HP R7000 HP UPS Best Practices

HP R7000 Manual

HP R7000 manual content summary:

  • HP R7000 | HP UPS Best Practices - Page 1
    Power Protection 2 Recommended Duration of Use...2 Battery Replacement ...3 Select Load Appropriately / Sizing A UPS 3 Select Application Voltage / High volt VS Low Volt (120V or 208V 3 HP UPS Management...4 HP Power Manager Software...4 HP Management Module (AF401A 5 Rackmount UPS Model Numbers
  • HP R7000 | HP UPS Best Practices - Page 2
    network equipment, HP has developed a series of UPSs, ranging from 750VA to 12000VA. These UPSs enhance reliability and ensure high availability and uptime, while accompanying power management software continuously monitors and manages we strongly recommend considering replacing UPS's after a maximum
  • HP R7000 | HP UPS Best Practices - Page 3
    Battery Replacement It is best practice to replace the batteries every three years to ensure that the load will be properly supported during power outages, especially during high load conditions. There are a number of conditions that affect battery life, including temperature and the depth and
  • HP R7000 | HP UPS Best Practices - Page 4
    crashes and data loss, HP Power Management Software also helps users stay informed with UPS alarms sent via network broadcasts, SNMP, email, pager or mobile phone. Network administrators can also use the software to manage all UPSs on the network, check battery health and perform other valuable
  • HP R7000 | HP UPS Best Practices - Page 5
    Centers Provide access to multiple users Include a web interface management software that can be accessed with a web browser Include a Service Menu, a text-based menu that can be accessed through telnet or hyperterminal emulation session Use HP Management Module Software version 2.0 or higher. http
  • HP R7000 | HP UPS Best Practices - Page 6
    AF417A AF442A AF434A AF436A AF437A Management Module Serial Adapter - 5 pack R3000 ERM R/T3000 ERM R5500 ERM R5500 Tower Conversion Kit R8000/3 and R12000/3 ERM HP R12000/3 EXPANSION MODULE FOR RP36000/3 NA HP R12000/3 EXPANSION MODULE FOR RP36000/3 INTL HP Rackmount UPS Advantages Designed for
  • HP R7000 | HP UPS Best Practices - Page 7
    all network devices  Provides details of current system status  Enables users to schedule shutdowns at predetermined times, as well as define responses to alarm conditions UPS Options  UPS Option Card - HP UPS Management Module The HP UPS Management Module enables you to monitor and manage power
  • HP R7000 | HP UPS Best Practices - Page 8
    to optional Extended Runtime Modules (ERMs), allowing customers to increase runtime. The densest, most power-packed UPS available, the HP R3000 delivers more watts per U than any other UPS, enabling more valuable rack space to be utilized by servers, storage and networking equipment. Page 8 of 27
  • HP R7000 | HP UPS Best Practices - Page 9
    applications outside the data center or to support multiple tower servers, wiring closets, and blade enclosures such as the HP c3000 BladeSystem. An industry leading 3 year warranty and enhanced battery management with pre-failure warning insures that the HP R/T3000 will protect your power needs
  • HP R7000 | HP UPS Best Practices - Page 10
    extra-long battery life with Enhanced Battery Management (EBM); longer runtime with Digital Signal Processing technology (DSP); extended battery runtime with optional Extended Runtime Modules (now supports up to 4 ERMs with FW version 2.08 or higher); and easy serviceability with hot-swappable
  • HP R7000 | HP UPS Best Practices - Page 11
    three-phase, UPS line delivers industry-leading energy efficiency, scalability and flexibility. With 12kVA/12kW modules that occupy just 6U of valuable rack space, the HP three-phase UPS line features twice the power density of any comparable product on the market. Furthermore, the scalable design
  • HP R7000 | HP UPS Best Practices - Page 12
    batteries for simplified service without powering down the UPS  Power Management Software o Bundled free with every UPS, the software allows easy UPS management and monitoring, while providing prioritized, sequential shutdown of all network devices o Provides details of current system status
  • HP R7000 | HP UPS Best Practices - Page 13
    network environments, HP's T1000 and T1500 G3 models (1000VA/670 Watts and 1400VA/950 Watts) are designed with a host of key benefits including increased power rating, intuitive front panel display, hot-swappable batteries and prioritized shutdown using bundled HP Power Manager management software
  • HP R7000 | HP UPS Best Practices - Page 14
    Run Time per HP UPS Model Backup times** (in minutes) T750 G2 and T750 Japan Load, battery runtime at 100% battery charge 15 minutes 5 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes With 1 ERM
  • HP R7000 | HP UPS Best Practices - Page 15
    †Requires firmware v2.08 or higher With 1 ERM 160 minutes 50% 8 67% 9.6 80% 12 100% Battery Runtime Chart Internal +1 ERM +2 ERM +3 ERM +4 ERM 55 118 183 253 329 37 78 119 163 Number of Total load UPS Modules kW 6 60 Internal 6 +1 ERM +2 ERM +3 ERM +4 ERM 15 22 29 37 Configuration
  • HP R7000 | HP UPS Best Practices - Page 16
    R1500 G2 NA R1500 G2 INTL R1500 G2 JPN/TWN R3000 Low Volt NA PDU Model Number NA NA NA 252663-D71 R3000 High Volt NA 252663-B24 R3000 Low Volt JPN 252663-D71 R3000 High Volt JPN 252663-B24 R3000 High Volt INTL 252663-B24 R/T3000 Low Volt NA/JPN R/T3000 High Volt NA/JPN R/T3000 High
  • HP R7000 | HP UPS Best Practices - Page 17
    AF446A AF447A AF456A AF448A AF449A AF457A AF450A AF451A AF458A T750 G2 NA T750 G2 INTL T750 JAPAN T1000 G3 NA T1000 G3 INTL T1000 JAPAN T1500 G3 NA T1500 G3 INTL T1500 JAPAN PDU Model PDU Description Number NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Page 17 of 27
  • HP R7000 | HP UPS Best Practices - Page 18
    the UPS goes on battery to protect from a power anomaly, the UPS software will direct the attached load to shut down. For detailed information and a step-by-step process to configure this, please refer to your Owner's Manual. 2. When Performing a Hot Swap Electronics Module Replacement on the R3000
  • HP R7000 | HP UPS Best Practices - Page 19
    the NC REPO is equivalent of a REPO signal being sent to the UPS. Please refer to the users guide detailed installation instructions. 8. R12000/3 and A-B-C clockwise phase rotation The HP three phase UPS require A-B-C clockwise phase rotation for the input wiring. The unit detects and reports this
  • HP R7000 | HP UPS Best Practices - Page 20
    Page 20 of 27
  • HP R7000 | HP UPS Best Practices - Page 21
    Page 21 of 27
  • HP R7000 | HP UPS Best Practices - Page 22
    UPS/PDU power cord plug/receptacle reference Rackmount UPS products HP R1500 G2 NA/JPN/TWN Input plug type Part number: AF419A / Low Voltage NEMA 5-15P AF421A Output receptacles 4 - Low Voltage NEMA 5-15R HP R1500 G2 UPS INTL Part number: AF418A Input receptacle type High Voltage IEC320 C14
  • HP R7000 | HP UPS Best Practices - Page 23
    LS 2 - 1 - IEC320-C19 HP R5500 high voltage UPS NA/JPN Part number: AF426A Input plug type High Voltage NEMA L6-30P Output receptacles LS 1 - 1 L6-30R (on pigtail) LS 1 - 2 - IEC C-19 LS 1 - 2 - IEC C-13 LS 2 - 2 - IEC C-19 LS 2 - 2 - IEC C-13 HP R5500 high voltage UPS INTL Part number: AF416A
  • HP R7000 | HP UPS Best Practices - Page 24
    516P6 (16A) Output receptacles 1 - IEC309 516C6 (16A) HP R12000/3 high voltage UPS NA Part number: AF429A Input plug type IEC 560P9 (60A) Output receptacles 2 - NEMA L15-30 - receptacle are on output module HP R12000/3 high voltage UPS INTL Part number: AF430A Input plug type IEC309 532P6 (32A
  • HP R7000 | HP UPS Best Practices - Page 25
    HP RP36000/3 high voltage UPS NA Part number: AF438A No Photo Available Receptacles on output modules 2 - NEMA L15-30 HP RP36000/3 high voltage UPS INTL Part number: AF439A No Photo Available Receptacles on output modules 2 - IEC309 516C9 (16A) Page 25 of 27
  • HP R7000 | HP UPS Best Practices - Page 26
    type Low Voltage NEMA 5-15P Output receptacles 6 - Low Voltage NEMA 5-15R HP T1000 G3 UPS NA Part number: AF448A Input plug type Low Voltage NEMA 5-15P Output receptacles 6 - Low Voltage NEMA 5-15R HP T1000 G3 UPS INTL Part number: AF449A Input receptacle type High Voltage IEC320 C14 Output
  • HP R7000 | HP UPS Best Practices - Page 27
    solutions, please refer to the following web pages: HP Power Manager: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/software/powermanager/index.html HP UPSs: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html# UPS Sizing: www.upssizer
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27

Page 1 of 27
HP UPS Best Practices
Abstract
.........................................................................................................................................
2
Introduction
...................................................................................................................................
2
The Importance of Power Protection
............................................................................................
2
Recommended Duration of Use
....................................................................................................
2
Battery Replacement
....................................................................................................................
3
Select Load Appropriately / Sizing A UPS
....................................................................................
3
Select Application Voltage / High volt VS Low Volt (120V or 208V)
.............................................
3
HP UPS Management
...................................................................................................................
4
HP Power Manager Software
....................................................................................................
4
HP Management Module (AF401A)
..........................................................................................
5
Rackmount UPS Model Numbers
.............................................................................................
6
Tower UPS Model Numbers
.....................................................................................................
6
UPS Options
.............................................................................................................................
6
HP Rackmount UPS Advantages
.................................................................................................
6
HP Rackmount UPS Models
.........................................................................................................
8
HP R1500 G2 Rackmount UPS
................................................................................................
8
HP R3000 Rackmount UPS
......................................................................................................
8
HP R/T3000 Rackmount UPS
...................................................................................................
9
HP R5500 Rackmount UPS
....................................................................................................
10
HP Three-phase Rack-mountable UPS
..................................................................................
11
HP Tower UPS Advantages
........................................................................................................
12
HP Tower UPS Models
...............................................................................................................
13
HP T750 G2 UPS
....................................................................................................................
13
HP T1000 G3 and T1500 G3 UPSs
........................................................................................
13
HP T750 Japan T1000 Japan and T1500 Japan UPSs
..........................................................
13
Run Time per HP UPS Model
.....................................................................................................
14
Recommended Power Distribution Units (PDU)
.........................................................................
16
Avoiding Potential Glitches
.........................................................................................................
18
Worldwide Power Requirements
.................................................................................................
19
UPS/PDU power cord plug/receptacle reference
........................................................................
22
Additional Information
.................................................................................................................
27
The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth
in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting
an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.