    HP NetServer LXr 8500 Rack Assembly and Cabling Reference Guide HP Part Number D7054-90015 Printed September 1999
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 2
    Cupertino, CA 95052-8059 USA © Copyright 1999, Hewlett-Packard Company. Audience Assumptions The guide is for the person who installs, administers, and troubleshoots LAN servers. Hewlett-Packard Company assumes you are qualified in the servicing of computer equipment and trained in recognizing
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 3
    Routing Cables to the LXr 8500 27 Step 1: Prepare to Cable the HP NetServer LXr 8500 27 Assess How Components Will be Connected to the Server 27 Attach Cable Guide to Rack Column 27 Mount the Cable Management Arm 27 Mount Power Distribution Units 28 Step 2: Connect the LXr 8500 Data Cables to
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 4
    the Server 30 Attach Data Cables to Other Components 32 Step 3: Cable the LXr 8500 for Power 32 Attaching Server and Component Power Guides 42 Route and Tie Cables into the Management Arm 42 Step 5: Powering Up and Powering Down the Components in the Rack....... 45 Power Up Sequence 45 Power
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 5
    to use in this process, see Appendix A. For instructions on how to install the HP NetServer LXr 8500 in a rack, consult the Installation Road Map shipped with your rack or the Installation Guide shipped with your NetServer unit. NOTE For instructions on how to assemble other components in a rack
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 6
    for Cabling the HP NetServer LXr8500 Figure 1-1. The HP NetServer LXr 8500 Site Preparation You may want to copy and use the site preparation checklist in this section (Table 1-1). Doing so before you begin to install and cable the NetServer may reveal actions you can take to support your success
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 7
    HP NetServer General Guidelines Logical and physical network design provided Server configuration parameters determined Disk partition and directory structure determined Required incoming power NetServer rack is to be installed is level Assess floor strength and ensure it is sufficient to support
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 8
    so on Valid, supportable configuration for added devices, interfaces, memory, and so forth Correct type and length of cables, as specified in order documents Site Preparation -- Circuit Breakers When you connect the HP NetServer LXr 8500 to an AC power source, the server temporarily draws a large
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 9
    Chapter 1 Preparation for Cabling the HP NetServer LXr8500 If you install several HP NetServers on one circuit, however, precautions are necessary. For instance, if there is a power failure and power is then restored all the servers immediately begin to draw inrush current at the same time. If the
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 10
    Cabling the HP NetServer LXr8500 Prevent shock hazard by disconnecting power and telephone cords when you service or install components. Prevent static-dissipating work surface connected to the server chassis when handling printed circuit boards, memory devices, and processor chips or modules.
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 11
    units without help. Also, remove power supplies and hard disk drives to minimize the amount of weight to be lifted. Compare the order documents to the packing list or to a list of boxes received. Check to see that all parts are present. Unpack the HP NetServer and external storage and tape backup
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 12
    for Cabling the HP NetServer LXr8500 3. instructions from the supplying organization first, if you have them. Otherwise, continue with this set of instructions rack enclosure, server, mass storage units, and other components. Stage cartons a few feet from your assembly and final power-up location.
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 13
    the HP NetServer LXr8500 WARNING a time. Reduce weight by removing power supplies and hard disk drives from servers. Always use the rack mounting handles upward). Each package contains rack installation instructions or a user guide. NOTE If an Uninterruptible Power Supply (UPS) is included, plug
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 14
    to be used, install it following instructions which accompany the unit. NOTE Most HP NetServers have an internal fan system. However, rack doors must be perforated (front and/or rear). In this case, you do not need an extractor fan. 2. If an Uninterruptible Power Supply (UPS) is used, install the
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 15
    HP NetServers and mass storage units have instructions in their user or installation guides for mounting the units in the rack enclosure. For other servers and storage units, rack mounting instructions have installed the UPS, Redundant Switch, and Power Distribution Units. Do so now if you have
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 16
    rack, replace disk drives and power supplies and add the front panel (bezel) to the unit. 6. Proceed with units one by one, from the bottom of the rack to the top. Fill any gaps with filler panels. 10. Connect and Route Cables NOTE Illustrated information about cabling the HP NetServer LXr 8500 in
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 17
    1 Preparation for Cabling the HP NetServer LXr8500 • Determine configurations for and mount the PDU (Power Distribution Unit or Units). Connect the LXr 8500 Data Cables to Peripheral Components • Plan where data connections are to be made. • Attach data cables to the server. Mark the ends of data
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 18
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 19
    208 or 230/240 VAC. Power supply (UPS) and distribution (PDU) components are available to support these configurations. A Redundant Switch is also available. Details of power considerations for the HP NetServer LXr 8500 include: ◊ the appropriate power cord for each server is shipped according to
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 20
    and receptacles for the two rack power supply subsystems for the HP NetServer LXr 8500. Table 2-1. UPS Models and Power Ratings Uninterruptible Power Supplies (UPS) Available APC Model NS3000RMT3U NS2200RMI3U NS3000RMI3U Power (VA)1 3000 2200 3000 Power (Watts)2 2250 1600 2250 Note 1. Ensure
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 21
    NS3000RMI3U SU044-1, C20 inputs, country-specific C19 cords, and E7804A, 4 m, C20 to C19 jumper cord to PDU4 SU044-1, C20 inputs, country-specific C19 cords, and E7804A, 4 for 13-amp loads, and limits the PDU to 13 amps of total supply. Note 3. The circuit load should be limited to 3000 VA when this
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 22
    Power Distribution Units Two types of Power Distribution Units (PDU) are currently available for the LXr 8500, as follows: ◊ The wide-range 200/240 VAC PDU (HP -amp unit with its 10-amp extension and jumper cable, order HP part number E7672A.) NOTE The extension PDU (E7670A) only increases the
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 23
    HP NetServer Rack Storage/12 or /12FC Horizontal Mounting Not Recommended Power Distribution Unit Types Interferes with HotSwappable Power Supplies Interferes with HotSwappable Power Supplies Interferes with HotSwappable Power Supplies Interferes with HotSwappable Power Supplies Mechanically
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 24
    Mounting of Two PDUs in a Fully Utilized Rack Cable Guides Mounted on the Column Across from the Door Hinges Examples of Data Cable Routes from Server to Connectors on Other Components 200-240 VAC WideRange 10-Amp, 19-Inch Power Distribution Unit, Installed Horizontally Behind the Monitor
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 25
    Note 3 The 10-amp PDU can be ordered as an accessory using part number E7670A. The cord that connects it to the 16-amp PDU first is exceeded. 3. One 16-amp PDU is supplied for each Uninterruptible Power Supply (UPS) in a rack. 4. (a) When several HP Rack Storage/8 or Rack Storage/12 units are in
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 26
    Component Receptacles Required HP NetServer LXr 8500 HP Rack Storage/12 All other devices one C19 two C13 or use Y-Cable* one C13 * Two Y-Cables may be used to connect two HP Rack Storage/8 or Rack Storage/12 units to two C13 receptacles. Power and Current for Estimating Supply Needs When
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 27
    Table 2-6. 208 VAC Power and Current: Approximate Requirements of Rack Optimized Devices and Components Device (Notes 1, 2, 3) HP NetServer LXr 85004 HP NetServer LPr HP NetServer LXr 80004 HP NetServer LH 4r HP NetServer LH 3r HP NetServer LXr Pro8 HP NetServer LXr Pro HP Fibre Channel Hub D6976A
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 28
    2-7. 230/240 VAC Power and Current: Approximate Requirements of Rack Optimized Devices and Components Device (Notes 1, 2, 3) HP NetServer LXr 85004 HP NetServer LPr HP NetServer LXr 80004 HP NetServer LH 4r HP NetServer LH 3r HP NetServer LXr Pro8 HP NetServer LXr Pro HP Fibre Channel Hub D6976A
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 29
    HP NetServer can be extended for service by trained personnel • power supplies and distribution units supplied with the rack assembly can meet requirements for power, current, and number of receptacles Cable Guide the server. And this in turn depends on Cable Guide placement. • Cable Guide placement
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 30
    the servers and connected devices provide for the Cable Management Arm (for the LXr 8500). Cooling Requirements for the LXr 8500 The HP NetServer proper cooling. Because of the high capacity fans installed in the HP NetServer LXr 8500, no external exhaust fan is needed with this unit. The rack must
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 31
    Power Distribution Units as noted below. See Figure 2-2 for an example illustration showing how these three items may look when mounted.. Attach Cable Guide to Rack Column Using the instructions included, attach the two Cable Guides to the rack column. Mount the Cable Management Arm The HP NetServer
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 32
    PDU Configurations," particularly Table 2-4. Follow mounting instructions included with your power distribution units. Notice these cannot be HP NetServer Navigator to configure your server. Figure 3-2 shows a similar set-up for the Rack Storage/12FC. See the HP NetServer LXr 8500 Installation Guide
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 33
    for configuring the system, but is shown for informational purposes. The configuration in Figure 3-1 requires 2 UPS (power supplies) and 2 PDU (power strip) units at both 208 V and at 230/240 V. Figure 3-2 shows an HP NetServer LXr 8500 connected in Dual Active Mode to a Rack Storage/12FC. 29
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 34
    the HP NetServer LXr 8500 to the Rack Storage/12FC NOTE The configuration in Figure 3-2 requires 2 UPS (power supplies) and 2 PDU (power strip) units at both 208 V and at 230/240 V. For more information on data cabling with the Rack Storage/12FC, see the HP Rack Storage/12 FC Installation Guide
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 35
    connections from hubs, routers and other sources and connect their cables to corresponding server connectors. 3. Locate the cable that will attach the serial port on the Uninterruptible Power Supply (UPS) (if present) and plug the server end in. 4. Attach the video cable to the video port on the
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 36
    component (such as the UPS or video monitor) and its associated server. Guidelines used by rack configuration tools in generating rack layouts take possible distance limitations into account. Check power and data cords supplied with peripherals to ensure you have cables that are long enough to
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 37
    balancing loads on the Power Distribution Unit are shown in Tables 2-6 and 2-7. If applicable, use two circuits (each including a Power Distribution Unit and an optional Uninterruptible Power Supply) in one rack , does not exceed 16 amperes. Add more PDU-UPS circuits to support higher loads. 33
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 38
    Facing Inward DLT Library Mass Storage Unit (Two Inlets) HP NetServer LXr 8500 Mass Storage Unit (Two Inlets) Figure 3-4. Power Connection Locations on a Typical Rack (Rear View) 208V PDU Rack Power Configurations The 208 VAC PDU power configurations appear as shown below in Table 3-1 and Figure
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 39
    Power Configurations In the 208 VAC case, without a UPS, make sure your power system has the capacity to support the power and current needs of the components you will power VAC PDU Model E7671A or E7672A Power (VA) N/A Power (W) N/A Current (A)2 max 16 HP NetServer D7057A, 500 MHz, 512K Cache
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 40
    and Routing Cables to the LXr 8500 Recommended 208 VAC Power Configuration for the LXr 8500 HP NetServer LXr 8500 Uninterruptible Power Supply Captive L6-20P Cord Rack Mass Storage Unit Jumper Cable Supplied with NetServer Jumper Cables Supplied with Mass Storage Units Cable Orderable for 16-Amp
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 41
    will allow the full 16A rating of the PDU to be used. For use with 230/240 VAC power mains, direct connection to a junction box is usually necessary. In this case, an unterminated power cord is supplied. Be sure to obey all local electrical code requirements when connecting to the site electrical
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 42
    240 VAC PDU Power and Current Component1 Model Power Power Current (VA) (W) (A)2 208 VAC PDU E7671A or E7672A N/A N/A max 16 HP NetServer D7057A, 500 MHz shows a UPS connected to the power mains through an attached power cord (appropriate cords are supplied for each country). The UPS has
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 43
    Cables to the LXr 8500 Recommended 230/240 VAC LXr 8500 Configuration HP NetServer LXr 8500 Uninterruptible Power Supply Mass Storage Unit Jumper Cable Supplied with NetServer Jumper Cables Supplied with Mass Storage Units Captive Unterminated Cord to be Terminated Locally Cable Orderable
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 44
    Chapter 3 Procedure for Connecting and Routing Cables to the LXr 8500 shows two LXr 8500 units powered by two PDUs and two UPS units. Plugging each UPS into a different branch circuit ensures dual power supply is maintained. Figure 3-7. Dual Power Supply 40
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 45
    in Figure 3-8. For this example, one 41EIA Unit Rack (a 2-meter HP Systems or HP System/E rack) is completely filled with power supplies, servers, and storage units. Two mass storage units "sandwich" each NetServer. Branch Circuit A Branch Circuit B Figure 3-8. High Density Configuration, Block
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 46
    and the Cable Guides The HP NetServer LXr 8500 has a single power input cable, but multiple connections to I/O adapters in the PCI slots. Because power and data cables are supplied only in one length, measures are necessary to manage the cables attached to the rear of the server. A Cable Management
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 47
    the Server all the way in B. Plug power and data cables into the back of the Server F. Drape cables through the fingers of the Cable Guide E. Secure cables in the cable arm using the hook-and-loop cables supplied with the NetServer. 3. With the cable arm still in the unextended position, place
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 48
    LXr 8500 WARNING Before sliding the HP NetServer LXr 8500 out of the rack, NetServer out by grasping the handle below the LCD control panel. To PCI Boards Extend the Cable Management Arm to ensure you have enough cable before routing cables through the Cable Guide Figure 3-10. Extend the Server
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 49
    are properly warned. No specific order is necessary when powering off rack-optimized servers and associated components. However, to do so in an orderly way, you should bring down the operating system, then power off peripherals, then turn off servers. WARNING The HP NetServer LXr 8500 is connected
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 50
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 51
    . Mount the rack power subsystem, HP NetServer, HP Mass Storage Units, and peripheral equipment in the rack. Use instructions which come with them to mount the Power Distribution Unit(s) and the Cable Guides, and follow instructions in the HP NetServer LXr 8500 Installation Guide to mount Cable
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 52
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 53
    B Considerations in Mounting the Redundant Switch Table B-1 shows the Redundant Switch in four possible configurations. The illustrations which follow the table show 208 VAC configuration wiring diagrams and illustrate the Redundant Switch mounted in the HP Rack Systems/E. 49
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 54
    : 230/240V Mains Application with UPS SU 044-1 Application with No UPS SU 044-1 2 Detachable Power Cords, Country Specific NS3000RMI3U or NS2200RMI3U2 E7804A, 4m, C20 to C19 2 Detachable Power Cords, Country Specific Not Used Not Used Not Used E7804A, 4m, C20 to C19 3000 VA 3000 VA Note
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 55
    Appendix B Considerations in Mounting the Redundant Switch UPS Jumper Cord, L6-20P to C-19 Captive UPS Cord with L6-20P connects to L6-20R on Redundant Switch SKU 045-1 Switch Branch Circuit A Branch Circuit B Captive Cords, with L6-20P Cord Ends Figure B-1. 208 VAC Configuration of Redundant
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 56
    Appendix B Considerations in Mounting the Redundant Switch Note that switches of 230/240 VAC can be mounted in the same way as the 208 VAC models shown. See Table B-1. Figure B-3. Two UPS and Two Redundant Switches in a Rack 52
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 57
    to server, 30 overview, 28 dual power supply configuration, 40 E electrical current requirements 200/208 VAC table of devices, 23 230/240 VAC table of devices, 24 F fan not required for perforated doors, 10 H high density configuration, 41 HP Console Switch use with LXr 8500, 28 HP NetServer LXr
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 58
    unit at a time, 9 leveler feet, 8 lifting precautions, 8 moving racks safely, 8 preventing component damage, 6 rear latch removal, 10 remove power supplies and disk packs, 9 use attached rack mounting handles, 9 Safety rack cabling, 5 shipment to a second location packaging materials, 7 remove and
  • HP D5970A | HP Netserver LXr 8500 Rack Cabling Guide - Page 59
    Index W wide ranging switchless power units, 21 55
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59

HP NetServer LXr 8500
Rack Assembly and Cabling
Reference Guide
HP Part Number D7054-90015
Printed September 1999