDU User's Guide P-164000281-Rev 1 17 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 24
but does have a USB connector, obtain a DB9-to-USB converter cable. Follow the manufacturer's instructions to install the converter cable device drivers and to connect the converter cable to your computer. 4. on the router (or other LAN device. HP Monitored PDU User's Guide P-164000281-Rev 1 18 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 25
Interface Operation" on page 48. l To monitor the PDUs using the CLI interface, go to "Serial Interface Operation" on page 73. HP Monitored PDU User's Guide P-164000281-Rev 1 19 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 26
connected to it. ! IMPORTANT Follow all installation and operation safety information provided in the manufacturer's instruction manual for the EMP equipment. To install an optional EMP: 1. Locate the EMP and the RJ- recognizes the EMP. HP Monitored PDU User's Guide P-164000281-Rev 1 20 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 27
side of the outlets (see Figure 14). Figure 14. Securing the Cords Using Cable Ties Operating the PDU See "Operation Overview" on page 28 for instructions to operate the PDU, including starting and shutting down the equipment. HP Monitored PDU User - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 28
TCP/IP network connection to a PDU. The serial interface is supported on Microsoft Windows 2000, XP 2003, Windows Vista, and later releases connection between the PDU and a computer. NOTE These instructions use HyperTerminal as an example for setting up a PDU User's Guide P-164000281-Rev 1 22 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 29
icon representing the type of connection you will use, then click OK. Figure 16. Define a Serial Port or TCP/IP Connection HP Monitored PDU User's Guide P-164000281-Rev 1 23 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 30
. To open an authentication session, type your user name to log in (see Figure 17). Figure 17. Define a TCP/IP Connection HP Monitored PDU User's Guide P-164000281-Rev 1 24 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 31
or set command. Also see "PDU CLI Objects" (Table 9 on page 82) and "System CLI Objects" (Table 10 on page 90). HP Monitored PDU User's Guide P-164000281-Rev 1 25 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 32
module without the DHCP server installed, you can connect to the PDU using the default address: http://192.168.123.123 HP Monitored PDU User's Guide P-164000281-Rev 1 26 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 33
admin in the User name field and admin in the Password field. 4. The home page opens with the PDU Overview page. HP Monitored PDU User's Guide P-164000281-Rev 1 27 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 34
SCROLL LCD WINDOW ESCAPE DAISY CHAIN PORT USB PORT (FUTURE USE) SCROLL ENTER Figure 18. HP Monitored PDU Display and Connectivity HP Monitored PDU User's Guide P-164000281-Rev 1 28 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 35
communications module restart. 3 Connectivity and Monitoring ports Serial Service and Communication Port: Connects to the serial (COM) On/Off positions are indicated on the circuit breakers. NOTE To manually disconnect power to a device that is connected to the PDU, Guide P-164000281-Rev 1 29 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 36
Figure 20). CB L3 CB L2 CB L1 L1 Outlets L2 Outlets L3 Outlets Figure 20. Outlet Groups and Circuit Breakers HP Monitored PDU User's Guide P-164000281-Rev 1 30 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 37
user cannot select a custom sequence of screens. l EcoMode (energy saving mode) This mode is activated manually. The backlight is turned off to conserves energy.The screen darkens. l Settings mode (LCD main menu of the display for a 1Ph PDU. HP Monitored PDU User's Guide P-164000281-Rev 1 31 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 38
OFF: Normal operation FLASHING: Communicating with EMP (if installed) 3 Green Serial Service Port LED: PDU Communication Status OFF: PDU start-up in progress FLASHING: Normal Escape (ESC) Button 7 Enter Key 8 Forward (Up) Scroll Button HP Monitored PDU User's Guide P-164000281-Rev 1 32 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 39
. NOTE The On/Off positions are indicated on the circuit breakers. - For PDUs without circuit breakers. Plug in the power cord. HP Monitored PDU User's Guide P-164000281-Rev 1 33 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 40
the output power or the connected equipment. 22U, 36U, 42U Model Front Panel Figure 24. Reset Opening 1U Model Front Panel HP Monitored PDU User's Guide P-164000281-Rev 1 34 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 41
the screen. NOTE: On information screens, this button has no action. Scrolls up or down to the next screen or value. HP Monitored PDU User's Guide P-164000281-Rev 1 35 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 42
to go to the Main Menu. hp MM/DD/YYYY HH:MM:SS IP Address Part Number Figure 28. Startup Screen HP Monitored PDU User's Guide P-164000281-Rev 1 36 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 43
Menu to return to the Startup Screen. Main Menu AAcctitviveeAAlalramrms s Alarms History Meter Settings PDU Info Figure 29. Main Menu Selections HP Monitored PDU User's Guide P-164000281-Rev 1 37 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 44
3Ph input PDUs. NOTE 6 These submenus are only available on sections that measure current. Figure 30. HP Monitored PDU Menu Hierarchy HP Monitored PDU User's Guide P-164000281-Rev 1 38 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 45
:12:25 Alarms History Temperature high warning Down 07/07/2011 01:05:44 ESC Figure 32. Example Alarm History Displays HP Monitored PDU User's Guide P-164000281-Rev 1 39 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 46
• - Voltage - • Current - • Percent Load - • Active Power • • Crest Factor - • Apparent Power • - Reactive Power • - Power Factor • - Energy • - Peak Power • - Delta-wired Input Phase HP Monitored PDU User's Guide P-164000281-Rev 1 40 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 47
to review the data for your selection. After you review the data, press ESC twice to return to the previous menu. HP Monitored PDU User's Guide P-164000281-Rev 1 41 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 48
. Only the available options display, depending on the assigned user privileges. There are four Settings submenus: l Display l Daisy Chain l IPv4 l Factory HP Monitored PDU User's Guide P-164000281-Rev 1 42 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 49
step: 3. From the Host PDU, access the Daisy Chain Discovery option to start communication between the Host and the Device PDU. HP Monitored PDU User's Guide P-164000281-Rev 1 43 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 50
PDU Setup Daisy Chain Id: Enter 0 (Host) 0 (Host) 1 (Device) Place: End Daisy Chain Id: 0 (Host ) Enter Place: Middle Middle End Enter HP Monitored PDU User's Guide P-164000281-Rev 1 44 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 51
Daisy Chain Settings Enter Discovery No device Enter chained ESC ESC Enter Figure 43. Example Daisy Chain PDU Discovery (Not Communicating) HP Monitored PDU User's Guide P-164000281-Rev 1 45 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 52
Factory Return to Enter Factory Enter Settings? Yes No ESC Figure 45. Example Factory Submenu Displays Factory Confirm... OK Cancel Enter HP Monitored PDU User's Guide P-164000281-Rev 1 46 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 53
.xx. x.xxx Enter PDU Info IPv6 address xxxx:xxxx:xxxx:xxxx xxxx:xxxx:xxxx:xxxx Figure 46. Example PDU Info Display HP Monitored PDU User's Guide P-164000281-Rev 1 47 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 54
47). This section describes the functions provided by this interface. 1 2 3 10 4 9 8 5 7 6 Figure 47. Navigating the Web Interface (PDU Overview Opening Page) HP Monitored PDU User's Guide P-164000281-Rev 1 48 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 55
is exceeded: Active Alarms Present High Critical Threshold Alarm High Warning Threshold Alarm Low Warning Threshold Alarm Low Critical Threshold Alarm HP Monitored PDU User's Guide P-164000281-Rev 1 49 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 56
examples shown represent typical data displays reported from a single model. NOTE 3 The Web interface supports Microsoft Internet Explorer 8.0 and greater, Firefox (installed on Linux or Windows), and Google Chrome the default password is "admin." HP Monitored PDU User's Guide P-164000281-Rev 1 50 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 57
the Settings button on any power management page displays a separate window that allows you to change settings, such as alarm thresholds. HP Monitored PDU User's Guide P-164000281-Rev 1 51 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 58
: The Date & Time page allows you to select the date format and set the date and time, either manually or by synchronizing with the NTP (Network Time Protocol) server. You can set the time zone and have the the specified LDAP servers on this page. HP Monitored PDU User's Guide P-164000281-Rev 1 52 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 59
be changed at the first connection. If the administrator loses the password or login, contact your service representative to recover it. Only one user can be the SuperUser Administrator. This defaults to the and Date and Time Settings menu HP Monitored PDU User's Guide P-164000281-Rev 1 53 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 60
, and LDAPsettings. l Cannot upload the communication module configuration file or upgrade the firmware l Cannot change his profile or another user's account HP Monitored PDU User's Guide P-164000281-Rev 1 54 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 61
voltage warning threshold l High critical voltage threshold 7. To reset the threshold values to the default values, click Default, then click Save. HP Monitored PDU User's Guide P-164000281-Rev 1 55 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 62
zero, click Reset Max Power, then click Save. 10. To cancel this action and return to the Groups page, click Cancel. HP Monitored PDU User's Guide P-164000281-Rev 1 56 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 63
to the default values, click Default, then click Save. 8. To cancel this action and return to the Environment page, click Cancel. HP Monitored PDU User's Guide P-164000281-Rev 1 57 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 64
. NOTE For daisy-chained PDUs: l PDU type 00 indicates the host PDU logs. l PDU type 01 indicates the device PDU logs. HP Monitored PDU User's Guide P-164000281-Rev 1 58 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 65
and the trap receiver protocol must match the configured SNMP version. NOTE See "Enable/Disable the SNMP Agent" on page 68. HP Monitored PDU User's Guide P-164000281-Rev 1 59 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 66
mail without the event log file. 8. Select the date of the next report using the date picker or manually enter the date in mm/dd/yyyy format. 9. Set the frequency of the report if this recipient down list. The Users Settings dialog displays. HP Monitored PDU User's Guide P-164000281-Rev 1 60 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 67
the Web interface. l PDU User: The administrator assigns this remote group either read only or read-write privileges to this user. HP Monitored PDU User's Guide P-164000281-Rev 1 61 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 68
box to use the firmware upgrade functionality (default). l Disabled: Uncheck the check box to disable the firmware upgrade functionality. 4. Click Save. HP Monitored PDU User's Guide P-164000281-Rev 1 62 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 69
Upgrade network management card. A pop-up confirmation message displays: Are you sure you want to upgrade the Network Management Card? Please refer to the User's Manual for the upgrade procedure. Note: This will NOT restart the PDU or change the power status of the outlets. HP Monitored PDU User - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 70
Global Settings panel, choose the date format from the drop-down list. 4. Click Save. 5. Click the Set manually radio button. 6. Type the date according to the format defined by Date Format, or select the date using , ss = second. 8. Click Save. HP Monitored PDU User's Guide P-164000281-Rev 1 64 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 71
list: l Auto-negotiation l 100 Mbps Full Duplex l 10 Mbps Half Duplex l 10 Mbps Full Duplex l 10 Mbps Half Duplex 4. Click Save. HP Monitored PDU User's Guide P-164000281-Rev 1 65 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 72
are configured by the DHCP server. If DHCP is enabled, go to Step 5. l Disabled. The IPv4 settings are manually configured by the user. If DHCP is disabled, perform the following: - Type the IPv4 address. - Type the 5. Type the local IPv6 address. HP Monitored PDU User's Guide P-164000281-Rev 1 66 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 73
SMTP Server Authentication check box. l Type the login. l Type the password. l If not already provided, type the sender address. 6. Click Save. HP Monitored PDU User's Guide P-164000281-Rev 1 67 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 74
: only SNMPv1 users and SNMPv1 traps are supported. l SNMPv3: only SNMPv3 users and SNMPv3 traps are supported. l SNMPv1 & v3: both SNMPv1 and SNMPv3 users and traps are supported. 4. Type the SNMP Port number and with 8 to 24 characters allowed. HP Monitored PDU User's Guide P-164000281-Rev 1 68 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 75
submenu in the Settings menu. In the Network Management Card panel, click Restart network management card to restart the communications module. HP Monitored PDU User's Guide P-164000281-Rev 1 69 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 76
submenu in the Settings menu. In the Network Management Card panel, click Restart network management card to restart the communications module. HP Monitored PDU User's Guide P-164000281-Rev 1 70 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 77
group. 4. The resulting required field entries are active and highlighted. Type the associated values in the active entry boxes. 5. Click Save. HP Monitored PDU User's Guide P-164000281-Rev 1 71 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 78
in the Server, Port, and Time Out (sec) entry boxes. 6. Click Save. Otherwise, click Cancel to return to the LDAP page. HP Monitored PDU User's Guide P-164000281-Rev 1 72 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 79
Communication Configuration" on page 22 for more information creating a serial connection and configuring the network. Supported Commands The PDU CLI command set for managing and monitoring the PDU includes the following commands: can be sent. HP Monitored PDU User's Guide P-164000281-Rev 1 73 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 80
new value set [name] [value] PDU#0> Example 2 PDU#0>pdu ? Usage: select the strapping pdu unit to focus on pdu [number] PDU#0 HP Monitored PDU User's Guide P-164000281-Rev 1 74 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 81
or a family of objects. Example pdu#0>info System.Network.DHCP Name Unit ---- ---- System.Network.DHCP RO/RW ----RW Type ---0: Disabled 1: Enabled HP Monitored PDU User's Guide P-164000281-Rev 1 75 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 82
CLI PDU#0>quit Example with serial interface PDU#0>quit Session closed Example with network interface PDU#0>quit Connection to host lost. HP Monitored PDU User's Guide P-164000281-Rev 1 76 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 83
an array PDU#0>get . NOTE Values are separated by the pipe character ( | ). Example pdu#0>get System.User[x].SecurityRight 0|0|0|0|0|0|0|0 pdu#0> HP Monitored PDU User's Guide P-164000281-Rev 1 77 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 84
1 System.DaisyChain.Position 0 System.DaisyChain.Status 0 System.DaisyChain.Count 1 pdu#0> Example 2 pdu#0>get System.* System.NetworkManagementSystem.Count 8 System.NetworkManagementSystem[x].HostName ../.. pdu#0> HP Monitored PDU User's Guide P-164000281-Rev 1 78 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 85
the HID object and is obtained with a get command Example pdu#0>set System.Network.SNMP.V3.User[1].Name User 1 User 1 pdu#0> HP Monitored PDU User's Guide P-164000281-Rev 1 79 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 86
the pipe character ( | ). Example pdu#0>set System.Network.SNMP.V3.User[x].Name User 1|User 2|User 3|User 4 User 1|User 2|User 3|User 4 pdu#0> HP Monitored PDU User's Guide P-164000281-Rev 1 80 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 87
Serial Interface Operation pdu command Use this command to reset a daisy-chained PDU as the Host or Device. Usage PDU#0>pdu where: = 0 for the host; 1 for the device Example pdu#0>pdu 1 pdu#1> HP Monitored PDU User's Guide P-164000281-Rev 1 81 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 88
State[0] or [1].Level 0: Alarm not active 1: Alarm active Ex: State=0 AND State[0].Level=3 then Alarm=1 Dry Contact state - RO 0: Open 1: Close HP Monitored PDU User's Guide P-164000281-Rev 1 82 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 89
poles is combined. s RO s RO Nominal Amps: 10A, 16A, 20A, .. mA RO This is useful for both breaker and outlet section. HP Monitored PDU User's Guide P-164000281-Rev 1 83 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 90
the pole: 1, 2, or 3. - RO Ratio of active power / apparent power provided by the pole of the breaker or outlet section. m% RO HP Monitored PDU User's Guide P-164000281-Rev 1 84 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 91
CT, current is max of 2 pole measures) 3: Section of outlets (with 2 measurement, 2nd method of wiring CT, current is sum of 2 HP Monitored PDU User's Guide P-164000281-Rev 1 85 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 92
Line 1 Ratio of active power / apparent power provided by the phase. m% RO Value 0 to 100 for Cos PHI = 0.00 to 1.00 HP Monitored PDU User's Guide P-164000281-Rev 1 86 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 93
does not put 0 s RW in the counter, but it saves the current value of Energy timer into the data ...Reset.Energy. HP Monitored PDU User's Guide P-164000281-Rev 1 87 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 94
. - RO 1 to 56. Phase ID that powers the outlet: - RO - 1, 2, 3 to identify a simple phase. - 12, 23, 31 to identify a composed phase. HP Monitored PDU User's Guide P-164000281-Rev 1 88 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 95
firmware. Serial Number. F/W Version. Unit Access - RO - RO - RO s RO W RO mA RO V RO - RO - RW - RO - RO - RO - RO - RO HP Monitored PDU User's Guide P-164000281-Rev 1 89 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 96
RW RW RO RW RW RO RO RO Default Value "" 0 "" 1 1 0 0 1 "00:00:00:00:00:00" admin DaisyChainPosition 0: Middle 1: End RO 0 HP Monitored PDU User's Guide P-164000281-Rev 1 90 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 97
:00" 0: Auto Negotiation RW 0 1: 100 Mbps Full Duplex 2: 100 Mbps Half Duplex 3: 10 Mbps Full Duplex 4: 10 Mbps Half Duplex WO 0 HP Monitored PDU User's Guide P-164000281-Rev 1 91 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 98
RW 443 RW "192.168.123.123" RW "" RW "255.255.0.0" RW "" RO "" 0: Disabled RW 0 1: Enabled RW "" 0: Disabled RW 0 1: Enabled RO "" HP Monitored PDU User's Guide P-164000281-Rev 1 92 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 99
String:31 String:31 Integer1to65535 Integer1to65535 Description 0: Invalid 1: Valid 2: Manual Configuration 0: Simple 7: Digest MD5 0: No Authorization 1: By User "" 2 0 389 "LDAP Server1|LDAP Server2" 10 0 0 "" "" "" 0 0 "" "" 0 "" "" "" 25 161 HP Monitored PDU User's Guide P-164000281-Rev 1 93 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 100
1|SNMPv3 User 2|SNMPv3 User 3|SNMPv3 User 4" RW "|||" RW "|||" RW 0 RW 0 RW 22 RW 1 RW 23 RW 0 RO NB_TRAP_RECEIVE RS RW 0 RW "|||||||" HP Monitored PDU User's Guide P-164000281-Rev 1 94 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 101
mm/dd/yyyy 2: dd/mm/yyyy 3: yyyy-mm-dd 4: dd mm yyyy 0: Manual 1: Sync NTP System.User[x].Password admin Password:15 Access Default Value RW "Trap Receiver 1| 2|Account 3|Account 4|Account 5|Account 6|Account 7|Account 8" RW "|||||||" HP Monitored PDU User's Guide P-164000281-Rev 1 95 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 102
2: PDU User 3: Outlet User 0: No Access 1: Read-Only 2: Read/Write 0: Disabled 1: Enabled 0: local 1: remote Access Default Value RW 0 RW 0 RW 0 RW 0 HP Monitored PDU User's Guide P-164000281-Rev 1 96 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 103
the PDU at an ambient temperature of 25°C (77°F). NOTE The PDU does not contain any serviceable parts. Equipment Disposal Contact your local recycling or hazardous waste center for information on proper disposal of the firmware and the Web pages. HP Monitored PDU User's Guide P-164000281-Rev 1 97 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 104
(see Figure 50). 8. In the Network Management Card panel, check Firmware upgrade enabled and click Browse to find the upgrade file. HP Monitored PDU User's Guide P-164000281-Rev 1 98 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 105
completed. When completed, an upgrade message displays F/W: 100%, and the communications module reboots with the new firmware and new Web pages. HP Monitored PDU User's Guide P-164000281-Rev 1 99 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 106
the upgrade (see Figure 51). Figure 51. Launching the Upgrade 5. Then the upgrade finishes, the closing message displays (see Figure 52). HP Monitored PDU User's Guide P-164000281-Rev 1 100 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 107
LCD interface information, see "Active Alarms Menu" on page 39. For Web interface information, see "Web Interface Operation" on page 48. HP Monitored PDU User's Guide P-164000281-Rev 1 101 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 108
or event. The remaining five digits in the number code further identify and define the type of alarm (see Figure 54). HP Monitored PDU User's Guide P-164000281-Rev 1 102 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 109
Code 0 or 1 (OS or System) ! IMPORTANT For Type Code 0 and Type Code 1, always contact customer support for assistance. These errors are not user-correctable. The Type Code 0 and Type Code 1 alarms and events are bus is too great Command unknown HP Monitored PDU User's Guide P-164000281-Rev 1 103 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 110
. Type 2 alarms and events also provide the state of optional connected equipment. Type 3 alarms and events are triggered from user actions. HP Monitored PDU User's Guide P-164000281-Rev 1 104 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 111
the low temperature critical threshold. The temperature level reading is greater than the value configured as the high temperature warning threshold. HP Monitored PDU User's Guide P-164000281-Rev 1 105 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 112
(A) reading is greater than the value configured as the over current critical alarm threshold. No section voltage threshold has been triggered. HP Monitored PDU User's Guide P-164000281-Rev 1 106 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 113
specified user logged in by FTP. The specified user logged out by FTP. The specified user failed to log by FTP. HP Monitored PDU User's Guide P-164000281-Rev 1 107 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 114
-240V/346-415V wye 3Ph 24 outlets NA/JP mPDU HP 19.9 kVA 277/480V wye 3Ph 30 outlets NA mPDU HP Monitored PDU User's Guide P-164000281-Rev 1 108 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 115
L5-30 L6-30 C20 SEE NOTE C13 Outlets 12 16 C19 Outlets - - - 5-20R Outlets 12 - - RF-203P-HP (LS26) Outlets - - - HP Monitored PDU User's Guide P-164000281-Rev 1 109 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 116
32 24 16 24 48 16 Capacity (VA) 2880 4992 3680 3680 4992 7360 8320 7360 8646 5764 8646 17293 11040 HP Monitored PDU User's Guide P-164000281-Rev 1 110 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 117
IEC/EN 60934 UL 489 - UL 489 UL 489 - IEC/EN 60934 - UL 489 UL 489 IEC/EN 60934 UL 489 HP Monitored PDU User's Guide P-164000281-Rev 1 111 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 118
input current is greater than 16A) IEC 61000-4-2; IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11 HP Monitored PDU User's Guide P-164000281-Rev 1 112 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 119
for this product, always refer to the RMN. The RMN is not the marketing name or model number of the product. HP Monitored PDU User's Guide P-164000281-Rev 1 113 - HP 8.3kVA 208 Volt CS8265C Input 30xC13/3xC19 | HP Monitored Power Distribution - Page 120
detected. For more information, see the HP iLO 4 User Guide or HP Intelligent Provisioning User Guide on the HP website (http:// www.hp.com/go/ilo a Care Pack (service upgrade), see the Support & Drivers website (http:// www8.hp.com/us/en/support-drivers.html). If the problem cannot be resolved at
Part Number: 745293-001
September 30, 2013
Edition: 1
HP Monitored PDU
HP Monitored Power Distribution Unit
User’s Guide
Abstract
This document is for the person who installs and maintains HP PDU products. HP assumes you are qualified in the
installation of electrical equipment and trained in recognizing hazards in products with hazardous energy levels.