LiftMaster SL595203U SL595203U Installation Manual

LiftMaster SL595203U Manual

LiftMaster SL595203U manual content summary:

  • LiftMaster SL595203U | SL595203U Installation Manual - Page 1
    ELITE SERIES HEAVY DUTY INDUSTRIAL AC SLIDE GATE OPERATOR INSTALLATION MANUAL SL595101U 1 HP, 120/208-240 Vac Single Phase Phase SL595205U 2 HP, 575 Vac Three Phase • THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE SYSTEMS TECHNICIAN ONLY. • This model is for use on vehicular passage
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 2
    INFORMATION 38 MAINTENANCE 38 TROUBLESHOOTING 39 DIAGNOSTIC CODES 39 OPERATOR ALARM 42 TROUBLESHOOTING CHART 43 ACCESSORIES 45 you must read and fully understand this manual and follow all safety instructions. • DO NOT attempt repair or service of your gate operator unless you are
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 3
    reduce the risk of INJURY or DEATH: • READ AND FOLLOW ALL INSTRUCTIONS. • NEVER let children operate or play with gate controls. Keep is not moving. • KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware. • The entrance is for vehicles
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 4
    • Photoelectric Sensors • Screen Mesh • Vertical Posts • Instructional and Precautionary Signage 4. Install the gate operator only when: For a gate operator utilizing a non-contact sensor: a. Reference owner's manual regarding placement of non-contact sensor for each type of application. See
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 5
    An existing gate latch shall be disabled when a manually operated gate is retrofitted with a powered gate operator. stationary object nearest the roadway, (such as a gate support post) and the gate frame when the gate is in that the gate will enter a receiver guide, refer to ASTM F2200 for panel
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 6
    INTRODUCTION CARTON INVENTORY NOT SHOWN: Documentation Packet, Chain #50 - 24 feet, Eye Bolt Kit Operator Clamps Warning Signs (2) and Warranty Card Gate Brackets Hardware LiftMaster Monitored Retro-Reflective Photoelectric Sensor TOOLS NEEDED • 3/4" wrench for 1/2" concrete anchors •
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 7
    INTRODUCTION OPERATOR SPECIFICATIONS This model is intended for use in vehicular slide gate applications: Usage Classification Accessory Power Maximum Gate Weight Minimum Gate Travel Distance Maximum Gate Travel Distance Maximum Gate Travel Speed Maximum Daily Cycle Rate Maximum Duty Cycle
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 8
    INTRODUCTION OPERATOR SPECIFICATIONS HP 1 1-1/2 2 Phase Single Three Single Three Vac 120 Vac 208-240 Vac 208-240 Vac 480 Vac 575 Vac 120 Vac 208-240 Vac 208-240 Vac 480 Vac 575 Vac Main AC Supply Full Load Amps 16 Amps (22 Amps including Accessory Outlets) 8 Amps 6 Amps 3 Amps 1.8 Amps 20 Amps
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 9
    INTRODUCTION SITE PREPARATION Check the national and local building codes BEFORE installation. CONDUIT & CONCRETE PAD Conduit must be UL approved for low and high voltage. Consider the operator placement BEFORE installing the pad or post. SAFETY Entrapment protection devices are required to
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 10
    INTRODUCTION OVERVIEW OF TYPICAL INSTALLATION IMPORTANT SAFETY INFORMATION: One or more external monitored entrapment protection sensors shall be located where the risk of entrapment or obstruction exists at either the opening or closing direction. Any gap larger than 2-1/4 inches between the gate
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 11
    INSTALLATION • To AVOID damaging gas, power or other underground utility lines, contact underground utility locating companies BEFORE digging more than 18 inches (46 cm) deep. • DO NOT touch the heater when switch is on, heater may be hot. • To prevent damage to the operator or gate, DO NOT drive
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 12
    INSTALLATION STEP 1 (continued) INSTALL THE OPERATOR Check the national and local building codes before installation. INSTALL WITHOUT ADJUSTABLE RAILS NOTE: The rails will have to be removed for retro-fit installations. 1. Locate and anchor two posts made of 3" (7.6 cm) outer diameter heavy walled
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 13
    instructed. 1. Mount gate brackets to the vertical front and rear posts of the gate. 2. Remove the operator cover. 3. Locate and engage the manual guide, around drive and idler sprockets, and then through the second plastic chain guide as a chain support. Vent Plug Manual Release Handle Gate
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 14
    the maximum separation distance of the photoelectric sensors, then edge sensors MUST BE USED. Refer to the photoelectric sensor instructions for maximum separation distance. ProIpnesridtye PrOopuetsrtiyde CONTACT SENSORS (EDGE SENSORS) If the electrically activated edge sensor comes in contact
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 15
    protection devices depending on the specific device and how the device will function. Refer to the specific entrapment protection device manual for more information. These entrapment protection device inputs are for monitored devices, which include pulsed photoelectric sensors, resistive edge
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 16
    operator power switch. Upon completion of maintenance the area MUST be cleared and secured, at that time the unit may be returned to service. • Disconnect power at the fuse box BEFORE proceeding. Operator MUST be properly grounded and connected in accordance with national and local electrical codes
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 17
    INSTALLATION STEP 5 (continued) POWER WIRING SINGLE PHASE The operator is field configurable for usage at 120, 208, and 240 Vac. Factory default is 120 Vac. For 208 Vac Operation Unplug the motor harness from the "120V" receptacle on the power board and plug the harness in to the "208V / 240V"
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 18
    INSTALLATION STEP 5 (continued) POWER WIRING THREE PHASE The operator is field configurable for usage at 208, 240, and 480 Vac. Factory default is 240 Vac. For three phase 575V operators, the operator is configured at the factory for 575V ONLY (Models SL595105U and SL595205U). For 208 Vac
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 19
    INSTALLATION STEP 6 DUAL GATES ONLY There are two options for dual gate communication: wired or wireless. Follow the directions according to your application. Do not use wired and wireless communication simultaneously. WIRELESS DUAL GATES TO ACTIVATE THE WIRELESS FEATURE: 1. Choose an operator to be
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 20
    INSTALLATION STEP 6 continued... DUAL GATES ONLY DUAL GATE WIRE TYPE (SHIELDED TWISTED PAIR CABLE) 22AWG up to 200 feet (61 m) 18AWG - 200-1000 feet (61-305 m) Wire must be rated at 30 Volt minimum WIRED DUAL GATES Before digging, contact local underground utility locating companies. Use PVC
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 21
    set during this cycle. Limit Nuts READJUST THE LIMITS To readjust the limits, follow the "Set the Limits" and "Set the Force and Run Distance" instructions above. It is important that the force and run distance are set after every limit readjustment. Limit Switches 20
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 22
    INSTALLATION STEP 7 (continued) ADJUST THE HANDING AND LIMITS ERASE THE HANDING 1. To erase the handing, press and hold the OPEN LEFT and OPEN RIGHT buttons simultaneously (5 seconds) until both the OPEN LEFT and OPEN RIGHT LEDs blink rapidly and the operator beeps. 2. Release the buttons and the
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 23
    INSTALLATION STEP 9 OBSTRUCTION TEST The operator is equipped with an automatic obstruction sensing feature. If the gate encounters an obstruction during motion, the operator will automatically reverse direction of the gate for a short time and then stop the gate. After any adjustments are made,
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 24
    SBC OPN CLS STP COM OPEN CLOSE COM EYE/ EDGE 3 EYE/ EDGE 2 EYE ONLY 1 TO MAIN BOARD TERMINAL BLOCK For additional accessory wiring. Page 33 MANUAL RELEASE HANDLE Pull the manual release handle to manually open and close the gate. LIMIT SWITCHES Page 20 JUNCTION BOX 23
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 25
    CONTROL BOARD OVERVIEW CONTROL BOARD REFERENCE BIPART DELAY Page 25 LEARN BUTTON Pages 25, 34-35 DIAGNOSTIC DISPLAY Pages 25, 39-41 TIMER-TO-CLOSE Page 25 FORCE DIAL Page 26 TEST BUTTONS Pages 26, 39 HANDING BUTTONS Pages 20, 25 BIPART DELAY 4 2 6 OPEN LEFT OPEN 8 RIGHT HANDING
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 26
    operator type as SL595. The firmware version will show after the operator type, example "1.2". For more information about the codes refer to the Troubleshooting section. HANDING BUTTONS The handing buttons are used to determine which direction the gate will open and they are also used to set the
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 27
    adjustment. 5 4 3 2 1 6 7 8 9 10 TEST BUTTONS Used to operate the gate (OPEN, STOP and CLOSE). Also used to view the code history (refer to the Troubleshooting section). LED INPUT POWER TIMER GATE MOVING ACC PWR OVLD STATE OFF ON OFF ON 1 blink/second 2 blinks/second 8 blinks/second OFF ON
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 28
    WIRE ACCESSORIES TO CONTROL BOARD TERMINALS OPEN and COMM CLOSE and COMM STOP and COMM THREE BUTTON CONTROL STATION FUNCTION WIRING EXAMPLE Opens a closed gate. Hard open (maintained switch overrides external safeties and resets alarm condition). If maintained, pauses Timer-to-Close at OPEN
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 29
    WIRE ACCESSORIES TO CONTROL BOARD PHOTOELECTRIC SENSORS AND EDGE SENSORS The EYES/EDGE terminals are used for connecting entrapment protection devices. At least one external monitored entrapment protection device is required prior to gate movement. Monitored entrapment protection devices should
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 30
    EXPANSION BOARD OVERVIEW To AVOID damaging the circuit board, relays or accessories, DO NOT connect more than 42 Vdc (32 Vac) to the AUX relay contact terminal blocks. PLUG-IN LOOP DETECTOR INPUTS For Plug-In Loop Detectors (Model LOOPDETLM) SHADOW INTERUPT EXIT OPEN CLOSE POWER 1 EYE ONLY 2
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 31
    ON ON OFF Not used. ON OFF ON Energizes if gate is manually tampered with by being pushed off of close limit. For an additional ,000.). Cycle count displayed is between 1,000 and 9,999,000 cycles. After servicing, set Aux Relay switches back to their appropriate positions. Cycle count cannot be
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 32
    WIRE ACCESSORIES TO EXPANSION BOARD PHOTOELECTRIC SENSORS AND EDGE SENSORS The EYES/EDGE terminals are used for connecting entrapment protection devices. At least one external monitored entrapment protection device is required prior to gate movement. Monitored entrapment protection devices should
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 33
    WIRE ACCESSORIES TO EXPANSION BOARD INPUTS EXIT SHADOW INTERRUPT LOOPS FUNCTIONALITY WIRING EXAMPLE Loop wire connection for plug-in loop detector when loop is inside secured area near gate. • Open command - opens a closed gate • Soft open (maintained switch does not override external safeties
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 34
    ADDITIONAL WIRING To protect against fire and electrocution: • DISCONNECT power (AC or solar and battery) BEFORE installing or servicing operator. For continued protection against fire: • Replace ONLY with fuse of same type and rating. FIELD WIRING BIPART DELAY 4 2 6 OPEN LEFT OPEN 8 RIGHT
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 35
    installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 36
    PROGRAMMING LIFTMASTER INTERNET GATEWAY (NOT PROVIDED) To program the operator to the LiftMaster Internet Gateway: Program using the learn button on the operator's control board: 1. Connect the ethernet cable to the LiftMaster Internet Gateway and the router. 2. Connect power to the LiftMaster
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 37
    system) to indicate if gate is manually tampered with by being pushed off of close limit. Use during servicing only to Use during servicing only to determine operator cycles. determine operator cycles. Use during servicing only to Use during servicing only to determine operator cycles. determine
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 38
    SETTINGS DUAL GATE SETTINGS NOTE: We recommend that all accessories and board configurations are set on the primary operator. MAIN CONTROL BOARD FEATURE PRIMARY OPERATOR Timer-to-Close Set the TTC dial to desired setting OFF SECONDARY OPERATOR Bi-Part Delay Switch Bi-Part Delay: ON (will
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 39
    • SAVE THESE INSTRUCTIONS. To protect against fire and electrocution: • DISCONNECT power (AC or solar and battery) BEFORE installing or servicing operator. For to the operator before servicing. DESCRIPTION TASK Entrapment Protection Devices Warning Signs Manual Disconnect Drive Chain and
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 40
    TROUBLESHOOTING To protect against fire and electrocution: • DISCONNECT power (AC or solar and battery) BEFORE installing or servicing operator. For continued protection against fire: • Replace ONLY with fuse of same type and rating. DIAGNOSTIC CODES TO VIEW THE CODES The codes will show
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 41
    TROUBLESHOOTING DIAGNOSTIC CODES continued... Some codes are saved in the code history and some are not. If a code is not saved it will briefly appear on
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 42
    TROUBLESHOOTING DIAGNOSTIC CODES continued... Some codes are saved in the code history and some are not. If a code is not saved it will briefly appear on
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 43
    TROUBLESHOOTING OPERATOR ALARM If a contact sensor detects an obstruction twice consecutively the alarm will sound (up to 5 minutes) and the operator will need to be reset.
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 44
    TROUBLESHOOTING TROUBLESHOOTING CHART SYMPTOM Operator does not run and diagnostics display not the gate moves at least four feet between the OPEN limit and the CLOSE limit. a) Use manual disconnect, manually move gate, and ensure gate moves easily limit to limit. Repair gate as needed. b) Gate
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 45
    TROUBLESHOOTING TROUBLESHOOTING CHART continued... SYMPTOM POSSIBLE CAUSES Shadow loop does not keep gate at open limit. a) Vehicle detector setup incorrectly b) Defective vehicle loop detector Obstruction in a) Force
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 46
    maximum separation distance of the photoelectric sensors, then edge sensors MUST BE USED. Refer to the photoelectric sensor instructions for maximum separation distance. LiftMaster Monitored Through Beam Photoelectric Sensor (LMTBU) LiftMaster Monitored Retro Reflective Photoelectric Sensor (LMRRU
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 47
    Board Single Phase K1D8284-1CC Three Phase K1D8424-1CC Expansion Board K1D8387-1CC Idler Sprocket K305-153613 Mounting Bracket K10-30699-1 Chain Guide Kit K75-37700 Chain Guard K10-30702-2 Stop/Reset Button K23-34815-1 MOTOR ASSEMBLY SL595101U K94-37848-1 SL595103U K94-37849-1 SL595203U K94
  • LiftMaster SL595203U | SL595203U Installation Manual - Page 48
    this product. Then send this product, pre-paid and insured, to our service center for warranty repair. You will be advised of shipping instructions when you call. Please include a brief description of the problem and a dated proof-of-purchase receipt with any product returned for warranty repair
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

ELITE SERIES HEAVY DUTY INDUSTRIAL
AC SLIDE GATE OPERATOR
Model
SL595
INSTALLATION MANUAL
LiftMaster
845 Larch Avenue
Elmhurst, IL 60126-1196
THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE
SYSTEMS TECHNICIAN ONLY.
This model is for use on vehicular passage gates ONLY and not intended for use
on pedestrian passage gates.
This model is intended for use in Class I, II, III and IV vehicular slide gate
applications.
Visit LiftMaster.com to locate a professional installing dealer in your area.
This gate operator is compatible with MyQ
®
and Security+ 2.0
accessories.
SL595101U
1 HP, 120/208-240 Vac Single Phase
SL595103U
1 HP, 208-240/480 Vac Three Phase
SL595105U
1 HP, 575 Vac Three Phase
SL595151U
1-1/2 HP, 120/208-240 Vac Single Phase
SL595203U
2 HP, 208-240/480 Vac Three Phase
SL595205U
2 HP, 575 Vac Three Phase