HP T1500 IEC-320-C14 HP R/T2200 UPS User Guide

HP T1500 IEC-320-C14 Manual

HP T1500 IEC-320-C14 manual content summary:

  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 1
    HP R/T2200 UPS User Guide Part Number 404314-004 August 2008 (Fourth Edition)
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 2
    for technical or editorial errors or omissions contained herein. Intended audience This guide is for the person who operates, configures, maintains, and troubleshoots UPSs. HP assumes you are qualified in the servicing of high-voltage equipment and trained in recognizing hazards in products with
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 3
    ...33 Replacing the batteries...33 Important battery safety information 33 Battery care and storage guidelines 34 UPS battery replacement procedure 34 Cleaning battery spills ...36 Troubleshooting ...37 UPS does not start ...37 Contents 3
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 4
    ...41 Battery runtime...42 Environmental specifications ...42 Spares...43 Ordering spares...43 Spare parts list...43 Hardware options ...43 Technical support...44 Before you contact HP...44 HP contact information ...44 Warranty information...45 Limited warranty ...45 $250,000 Computer Load
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 5
    Battery replacement notice...50 Power cord statement for Japan...50 Electrostatic discharge ...51 Preventing electrostatic discharge ...51 Grounding methods to prevent electrostatic discharge 51 Acronyms and abbreviations...52 Index...53 Contents 5
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 6
    Component identification UPS front panel Item 1 2 Description Battery compartment Control buttons and LED display Component identification 6
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 7
    without the assistance of battery power. The UPS will emit a slight clicking noise. Shows approximately how much of the UPS power capacity is used to support the equipment connected to the output receptacles. Red-Maximum load Amber-Medium load Green-Light load Component identification 7
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 8
    Item 5 6 7 1 Description Battery Charge LED Battery Warning LED Mute/Test button Function When the UPS is operating from utility power (the Power LED is green), the Battery Charge LED indicates the approximate charge state of the batteries: • Red-The batteries are beginning to charge. • Amber-The
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 9
    Item 1 2 3 4 5 6 7 8 9 10 11 12 13 Description Load segment 1 (one NEMA 5-15 output receptacle for surge and battery backup protection) Load segment 2 (one NEMA 5-15 output receptacle for surge and battery backup protection) Load segment 3 (one NEMA 5-20 output receptacle for surge and battery
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 10
    Item 3 4 5 6 7 8 9 10 11 12 13 Description Load segment 3 (one IEC-320-C13 output receptacle for surge and battery backup protection) Load segment 4 (five unswitchable IEC-320-C13 output receptacles for surge and battery backup protection) Input circuit breaker Input power cord with IEC-320-C20
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 11
    power when the remote switch was closed, no power is available to the load devices until utility power is restored and the UPS has been manually powered up. To restore power to the load devices after the REPO feature is activated, press the Power On/Standby button after the AC source
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 12
    contains important safety instructions that should be followed during installation, operation, and maintenance of the UPS and batteries. WARNING: A risk of personal injury from electric shock and hazardous energy levels exists. The installation of options and routine maintenance and service of this
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 13
    date has passed. If the date on the battery recharge date label has passed without the battery being recharged, contact an HP authorized service representative for directions. 2. Transport the packaged unit to its installation location. 3. Unpack the equipment near the rack where the unit will be
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 14
    1. Remove the UPS front bezel. 2. Attach the logo badge above the LED/Control panel. Installation 14
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 15
    3. From inside the bezel, gently push out the LED/Control panel, rotate it 90 degrees, and then replace it in the bezel. 4. Replace the front bezel. 5. Stand the unit on its side with the LED/Control panel at the top. Installing the UPS in a rack Before installing the unit, review and adhere to all
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 16
    WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that: • The leveling feet are extended to the floor. • The full weight of the rack rests on the leveling feet. • The stabilizing feet are attached to the rack if it is a single-rack installation. • The racks are
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 17
    3. Insert screws through the rack into the mounting rail and the front of each mounting bracket. Do not completely tighten the screws. 4. Insert screws through the rack into the mounting rail and the rear of each mounting bracket. Do not completely tighten the screws. 5. Wait until the unit is
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 18
    Connecting the batteries WARNING: The unit contains sealed lead-acid battery modules. To prevent fire or chemical burns: • Do not attempt to recharge batteries after removal from the unit. • Do not disassemble, crush, or puncture the batteries. • Do not short the external contacts of the batteries.
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 19
    2. Connect the battery lead to the battery terminal. NOTE: A small amount of arcing may occur when connecting the batteries. This is normal and does not damage the unit or present any safety concern. 3. Replace the UPS front bezel. 4. Attach the RETMA rail covers. NOTE: The HP logo and product name
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 20
    When using an ERM, set the Battery Charge Level switch (DIP switch 3) to the down position, increasing the UPS charger output and charging the ERM faster. CAUTION: Do not set the Battery Charge Level switch to the down position without an ERM connected. There is a risk of damaging the internal
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 21
    , ensuring that all connected load devices are shutdown gracefully. NOTE: To install and configure the software, see the software user guide. The software user guide is available for download from the HP website (http://www.hp.com/go/rackandpower). Connecting the serial communications port CAUTION
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 22
    CAUTION: Using a USB to serial converter cable will damage the UPS. Connecting the REPO port WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS installed in a computer equipment room must be connected to a REPO circuit. IMPORTANT: The remote switch must be in
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 23
    Connecting the ground bonding cable The ground bonding screw is provided as an attachment point for conductors. Use a ground bonding cable if the rack contains any conductors for the purpose of functional grounding or bonding of ungrounded metal parts. The ground bonding cable is not included.
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 24
    using the jumper cords included with the UPS (INTL model). Charging the UPS batteries Allow the batteries to charge before putting the UPS into service. IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to devices. The batteries charge to: • 90% of their capacity
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 25
    1. Attach the logo badge above the LED/Control panel. 2. Stand the unit on its side with the LED/Control panel at the top. Installing the ERM in a rack Before installing the unit, review and adhere to all warnings provided in "Precautions (on page 12)." WARNING: To reduce the risk of personal injury
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 26
    NOTE: Mounting hardware for square- and round-holed racks is included in the UPS kit. 1. Attach the 2U side-mounting brackets to the unit. 2. Loosen the wing nuts, and extend the brackets to the desired length. Installation 26
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 27
    3. Insert screws through the rack into the mounting rail and the front of each mounting bracket. Do not tighten. 4. Insert screws through the rack into the mounting rail and the rear of each mounting bracket. Do not tighten. 5. Tighten the wing nuts. 6. Wait until the unit is installed and the
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 28
    Connecting the ERM to the UPS This symbol indicates the presence of electric shock hazards. The area contains no user or field serviceable parts. Do not open for any reason. WARNING: To reduce the risk of injury from electric shock hazards, do not open this enclosure. Plug the
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 29
    Charging the ERM batteries Connect the UPS to a grounded utility power outlet. When the UPS is plugged in, the unit automatically enters Standby mode and begins charging the ERM batteries. Allow 24 hours for the ERM to fully charge. Installation 29
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 30
    the alarm silences after power is restored. Audible alarm conditions Alarm type Condition Audible alarm Normal UPS on battery Shutdown imminent Battery problem Overload UPS operating from utility power UPS operating on battery power Batteries nearly out of power Batteries must be recharged UPS
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 31
    different settings for this dial. As the dial is turned clockwise, the UPS becomes more tolerant of variations in the input power's AC waveform. NOTE: While testing, operate connected equipment in a safe test mode so the effects do not disrupt critical operations. For the location of rear panel
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 32
    , see the HP website (http://www.hp.com/go/rackandpower). NOTE: To install and configure the software, see the software user guide. The software user guide is available for download from the HP website (http://www.hp.com/go/rackandpower). HP Power Manager: • Does not require complex management
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 33
    Read and observe the requirements in "Important battery safety information" and "Battery care and storage guidelines (on page 34)." 2. Follow the instructions in "UPS battery replacement procedure (on page 34)." Important battery safety information WARNING: The unit contains sealed lead-acid battery
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 34
    Battery care and storage guidelines CAUTION: Because of the short shelf life of the batteries, avoid storing a battery spare as a backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep these batteries charged while in storage is implemented. To maintain the
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 35
    3. Disconnect the battery leads. 4. Remove the battery bracket. 5. Remove the UPS battery modules. IMPORTANT: Do not pull the battery leads when removing or installing the batteries. Maintenance 35
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 36
    To replace the component, reverse the removal procedure. IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to devices. The batteries charge to: • 90% of their capacity within 4 hours • 100% of their capacity within 24 hours Cleaning battery spills 1. Put on acid-
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 37
    (on page 33). Action: Restart the update. Audible alarm sounds Action: 1. Identify the red LED associated with the audible alarm. 2. Check the troubleshooting information in this document to determine the cause of the alarm. Circuit breaker trips Action: Remove some of the load, and then press the
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 38
    up the UPS" on page 24). c. Allow the UPS batteries to charge for 24 hours. If the Battery Charge LED is also yellow or green: Troubleshooting 38
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 39
    LED is green: a. Continue to let the batteries charge until the Battery Charge LED is green. b. Initiate a self-test ("Initiating a self-test" on page 30). Troubleshooting 39
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 40
    Specifications UPS physical specifications Parameter Height Depth Width Weight Value 8.9 cm (3.5 in) 48.3 cm (19 in) 44.5 cm (17.5 in) 29 kg (64 lb) ERM physical specifications Parameter Height Depth Width Weight Value 8.9 cm (3.5 in) 34.3 cm (13.5 in) 44.5 cm (17.5 in) 28.6 kg (63 lb) UPS
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 41
    Power protection specifications UPS model R/T2200 NA/JPN/TWN R/T2200 INTL VA 2200 2200 Nominal power Nominal voltage rating (W) setting 1600 100, 110, 120 1600 220, 230, 240 Voltage specifications Configuration setting (VAC) 100 110 120 220 230 240 Available nominal output voltage (VAC)
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 42
    Feature Charging Specification Complete charge takes no more than 24 hours. After approximately 4 hours, the batteries reach 90% charge at default nominal utility voltage and no load. Battery runtime Load, percent 20 50 80 100 Load, watts 100 250 400 500 Estimated battery runtime 45 minutes 15
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 43
    (http://h61003.www6.hp.com). To replace parts under warranty, contact an HP authorized service representative. Spare parts list Item UPS unit NA UPS unit JPN/TWN UPS unit INTL options For information on the supported hardware options, see the HP website (http://www.hp.com/go/rackandpower). Spares
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 44
    HP authorized reseller: • In the United States, see the HP US service locator webpage (http://www.hp.com/service_locator). • In other locations, see webpage (http://welcome.hp.com/country/us/en/wwcontact.html). For HP technical support: • In the United States, for contact options see the Contact HP
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 45
    all applicable electrical and safety codes specified by the NEC. • The UPS is used under normal operating conditions and users comply with all instructions and labels. • The UPS is not damaged by accident (other than a utility power transient), misuse, or abuse. o The Guarantee applies only to the
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 46
    computers). The FCC requires devices in both classes to bear a label indicating the interference potential of the device as well as additional operating instructions for the user. FCC rating label The FCC rating label on the device shows the classification (A or B) of the equipment. Class B devices
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 47
    energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 48
    Canadian notice (Avis Canadien) Class A equipment This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. Class B equipment
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 49
    more information about where you can drop off your waste equipment for recycling, please contact your local city office, your household waste disposal service or the shop where you purchased the product. Japanese notice BSMI notice Korean notice Class A equipment Regulatory compliance notices 49
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 50
    to HP, an authorized HP Partner, or their agents. For more information about battery replacement or proper disposal, contact an authorized reseller or an authorized service provider. Power cord statement for Japan Regulatory compliance notices 50
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 51
    workstations. Wear the straps on both feet when standing on conductive floors or dissipating floor mats. • Use conductive field service tools. • Use a portable field service kit with a folding static-dissipating work mat. If you do not have any of the suggested equipment for proper grounding
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 52
    Acronyms and abbreviations EPO emergency power off ERM extended runtime module HPPM Hewlett-Packard Power Manager IEC International Electrotechnical Commission LED light-emitting diode NEC National Electrical Code NEMA National Electrical Manufacturers Association PFC power factor corrected REPO
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 53
    connecting 18 Battery Charge LED, location 7 Battery Charge LED, troubleshooting 39 battery replacement notice 50 Battery Warning LED, location 7 hardware options 43 HP technical support 44 I input circuit breaker, location 8, 9 input specifications 40 installation instructions 12, 13, 24 installing
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 54
    sensitivity adjustment dial, setting 30 powering down 31 powering up 24 problem diagnosis 37 R R/T2200 INTL 7, 9 R/T2200 NA/JPN/TWN supported hardware 43 T technical support 44 telephone numbers 44 temperature ranges (environmental) 42 testing LEDs 30 tower to rack conversion 13, 24 troubleshooting
  • HP T1500 IEC-320-C14 | HP R/T2200 UPS User Guide - Page 55
    UPS, installing 12, 13 USB connectors 21 V Voltage Correction LED, location 7 Voltage Correction LED, troubleshooting 39 voltage specifications 41 voltage, configuring 19 W warranties 45 weight, ERM 40 weight, UPS 40 Index 55
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55

HP R/T2200 UPS
User Guide
Part Number 404314-004
August 2008 (Fourth Edition)