HP R/T2200 IEC-320-C14 HP Uninterruptible Power System T700 Models User Guide
HP R/T2200 IEC-320-C14 Manual
![]() |
View all HP R/T2200 IEC-320-C14 manuals
Add to My Manuals
Save this manual to your list of manuals |
HP R/T2200 IEC-320-C14 manual content summary:
- HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 1
HP Uninterruptible Power System T700 Models User Guide October 2002 (Second Edition) Part Number 215420-002 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 2
in this document is provided "as is" without warranty of any kind and is subject to change without notice. The warranties for HP products are set forth in the express limited warranty statements accompanying such products. Nothing herein should be construed as constituting an additional warranty - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 3
Guide Intended Audience ...vii Important Safety Information ...vii Symbols on Equipment...vii Symbols in Text...viii Text Conventions...viii Related Documents...viii Getting Help...viii Technical Support ...ix HP Modes of Operation ...2-3 Charging the Batteries ...2-3 Placing the UPS in Operate Mode - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 4
Avis Canadien)...A-3 Class A Equipment ...A-3 Class B Equipment ...A-3 European Union Notice...A-3 Japanese Notice ...A-4 China Taiwan Notice ...A-4 Battery Replacement Notice...A-5 Appendix B Electrostatic Discharge Grounding Methods...B-1 iv HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 5
Appendix C Specifications Physical Specifications ...C-1 Input Specifications ...C-1 Output Specifications...C-2 Overcurrent Protection...C-3 Battery Specifications ...C-3 Battery Runtime...C-3 Environmental Specifications ...C-4 Index HP Uninterruptible Power System T700 Models User Guide v - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 6
- HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 7
instructions for configuration, and reference information for operation, battery maintenance, and troubleshooting for the Uninterruptible Power System (UPS). Intended Audience This guide is intended for individuals requiring information about the use of HP UPSs. HP , and servicing to qualified - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 8
indicates complete titles of manuals or variables. Variables Instructions • HP UPS XR Products Power Cord and Options Reference Guide • Industry Standard Terminology Glossary These documents are located on the Power Products Documentation CD or at www.hp.com. Getting Help If you have a problem - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 9
This Guide Technical Support In North America, call the HP Technical Support Phone Center at 1-800-652-6672. This service is available 24 hours a day, 7 days a week. For continuous quality improvement, calls may be recorded or monitored. Outside North America, call the nearest HP Technical Support - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 10
network surge protection) • Power protection for loads up to 700 VA/500 W • Support for UPS power management software Communications Port The UPS includes a communications port for data overload protectors located on the UPS rear panel. HP Uninterruptible Power System T700 Models User Guide 1-1 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 11
the following. Table 1-1: UPS T700 Models UPS Model T700 NA Kit Part Number 204015-001 Unit Part Number 204016-001 T700 JPN 204015-291 204016-191 T700 H INT'L 204015-B31 204016 "Front Panel Controls and LED Indicators," in Chapter 2. 1-2 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 12
Rear Panels The rear panel configurations of the UPS are shown in Figures 1-2, 1-3, and 1-4. 12 3 7 4 5 6 Figure 1-2: Rear panel of T700 NA 1 Communications port 2 Voltage configuration DIP switches 3 Network Transient Protector 4 Four 5-15 receptacles 5 Power cord with NEMA 5-15 plug 6 Input - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 13
Overview 1 2 3 4 5 Figure 1-3: Rear panel of T700 JPN 1 Communications port 2 Network Transient Protector 3 Four 5-15 receptacles 4 Power cord with NEMA 5-15 plug 5 Input power receptacle (IEC-320) 6 Input overload protector 1-4 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 14
HP computer systems through comprehensive control of HP UPSs. Specifically, power management software performs the following: IMPORTANT: Not all UPSs are equipped to support hp.com. Warranties To back up the wide range of features offered with the UPS, HP , HP offers all instructions and labels. - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 15
Overview Pre-Failure Battery Warranty For specific information on the battery warranty, refer to the section, "Pre-Failure Battery Warranty," in Chapter 4. 1-6 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 16
troubleshooting the unit. NOTE: For installation considerations and procedures, refer to the instructions included with the UPS. Copies of this document can be downloaded from www.hp Battery/Low Battery Amber-UPS is running on battery power or battery is low. () 3 Bad Battery ( ) Red-Battery is - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 17
) or starts UPS powering the load. Site Wiring Fault Indicator The UPS T700 NA model features a Site Wiring Fault Indicator (1) located on the rear panel of the to Chapter 5, "Troubleshooting." 1 Figure 2-2: Site Wiring Fault Indicator 2-2 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 18
the UPS into service. IMPORTANT: The batteries charge to: • 90 percent of their capacity within 3 hours • 100 percent of their capacity within 24 hours Charge the batteries for at least 24 hours before supplying backup power to devices. HP Uninterruptible Power System T700 Models User Guide 2-3 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 19
. When the Utility LED remains illuminated solid green, power is available at the UPS output receptacles. IMPORTANT: If the UPS is running on battery power (no utility power is present), press and hold the On/Standby button (2) until the audible alarm sounds. 1 2 Figure 2-3: Placing the UPS in - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 20
power to the loads ceases. 1 2 Figure 2-4: Placing the UPS in Standby mode IMPORTANT: • While in Standby mode, the UPS maintains the charge on the batteries, but no power is available at the output receptacles. • The UPS remains in Standby mode until an alternate mode is selected, or until utility - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 21
the UPS batteries (rather than unplugging the UPS). • For the meaning of individual LEDs, refer to "Front Panel Controls and LED Indicators," in this chapter. • For information on what to do if the self-test detects a problem, refer to Chapter 5, "Troubleshooting." 2-6 HP Uninterruptible Power - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 22
a problem. For information on what to do if the UPS detects an alarm condition, refer to Chapter 5, "Troubleshooting." "Troubleshooting." • If a utility power failure caused the alarm (the Utility LED goes out or the On Battery/Low Battery HP Uninterruptible Power System T700 Models User Guide 2-7 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 23
and troubleshooting alarms. UPS Voltage Configuration DIP Switches The voltage configuration DIP switches located on the rear panel of the UPS T700 NA model (left) and UPS T700 H INT'L model (right) allow UPS voltage configuration parameter adjustment. IMPORTANT: The UPS T700 JPN model does not - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 24
. The X on the UPS rear panel of each unit also indicates that the DIP switch can be positioned On or Off. IMPORTANT: The UPS T700 JPN model does not include the rear panel voltage configuration DIP switch feature, since this model cannot be altered from the 100 V configuration setting - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 25
Configuration 12 12 12 12 12 UPS T700 NA Model Configuration Settings 21 110V X 120V X Figure 3-3: 110 V configuration 110V 120V 21 X X Figure 3-4: 120 V a suitable power outlet and press the On/Standby button to power up the UPS. HP Uninterruptible Power System T700 Models User Guide 3-3 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 26
of personal injury from the hazardous energy levels associated with UPS batteries. The maintenance and replacement of batteries must be carried out by an authorized service representative. WARNING: The UPS contains sealed lead-acid batteries. To reduce the risk of fire or chemical burns, take the - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 27
240791-001. CAUTION: Because of the short shelf life of the battery, avoid storing a battery spare as a backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep the stored batteries charged is implemented. 4-2 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 28
failure. Preparing the UPS Batteries can be replaced without powering down the UPS if the UPS is not supplying battery power to devices (utility battery bracket (2). 2 1 Figure 4-2: Removing the UPS front bezel and metal battery bracket HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 29
IMPORTANT: The batteries charge to 90 percent of their capacity within less than 3 hours. Allow the batteries to charge for 24 hours before using the UPS to supply backup power to devices. The load may not be fully protected for 24 hours. 4-4 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 30
before it actually fails. Specifically, the Pre-Failure Battery Warranty ensures that when customers receive notification from HP power management software that the battery may fail, the battery is replaced free of charge under the warranty. HP maintains the highest standards in the industry, as - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 31
warranty coverage is three years for parts. The warranty for the first year of ownership includes parts and labor. If battery spares are not available for a particular HP UPS model, then the entire UPS, including its battery, is replaced. 4-6 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 32
. Troubleshooting If problems occur when starting or using the UPS, refer to Table 5-1 for possible causes and suggested actions. Table 5-1: Troubleshooting Guide Symptom The UPS does not start and the Utility LED ( ) is not illuminated. An audible alarm is present. The UPS operates on battery - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 33
Table 5-1: Troubleshooting Guide continued Symptom Possible Cause The UPS does not provide the expected backup time. The battery may be fully discharged due to long term storage, frequent power outages, or end of battery life. The battery is disconnected. The On Battery/Low Battery LED - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 34
the batteries for 24 hours. Initiate a self-test. If the Bad Battery LED ( ) is still flashing, replace the batteries. Save your work and turn off the equipment. Turn off the UPS. Contact an authorized service representative. continued HP Uninterruptible Power System T700 Models User Guide 5-3 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 35
down the UPS. Contact an authorized service representative. Repairing the UPS Repairs to the UPS must be carried out by HP or an authorized service representative. Other than battery replacement, there are no UPS user-serviceable parts. 5-4 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 36
to bear a label indicating the interference potential of the device as well as additional operating instructions for the user. The rating label on the device shows the classification (A or B) to correct the interference at personal expense. HP Uninterruptible Power System T700 Models User Guide A-1 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 37
radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that may void the user's authority to operate the equipment. A-2 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 38
these directives implies conformity to the following European Norms (in brackets are the equivalent international standards): • EN50091-1 - UPS Product Safety Requirements • EN50091-2 - UPS EMC Requirements HP Uninterruptible Power System T700 Models User Guide A-3 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 39
Regulatory Compliance Notices Japanese Notice China Taiwan Notice A-4 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 40
about battery replacement or proper disposal, contact your authorized reseller or your authorized service provider. WARNING: The UPS contains a sealed lead-acid battery pack. return them to HP, your authorized HP Partners, or their agents. HP Uninterruptible Power System T700 Models User Guide A-5 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 41
on conductive floors or dissipating floor mats. • Use conductive field service tools. • Use a portable field service kit with a folding static-dissipating work mat. If you do with product installation, contact your authorized reseller. HP Uninterruptible Power System T700 Models User Guide B-1 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 42
. Topics also include battery descriptions, battery runtime estimates, and 13.2 in 27 lb Input Specifications Table C-2: Input Specifications UPS Model T700 NA T700 JPN T700 H INT'L Utility Voltage Frequency (Hz) 50/60 50/60 50 HP Uninterruptible Power System T700 Models User Guide C-1 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 43
Output Specifications Table C-3: Output Specifications UPS Model T700 NA T700 JPN T700 H INT'L Effective VA 700 700 700 Utility power (normal range) Other features Battery power Feature On-line efficiency Voltage wave THD at low battery shutdown High energy 6500 A peak MOVs and line - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 44
T700 NA T700 JPN T700 H INT'L Input Protection Input Overload Protector Input Overload Protector Input Overload Protector Battery Specifications Table C-6: Battery from the devices to the appropriate output receptacles of the UPS. HP Uninterruptible Power System T700 Models User Guide C-3 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 45
damage Up to 3,048 meters (10,000 feet) above sea level Up to 9,144 meters (30,000 feet) above sea level Less than 46 dBA C-4 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 46
troubleshooting 5-1 audible noise specification C-4 authorized reseller ix B Bad Battery LED 2-1 batteries care and storage 4-5 charging 2-3, 4-1 determining when to replace A-1 Declaration of Conformity A-2 device modifications A-2 HP Uninterruptible Power System T700 Models User Guide Index-1 - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 47
battery packs 4-2 UPS 1-2 physical specifications C-1 port, communications 1-1 power cords 1-2 power management software 1-5 problems See troubleshooting removing batteries 4-3 repairing the UPS 5-4 replacing batteries 4-2, 4-3 Index-2 HP Uninterruptible Power System T700 Models User Guide - HP R/T2200 IEC-320-C14 | HP Uninterruptible Power System T700 Models User Guide - Page 48
preventing electrostatic damage to B-1 T technical support ix telephone numbers ix temperature specifications C-4 testing batteries 4-4 text conventions viii tools, conductive field service type B-1 troubleshooting 5-1 U Uninterruptible Power System battery maintenance 4-1 installing 2-1 operating
![](/manual_guide/products/hewlettpackard-pro-ups-500-240v-hp-uninterruptible-power-t700-models-user-guide-0c94121/1.png)
HP Uninterruptible Power System
T700 Models
User Guide
October 2002 (Second Edition)
Part Number 215420-002