Site Preparation Guide HP Integrity Superdome/sx2000 and HP9000/sx2000 Servers HP Part Number: A9834-9003D Published: November 2007 Edition: Fourth Edition - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 2
to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 3
...9 Typographic Conventions...9 Related Information...9 Publishing History...10 HP Encourages Your Comments...10 1 System Specifications 11 Dimensions Power Options...13 System Power Requirements...14 Component Power Requirements 15 IOX Cabinet Power Requirements 15 IOX Cabinet Power - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 4
4 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 5
List of Figures 1-1 1-2 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 PDCA Locations...14 Airflow Diagram...19 Cable Cutouts and Caster Locations 21 SD16 and SD32 Space Requirements 22 SD64 Space Requirements...23 Computer Floor Template...24 Computer Floor Template...25 Computer - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 6
6 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 7
15 1-12 I/O Expansion Cabinet ac Power Cords 16 1-13 Operational Physical Environment Requirements 16 1-14 Nonoperational Physical Environment Requirements 16 1-15 HP Integrity Superdome/sx2000 Dual-Core CPU Configurations 17 1-16 HP Integrity Superdome/sx2000 Single-Core CPU Configurations 17 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 8
8 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 9
is represented using this font. • Text to be replaced with text that you supply is represented using this font. Example: "Enter the ls -l filename command" means can find other information on HP server hardware management, Microsoft® Windows®, and diagnostic support tools at the following Web sites - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 10
diagnostics and event monitoring tools. This site has manuals, tutorials, FAQs, and other reference material. Website for HP Technical Support: http://us-support2.external.hp.com The HP IT resource center website provides comprehensive support information for IT professionals on a wide variety of - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 11
for optional IOX cabinets. NOTE: To determine the weight of the Support Management Station (SMS) and any console used with this server, see the related documents. Table 1-3 System Component Weights Component Chassis1 Cell board without power board and DIMMs Weight Per Unit (lb/kg) 745.17/338 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 12
/30.88 DIMMs 0.20/0.09 256 51.20/23.04 Bulk power supply 3.83/1.74 6 23.00/10.44 PDCA 26.00/11.80 2 52.00/23.59 I/O card cage 36.50/16.56 4 146.00/66.24 I/O cards Fully configured server (SD32 cabinet) 0.45/0.20 48 1 21.60/9.80 1354.65/614 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 13
circuit breaker to support the Marked Electrical current of 44 A per phase. The facility electrician and local service codes determine proper earlier Superdome systems. Table 1-6 Available Power Options Option Source Type Source Voltage (Nominal) PDCA Input Current Per Power Receptacle Required - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 14
two PDCAs, however, the rotation must be consistent for both. Figure 1-1 PDCA Locations PDCA 1 PDCA 0 System Power Requirements Table 1-8 and Table 1-9 list the ac power requirements for an HP Integrity Superdome/sx2000 system. These tables provide information to help determine the amount of ac - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 15
Nominal input voltage Input voltage range (minimum to maximum) Frequency range (minimum to maximum) Number of phases Marked electrical input current Maximum inrush current Power factor correction Value 200/208/220/230/240 V ac rms 170-264 V ac rms 50/60 Hz 1 16 A 60 A (peak) 0.95 minimum Table - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 16
(number of cell boards, amount of memory per cell, and number of I/O chassis) for the HP Integrity Superdome/sx2000. The table contains two columns of power numbers expressed in watts. The Breaker Power column lists the power used to size the wall breaker at the installation site. The Typical - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 17
. The protective earth (PE) ground wire is not switched. Table 1-16 HP Integrity Superdome/sx2000 Single-Core CPU Configurations1 Cell (in cabinet) Memory (DIMMs I/O (fully per Cell) populated) 8 32 4 8 16 2 8 8 4 Typical Power (Watts) 9130 7260 7783 Cooling (BTU/Hr) 31181 24794 26580 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 18
Table 1-16 HP Integrity Superdome/sx2000 Single-Core CPU Configurations (continued) Cell (in cabinet) Memory (DIMMs I/O (fully per Cell) populated) Typical Power (Watts) Cooling (BTU/Hr) Breaker Power (Watts)2 8 8 2 6823 23302 8596 8 4 4 7260 24794 9147 8 4 2 6300 21516 7938 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 19
Airflow exit (2600 CFM) Airflow exit (300 CFM) Air flows front to rear (2750 CFM) A thermal report for the HP Integrity Superdome/sx2000 server is provided in Table 1-17 (page 19). Table 1-17 Physical Environmental Specifications Description Minimum Configuration Maximum Configuration Typical - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 20
1 Derate maximum dry bulb temperature 1oC/300 m above 900 m. 2 The system deviates slightly from front to top and rear airflow protocol. Approximately 5 percent of the system airflow is drawn in from the rear of the system. See Figure 1-2 (page 19) for more details. 3 See Table 1-15 (page 17) and - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 21
A Templates This appendix contains blank floor plan grids and equipment templates. Combine the necessary number of floor plan grid sheets to create a scaled version of your computer room floor plan. Templates Figure A-1 illustrates the locations required for the cable cutouts. Figure A-2 "SD16 and - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 22
Figure A-2 SD16 and SD32 Space Requirements 22 Templates - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 23
drawn to the same scale as the floor plan grid (1/4 inch = 1 foot). These templates show basic equipment dimensions and space requirements for servicing. The service areas shown on the template drawings are lightly shaded. Use equipment templates with the floor plan grid to define the location of - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 24
4. Cut out each template selected in step 3, then place it on the floor plan grid created in step 2. 5. Position pieces until the desired layout is obtained then fasten the pieces to the grid. Mark the locations of the computer room doors, air conditioning floor vents, utility outlets, and so on. - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 25
Figure A-5 Computer Floor Template Templates 25 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 26
Figure A-6 Computer Floor Template 26 Templates - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 27
Figure A-7 Computer Floor Template Templates 27 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 28
Figure A-8 Computer Floor Template 28 Templates - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 29
Figure A-9 SD32, SD64, and IOX Cabinet Templates Templates 29 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 30
Figure A-10 SD32, SD64, and IOX Cabinet Templates 30 Templates - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 31
Figure A-11 SD32, SD64, and IOX Cabinet Templates Templates 31 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 32
Figure A-12 SD32, SD64, and IOX Cabinet Templates 32 Templates - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 33
Figure A-13 SD32, SD64, and IOX Cabinet Templates Templates 33 - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 34
Figure A-14 SD32, SD64, and IOX Cabinet Templates 34 Templates - HP Integrity Superdome SX2000 | Site Preparation Guide, Fourth Edition - HP Inte - Page 35
emission specifications, 18 P power dissipation, 16-17 power options option 6, 13-14 option 7, 13, 14 power requirements I/O expansion cabinet, 15 system, 14 S shipping dimensions and weights, 12 space requirements computer room layout, 23 equipment footprint templates, 23 Superdome system air flow
Site Preparation Guide
HP Integrity Superdome/sx2000 and
HP9000/sx2000 Servers
HP Part Number: A9834-9003D
Published: November 2007
Edition: Fourth Edition