Panasonic WU-216MF2U9 - Technical Data Manual

Panasonic WU-216MF2U9 Manual

Panasonic WU-216MF2U9 manual content summary:

  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 1
    Order No. SBPAC1509016CE 3WAY VRF System U-72MF2U9 U-96MF2U9 U-120MF2U9 U-144MF2U9 U-72MF2U94 U-96MF2U94 U-120MF2U94 U-144MF2U94 Model No. Outdoor Unit Type Outdoor Unit Type MF2 3WAY VRF System 72 U-72MF2U9 U-72MF2U94 Nominal Capacity 96 120 U-96MF2U9 U-120MF2U9 U-96MF2U94 U-120MF2U94
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 2
    service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: ● Carefully read this instruction problem, contact our sales/service outlet or your certified dealer for additional instructions rigid and strong enough to support or hold the unit,
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 3
    authorized dealer or specialist for cleaning. • In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair. CAUTION • Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured. • Ventilate
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 4
    Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing Material: Use clean, dry, free of oil, refrigeration grade, seamless, phosphorous deoxidized copper tube rated for R410A only. Wall thickness shall comply with the applicable legislation. The minimal wall
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 5
    3-2. Use R410A exclusivee ccyylliinnddeerr oonnllyy.. Single-outlet valve (with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown. New refrigerant R410A cannot be used for earlier models 1. Compressor specifications are diffeerreenntt.. If recharging a
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 6
    P1) 12. Concealed Floor Standing (Type R1) 13. Fresh Air Intake * Refer to the VRF SYSTEM TECHNICAL DATA (TD831178) Section 5: TEST RUN ...5-1 * Refer to the SERVICE MANUAL & TEST RUN SERVICE MANUAL (SM830246) v v
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 7
    Section 6: ELECTRICAL DATA 6-1 1. Outdoor Unit 6-2 2. Indoor Unit * Refer to the VRF SYSTEMS INDOOR UNIT TECHNICAL DATA (TD831178) Section 7: PCB AND FUNCTIONS 7-1 1. Outdoor Unit Control PCB 7-2 2. Indoor Unit Control PCB Switches and Functions * Refer to the VRF SYSTEMS INDOOR UNIT TECHNICAL
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 8
    - MEMO -
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 9
    Contents Outline of 3WAAYYVVRRFFSSYYSSTTEEMM 1. OUTLINE OF 3WAY VRF SYSTEM 1. Line-up ...1-2 2. Features of 3WAY VRF SYSTEM 1-5 1 2 3 4 5 6 7 8 1 - 1 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 10
    11.. LLiinnee--uupp Outline of 3WAY VRF SYSTEM Indoor units Type 7 9 12 15 18 24 36 48 54 4-Way Cassette 36" X 36" (Type U2) S-07MU2U6 S-09MU2U6 S-12MU2U6 S-24MU2U6 S-36MU2U6 4-Way Cassette 24" X 24" (Type Y2) CLOSE OPEN OPEN CLOSE CLOSE OPEN OPEN CLOSE CLOSE OPEN OPEN
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 11
    1. Line-up Outdoor units Type Capacity: BTU/h (kW) Cooling / Heating U-72MF2U9 U-72MF2U94 Outdoor Unit C:28-47/64(730) (Installation hole pitch) Outline of 3WAY VRF SYSTEM 72 72,000 (21.1) / 81,000 (23.7) *1. The tubing is routed out from the bottom. *2. The tubing is routed out from the front.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 12
    1. Line-up Outline of 3WAY VRF SYSTEM Type Capacity: BTU/h (kW) Cooling / Heating U-120MF2U9 U-120MF2U94 120 120,000 (35.2) / 135,000 (39.6) *1. The tubing is routed out from the bottom. *2. The tubing is routed out from the front. *1 B:28-47/64(730) (Installation hole pitch) A:37-61/64(964)*2 (
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 13
    into one pipe shaft, you can minimize tubing space and construction labor. Solenoid * 1 valve kit 1 Indoor unit If indoor/outdoor units need servicing, a ball 2 valve (field supply) cuts off non-operational units to let other units stay running. ADDITION If your indoor capacity load
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 14
    2. Features of 3WAY VRF SYSTEM Dimensions 6-Ton U-72MF2U9 U-72MF2U94 8-Ton U-96MF2U9 U-96MF2U94 10-Ton U-120MF2U9 U-120MF2U94 12-Ton U-144MF2U9 U-144MF2U94 6, 8, 10, 12 Ton Outline of 3WAY VRF SYSTEM *1. The tubing is routed out from the bottom. *2. The tubing is routed out from the front. 28-47
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 15
    2. Features of 3WAY VRF SYSTEM Outline of 3WAY VRF SYSTEM Capacity control The compressor combination (DC inverter compressor + DC inverter compressor) allows smooth capacity control from 0.6-Ton to 30-Ton. Realization of smooth capacity control from 0.6-Ton to 30-Ton Capacity control is possible
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 16
    - MEMO - 1 - 8
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 17
    CCoonntteennttss Design of 3WAYY VVRRFF SSYYSSTTEEMM 2. DESIGN OF 3WAY VRF SYSTEM 1. Model Selection and Capacity Calculator 2-3 1-1. Operating Range ...2-3 1-2. Procedure for Selecting Models and Calculating Capacity 2-4 1-3. Tubing Length...2-5 1-4. Tubing Size ...2-8 1-5. Straight
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 18
    CCoonntteennttss Design of 3WAYY VVRRFF SSYYSSTTEEMM 8. Optional Parts ...2-55 8-1. Installing Distribution Joint 2-55 8-2. Optional Distribution Joint Kits 2-56 8-3. Optional Solenoid Valve kit (CZ-P56HR2U / CZ-P160HR2U 2-58 8-4. Solenoid Valve kit (CZ-P456HR2U / CZ-P656HR2U / CZ-P856HR2U / CZ
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 19
    11.. MMooddeell SSeelleeccttiionng aanndd CCaappaacciittyy CCaallccuullaattoorr 1-1. Operating Range D%eFsTiJgHnOoPf G3W8A"Y:V7R3F'S4Y:S4T5E&M. Cooling 122 Heating 113 77 104 68 64 95 59 Outdoor air intake temp. F (DB) Outdoor air intake temp. F (WB) 86 50 1 77 41 68 Operating
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 20
    1. Model Selection and Capacity Calculator Design of 3WAY VRF SYSTEM 1-2. Procedure for Selecting Models and Calculating Capacity Model Selection Procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 21
    1. Model Selectionng and Capacity Calculator Design of 3WAAYYVVRRFFSSYYSSTTEEMM 1-3. Tubing Length Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below. 1. Main tubing length (maximum tubing size) LM = LA + LB
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 22
    1. Model Selecting and Capacity Calculator 1. Model Selection and Capacity Calculator Design of 3WAY VRF SYSTEM *5: If the tubing length marked "L" (L2 - L4) exceeds 131 ft. (40m), increase the tubing size at the portion after the 1st distribution joint by 1 rank for the liquid tube, suction tube
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 23
    11.. MMooddeell SSeelleeccttiinogn aanndd CCaappaacciittyy CCaallccuullaattoorr Design of 3WAY VRF SYSTEM Design of 3WAY VRF SYSTEM Example 1 Outdoor unit 1 L4: 99ft. (30m) Portion increased by one size is overlapped but only one size is increased. LF: 49ft. (15m) LH: 115ft. (35m) LG: 180ft.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 24
    1. Model Selectionng and Capacity Calculator Design of 3WAYYVVRRFFSSYYSSTTEEMM 1-4. Tubing Size Table 2 Main Tubing Size (LA) Between 1st distribution joint for outdoor unit and 1st distribution joint (for indoor unit) Unit: in. (mm) BTU/h (kW) 72,000 96,000 120,000 144,000 168,000 192,000
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 25
    22.3 3 (2.30) (2.80) (3.20) (3.80) (4.70) (5.85) (6.80) Y-branch distribution joint Equivalent length conversion not needed. Ball valve for service Equivalent length conversion not needed. Table 8 Refrigerant tubing (Existing tubing can be used.) Tubing size (in. (mm)) 4 * When bending the
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 26
    1. Model Selectionng and Capacity Calculator Design of 3WAYYVVRRFFSSYYSSTTEEMM Table 10 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit Further charge a certain amount listed below in addition to the amount of refrigerant charge. Combination number of outdoor unit 1 2 3
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 27
    1. Model Selection and Capacity Calculator Design of 3WAY VRF SYSTEM 1-8. Installation Standards Relationship between A/C units and refrigerant tubing Outdoor unit 4-tube layout Suction tube Discharge tube Liquid tube Balance tube Outdoor unit 3-tube layout Suction tube Discharge tube Liquid
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 28
    1. Model Selectionng and Capacity Calculator DeDseigsingnofo2f W3WAAYYVVRRF SYYSSTTEEMM 1-10. Calculation of Actual Capacity of Indoor Unit Calculating the actual capacity of each indoor unit Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 29
    1. Model Selection and Capacity Calculator Design of 3WAY VRF SYSTEM 2. Indoor unit capacity correction coefficient Indoor unit capacity correction (BTU/h) = (G) × ( I ) × (D) * Indoor unit capacity correction ≤ (G) (E) Capacity correction for the indoor unit temperature conditions (BTU/h) From
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 30
    1. Model Selectionng and Capacity Calculator Design of 23WAY VRF SYSTEM 3. Graph of capacity correction coefficients Graph of outdoor unit capacity characteristics (1 - (2)) Outdoor unit cooling capacity characteristics Outdoor unit heating capacity characteristics 125 125 Surplus capacity
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 31
    1. Model Selectionng and Capacity Calculator Design of 32WAY VRF SYSTEM Graph of indoor unit capacity characteristics (2 - (2)) Indoor unit cooling capacity characteristics 140 indicates the rating point. Indoor unit heating capacity characteristics 140 indicates the rating point. Surplus
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 32
    1. Model Selectionng and Capacity Calculator DeDseigsingnofo2f W3WAAYYVVRRF SYYSSTTEEMM The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suction tubes. See Table 14 and make the appropriate changes. However be sure that the
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 33
    2. System Design Design of 3WAY VRF SYSTEM 2-1. System Example Below are the tables created using the "PAC System Diagram Software". Outdoor unit 1 60ft. Elevation difference : 30ft. 30ft. 15ft. 30ft. 15ft. 50ft. 15ft. 15ft. Indoor unit 1 15ft. Indoor unit 2 15ft. 30ft. Indoor unit 3
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 34
    2. System Design Design of 3WAY VRF SYSTEM 2-2. Example of Tubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in Tables 2, 3, 4, 6, 9 and 10, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 35
    2. System Design Design of 3WAY VRF SYSTEM Example: Outdoor unit Type 96 Type 72 B A LA LB 1-1 1 Example of each tubing length Main tubing Distribution joint tubing LA = 131 ft. (40m) Outdoor side Indoor side LB = 16 ft. (4.9m) LC = 16 ft. (4.9m) LC A = 7 ft. (2.1m) B = 7 ft. (2.1m)
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 36
    2. System Design Design of 3WAY VRF SYSTEM 2-3. Installing Distribution Joint CAUTION Pay special attention to any location, such as a basement, etc., where leaking refrigerant can accumulate, since refrigerant gas is heavier than air. (1) Refer to "HOW TO ATTACH DISTRIBUTION JOINT" enclosed
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 37
    3. ELECTRICAL WIRING Design of 3WAY VRF SYSTEM 3-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as (6) Unauthorized changes in the internal wiring can be very shown on its nameplate, then carry out the wiring closely dangerous. The manufacturer will
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 38
    Circuit (R.C.) address should be set before 7 turning the power on. (4) Regarding the R.C. address setting, refer to the separated "SERVICE MANUAL & TEST RUN SERVICE MANUAL U1 U2 1 2 (SM830246)", page 6-7 "5. Auto Address Setting". Address U1 U2 12 Inter-unit Inter-outdoor unit setting can
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 39
    3. ELECTRICAL WIRING Design of 3WAAYYVVRRFFSSYYSSTTEEMM CAUTION (1) When linking outdoor units in a network, see the section "ATTENTION!". (2) Do not install the inter-unit control wiring in a way that forms a loop. Outdoor unit Outdoor unit Outdoor unit Prohibited Prohibited Indoor unit
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 40
    33.. EELlLeEEcCCtrTTicRRaIIlCCWAAiLLrinWWgIIRRIINNGG Design of 3WAY VRF SYSTEM 3-4. Connecting Multiple Indoor Units to a Single Solenoid Valve Kit It is possible to connect multiple indoor units to one solenoid valve kit. The indoor units can be controlled individually or be operated as a group.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 41
    all connected indoor units * Contact your local distributor to obtain a specific program settings software. *1: Refer to "Test Run" for setting instructions. Please note the following system example is prohibited and avoid the following connection. 1 Solenoid valve kit Indoor unit Indoor unit
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 42
    . A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. When connecting each power wire to the terminal, follow the instructions on "How to connect wiring to the terminal" and fasten the wire securely with the fixing screw of the terminal board. Strip 3/8" (10mm
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 43
    3. ELECTRICAL WIRING Design of 3WAAYYVVRRFFSSYYSSTTEEMM U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94 In this case, replace the pins 1 and 2 of the 2P connector (BRN, EMG, CN69) with the pins 2 and 3. Cut out the jumper (JP11). (CR-72MF2U94/ACXA73-02070) Jumper JP11 EMG, CN69 1 2P
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 44
    3. ELECTRICAL WIRING U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94 Electronic component box Inter-unit control wiring (U1, U2) 4P terminal board *1 Inter-outdoor unit control wiring (1, 2) 4P terminal board *1 Terminal board for power supply 3P terminal board *2 Earth terminal *3 1
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 45
    is well ventilated. NOTE Do not do any wiring or tubing within 1 ft. (0.3m) of the front panel, because this space is needed as a servicing space for the compressor. allow enough room around the unit for air intake/exhaust and possible maintenance. Ensure a base height of 4" (100mm) or more to
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 46
    the line of outdoor units and keep distance between each outdoor unit. If you do not allow enough space and distance between units, the following trouble will occur because the passage for fresh air is reduced even if space around collected installation is kept large enough. (A) In case that the
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 47
    4. SELECTING THE INSTALLATION SITE Design of 3WAY VRF SYSTEM 4-2-1. Calculating Method of Collecting Installation Dimensions Determine the number of outdoor units per one block (block of collected outdoor units) Check the length per one block (Lb) Determine the distance between the blocks of
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 48
    4. SELECTING THE INSTALLATION SITE Design of 3WAY VRF SYSTEM Installation dimension of outdoor unit (Distance between blocks) * The length of block (Lb) is calculated by minimum 2-3/8 in. (60 mm) of the distance between the outdoor units (distance between top panels). Lb1 La1 Table 15 Minimum
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 49
    tonnage (Ton/line), find the necessary distance between the lines (Luu) derived from the applicable Figure No. in Table 17. * If the front side (servicing area) of the outdoor units is facing each other and the distance between the lines (Luu) derived 3 from the applied Figure No. in Table 17
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 50
    (2.2) Fig. 4 Distance between the lines (Luu) GU N  Over 5 lines : Concrete foundation (Distance between the lines as open space for service 4 clearance needs minimum 1.64 ft. (0.5 m).) 127.4 111.5 5 95.5 4.92 ft. (1.5 m) 3.212..83604ft.fftt(..1((.000..7m5 )mm)) 6 79.6 63.7 ͔͞Li
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 51
    per line: Ton/line 4.92 ft. (1.5 m) Catwalk installation (Minimum distance between the lines requires 1.64 ft. (0.5 m) as open space for service clearance.) 127.4 111.5 95.5 79.6 3.28 ft. (1.0 m) 2.30 ft. (0.7 m) 1.64 ft. (0.5 Lifting height : Hu ʹ0.66 ft. m) (0.2 m) 63.7 1 47.8 31
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 52
    4. SELECTING THE INSTALLATION SITE Design of 3WAY VRF SYSTEM Ht Hw Hwet α Ht Hu Wall Stack Lw Hl Ineffective opening area Effective opening area Xl Hw Hk Hs Hu Lifting height Xs Xk Xf Hf Fig. 7 Fig. 8 H_ : Width (ft. (m)) 1 X_ : Opening ratio (%) α : Height from the bottom of
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 53
    4. SELECTING THE INSTALLATION SITE Design of 3WAY VRF SYSTEM Step 3 Calculate the effective suction length (Le). If, Lw ≥ 19.7 ft. (6 m), Lwe = 19.7 ft. (6 m) If, Lw < 19.7 ft. (6 m), Lwe = Lw Le1 = Lwe4 + Lm + Lwe2 Le2 = Lwe1 + Ln + Lwe3 Le3 = Le1 Le4 = Le2 Then, calculate the effective
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 54
    Projected wall height (HbP)rowall height (Hb) (In case the air cannot p(Iasnsctahsreo tuhgeh taihrecawnalln.)ot pass through the wall.) Hนb
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 55
    (2m) between the airdischarge outlet and a nearby obstacle. 4-4. Installing the Outdoor Unit in Heavy Snow Areas In locations where wind-blown snow can be a problem, snow-proof ducting (field supply) should be fitted to the unit and direct exposure to the wind should be avoided as much as possible
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 56
    4. SELECTING THE INSTALLATION SITE 4-6. Dimensions of Wind Ducting Reference diagram for air-discharge chamber (field supply) Note: Can be installed so that the air direction is to the front or rear direction. Air direction: Front direction Design of 3WAY VRF SYSTEM unit: in. (mm) Top view 46-11/
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 57
    C : 28-47/64 (730) Installation hole pitch B : 28-47/64 (730) Installation hole pitch downward tubing direction A : 37-61/64 (964) Installation hole pitch forward tubing direction 4. SELECTING THE INSTALLATION SITE Design of 3WAY VRF SYSTEM Reference diagram for air-discharge chamber (field
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 58
    4. SELECTING THE INSTALLATION SITE 4-7. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply) Note: Can be installed so that the air direction is to the front or rear direction. Air direction: Front direction 42-1/4 (1073) Design of 3WAY VRF SYSTEM unit: in. (mm) 34
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 59
    4. SELECTING THE INSTALLATION SITE Design of 3WAY VRF SYSTEM Reference diagram for snow-proof ducting (field supply) (continued) Combination of units For various types of combination. 7-3/32 (180) 8-17/64 (210) 7-3/32 (180) 8-17/64 (210) G E E E D D D unit: in. (mm) 39-3/8 (1000) Top
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 60
    hole pitch) A: 37-61/64 (964) (Installation hole pitch) Vibration insulator Vibration insulator Vibration insulator 5 G D E E DF D D D 2 support area per each leg (x2) must install vibration insulator material and mount. 6 The area of dimension marked with the
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 61
    5. HOW TO INSTALL THE OUTDOOR UNIT Air intake Design of 3WAY VRF SYSTEM Unit: in. (mm) Air intake C B A 39-3/8 (1000) Air intake 45/64 (18) 19/32 (15) 45-9/32 (1150) (Installation hole pitch) 46-29/64 (1180) 1 A : 37-61/64 (964) [Installation hole pitch] * The tubing is routed out from the
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 62
    Connection method Use supplied connector tube? 1 Suction tube Brazing No Service valve mounted on the 2 Discharge tube unit side: Flare counection tubes Remove flare nuts attached to the service valve and reuse them. Note: Make sure the service valve is completely closed. If not, the
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 63
    144 through the front side Bottom plate (6 Ton) (8 Ton) (10 Ton) (12 Ton) Service port cap lbs · inch N · m {kgf · cm} 90-100 10-12 {100- m 170-220 20-25 {200-250} 120-160 14-18 Valve cap width 35/64 (14) Service port cap Flare nut Valve cap 4 ø1/4 (ø6.35) width 35/64 (14) {kgf · cm} {
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 64
    5. HOW TO INSTALL THE OUTDOOR UNIT Design of 3WAY VRF SYSTEM Precautions for brazing Be sure to replace the air inside the tube with nitrogen to prevent oxide film from forming during the brazing process. Be sure to use a damp cloth or other means to cool the valve unit during brazing. Work method
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 65
    6. HOW TO PROCESS TUBING Design of 3WAY VRF SYSTEM The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. 6-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 66
    by refrigerant leakage. In order to prevent damage to the flare caused by over-tightening of the flare nuts, use the table above as a guide when tightening. 7 When tightening the flare nut on the liquid tube, use an adjustable wrench with a nominal handle length of 7-7/8" (200 mm). 8 9 35
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 67
    6. HOW TO PROCESS TUBING Design of 3WAY VRF SYSTEM 6-3. Insulating the Refrigerant Tubing 6-4. Taping the Tubes Tubing Insulation Thermal insulation must be applied to all unit tubing, including the distribution joint (purchased separately). How to arrange 2 tubes (between solenoid valve kit and
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 68
    between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and 1 moisture from the system. ex.)Type 72 Service port cap Air Purging with a Vacuum Pump (for Test Run) Flare nut Preparation Check that each tube between the indoor and outdoor units
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 69
    7. AIR PURGING Design of 3WAY VRF SYSTEM (3) Do a leak test of all joints of the tubing (both indoor and outdoor) and all service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after a leak test. (4) After the system is found to be free of leaks, relieve
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 70
    in the section 1-6 "Additional Refrigerant Charge") using the liquid tube service valve. Use a balance or scale to measure the refrigerant 1 once, charge the remaining refrigerant in liquid form by using the suction tube service valve with the system in Cooling mode at the time of test 2 run
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 71
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-1. Installing Distribution Joint Pay special attention to any location, such as a basement, etc., where leaking refrigerant CCAAUUTTIIOONN can accumulate, since refrigerant gas is heavier than air. (1) Refer to "HOW TO ATTACH DISTRIBUTION JOINT"
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 72
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-2. Optional Distribution Joint Kits Refer to the installation instructions packaged with the distribution joint kit for the installation procedure. Table 18 Model name Cooling capacity after distribution Remarks 1. CZ-P900PH1U 2. CZ-P224BH1U 3.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 73
    8. Optional Parts Design of 3WAY VRF SYSTEM Table 20 Dimensions for connections of each part Position Dimension A ø1-1/2" (ø38.1) B ø1-1/4" (ø31.75) C ø1-1/8" (ø28.58) D ø1" (ø25.4) E ø7/8" (ø22.22) F ø3/4" (ø19.05) G ø5/8" (ø15.88) H ø1/2" (ø12.7) Unit: in. (mm) I J ø3/8" - (ø9.52)
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 74
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-3. Optional Solenoid Valve kit (CZ-P56HR2U / CZ-P160HR2U) 8-3-1. Accessories Part Name Figure Q'ty Remarks Washer 2 For suspension bolts Suspension hook Tapping screw ( L=15/32" (12 mm)) Tapping screw ( L=5/16" (8 mm)) 1 Wire holder 3-Way
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 75
    in the table at right. 5 - 55/64 8 - 21/32 4 - 21/64 Design of 3WAY VRF SYSTEM 7 - 7/8" or more Rear side 7 - 7/8" or more Front side 1 Service space 2 Solenoid Valve Kit Indoor Unit Capacity CZ-P56HR2U Type 18 or under CZ-P160HR2U Type 24 - 54 5 - 55/64 3 2 - 29/32 3 - 5/8 43/64
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 76
    8. Optional Parts Design of 3WAY VRF SYSTEM How to use the fittings Suspension hook Suspension bolt (3/8" or M10) (field supplied) Nut (field supplied) (3/8" or M10) Washer (supplied) ● Tapping screw (L=15/32"(12mm) : supplied ) ● Never use a long screw other than the accessory screw. This may
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 77
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-3-5. ELECTRICAL WIRING 8-3-5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Each wiring connection must be done
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 78
    unit with wet hands. Failure to do so could result in electric shock. 9 * Regarding the solenoid valve relay kit, refer to the indoor unit Installation Instructions. 2 - 62
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 79
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4. Solenoid Valve kit (CZ-P456HR2U / CZ-P656HR2U / CZ-P856HR2U / CZ-P4160HR2U) 8-4-1. Accessories Part Name Figure Type 456 Q'ty Type Type 656 856 Type 4160 Remarks Washer 8 8 8 8 For suspension bolts Tapping screw ( L=5/16" (8 mm)) 16 24 32
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 80
    " in " 8-4-3. Valve Dimensions and Hanging Method".) ● Provide a service space as shown in the below figure. ● Never conduct drilling or more) 7 - 7/8" or more (200 mm or more) Secure the service space 1 for the local tubing Service space Upper side 2 3 Type 456, 656, 4160 Type 856 11
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 81
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-3. Valve Dimensions and Hanging Method ● There are 4 types of solenoid valve kits: type 456, 656, 856 and type 4160. The corresponding indoor unit model capacities are shown in the table at right. Solenoid Valve Kit No. of port CZ-P456HR2U 4 CZ-
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 82
    BB Liquid tube ID N Gas tube ID P How to use the fittings 1.Check the suspension bolt pitch. 2.Ensure that the ceiling is strong enough to support the weight of the unit. 4 3.To prevent the unit from dropping, firmly fasten the suspension bolts as shown in the figure below. Hole-in-anchor
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 83
    8. Optional Parts 8-4-4. Wiring, Tubing and Heat Insulation 8-4-4-1. Refrigerant tubing Design of 3WAY VRF SYSTEM Remove the protection tubes before connection. Cool the tubes with damp cloth or other means Remove the protection tubes Liquid tube 1 when connecting to the left side. Gas tube
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 84
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-5. ELECTRICAL WIRING 8-4-5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Each wiring connection must be done
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 85
    8. Optional Parts Design of 3WAY VRF SYSTEM Wiring ** from control board 8-4-5-3. Wiring System Diagram Indoor unit 1 Electrical box Control board (Main) 3WAY (BLK) 5P Solenoid valve relay kit 1 Control board (CR-SV80A-N) OPTION / 3WAY (WHT) 6P 1 Class Ⅰ Terminal board Power supply field
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 86
    unit with wet hands. Failure to do so could result in electric shock. * Regarding the solenoid valve relay kit, refer to the indoor unit Installation Instructions. 9 2 - 70
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 87
    type solenoid valve kit between Multiple type solenoid valve kit and indoor unit (Lb), increase the tubing size by 1 rank. Refer to the installation instruction of outdoor unit for the La Indoor Lb ≤ 98ft (30m) 3 tubing size. L ≤ 164ft (50m) NOTE The following chart shows that the total
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 88
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-6-2. Series connection by 2 Multiple type solenoid valve kit The length between the Multiple type solenoid valve kits shall be within 0.66ft (0.2m). (See right table for detail about 2 box combination.) Available combination OK :○ × 1 First box 2
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 89
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-6-3. Connection with Distribution Joint Multiple type solenoid valve kit after the distribution joint kit is possible. Outdoor Indoor Indoor Indoor Indoor possible Single type solenoid valve kit Single type solenoid valve kit Multiple type
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 90
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-6-5. 2 ports to be used in parallel ● 2 ports to be used in parallel for the unit 24-48 type Use 856 type, 656 type and 456 type Multiple type solenoid valve kit. ● Use distribution joint to unite 2 outlet ports to 1 port. Outdoor Multiple type
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 91
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-6-7. Single Floor Building Layout Multiple type solenoid valve kit after the distribution joint is possible. Outdoor 0.49ft ≤ (0.15 m ≤ ) La= Farthest indoor unit 0.49ft ≤ (0.15 m ≤ ) Single type solenoid valve kit Indoor Multiple type solenoid
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 92
    8. Optional Parts Design of 3WAY VRF SYSTEM 8-4-6-10. Limitation to Pipe Length Distribution joint and Multiple Type Solenoid Valve Kit (x1) Maximum pipe length from distribution joint indoor unit 164ft (50m) Maximum pipe length from multiple type SVK to each indoor unit 98ft (30m) Multiple
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 93
    8. Optional Parts Design of 3WAY VRF SYSTEM Distribution joint and Multiple type Solenoid Valve Kits (x2) Maximum length from distribution joint to indoor unit 164ft (50m) Maximum length from multiple type SVK to indoor unit 98ft (30m) Multiple Indoor unit "Total capacity (A) (B) Length from
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 94
    8. Optional Parts Design of 3WAY VRF SYSTEM Only Multiple Type Solenoid Valve Kit Maximum length from multiple type solenoid valve kit to indoor unit 98ft (30m) Multiple type SVK Indoor unit distribution joint before multiple type SVK (A) Pipe size from distribution joint to multiple type SVK
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 95
    8. Optional Parts Design of 3WAY VRF SYSTEM Distribution joint and Multiple type Solenoid Valve Kit ʢParallel line connection available to indoor unitʣ Maximum length from distribution joint to indoor unit 164ft (50m) Maximum length from multiple type solenoid valve kit to indoor unit 98ft (30m
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 96
    8. Optional Parts Design of 3WAY VRF SYSTEM Distribution Joint and Multiple Type Solenoid Valve Kit (Parallel line connection at 2 ports) Maximum length from distribution joint to indoor unit Maximum length from multiple type SVK to indoor Unit From multiple type SVK to indoor unit pipes ᶄ and ᶅ
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 97
    Contents Control of 3WAY VRF SYSTEM 3. Control of 3WAY VRF SYSTEM 1. Main Operating Functions 2. Wireless Remote Controller 3. High-spec Wired Remote Controller (CZ-RTC5A) 4. Timer Remote Controller (CZ-RTC4) 5. Simplified Remote Controller (CZ-RE2C2) 6. System Controller (CZ-64ESMC2U) 7.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 98
    - MEMO - 3 - 2
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 99
    CCoonntteennttss 33WWAAYY VVRRFF SSYYSSTTEEMM UUnnEiiltteSScppteercciciiffaiicclaaDttiiaoontnass 4. 3WAY VRF SYSTEM UNIT SPECIFICATIONS 1. Outdoor Unit ...4-2 1-1. Specifications ...4-2 1-2. AHRI Registration Values 4-16 1-3. Dimensional Data ...4-18 1-4. Multiple Unit Installation Example
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 100
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications 1-1. Specifications Unit Specifications (1) Outdoor unit MODEL U-72MF2U9 U-96MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Nominal Cooling capacity Heating capacity Btu/h (kW) Btu/h (kW) 72,000 (21.1) 81,000 (
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 101
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (2) Outdoor unit MODEL U-120MF2U9 U-144MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Nominal Cooling capacity Heating capacity Btu/h (kW) Btu/h (kW) 120,000 (35.2) 135,000 (39.6) 144,000 (
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 102
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (3) Combination Model Name WU-168MF2U9 WU-192MF2U9 Outdoor unit Single Model Name U-72MF2U9 U-96MF2U9 U-72MF2U9 U-120MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Nominal Cooling capacity
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 103
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (4) Combination Model Name WU-216MF2U9 WU-240MF2U9 Outdoor unit Single Model Name U-72MF2U9 U-72MF2U9 U-72MF2U9 U-72MF2U9 U-72MF2U9 U-96MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 104
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (5) Combination Model Name WU-264MF2U9 WU-288MF2U9 Outdoor unit Single Model Name U-72MF2U9 U-72MF2U9 U-72MF2U9 U-72MF2U9 U-120MF2U9 U-144MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 105
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (6) Combination Model Name WU-312MF2U9 WU-336MF2U9 Outdoor unit Single Model Name U-72MF2U9 U-120MF2U9 U-72MF2U9 U-120MF2U9 U-120MF2U9 U-144MF2U9 Performance test condition AHRI Standard 1230 AHRI Standard 1230
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 106
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (7) Combination Model Name WU-360MF2U9 Outdoor unit Single Model Name U-120MF2U9 U-120MF2U9 U-120MF2U9 Performance test condition AHRI Standard 1230 Nominal Cooling capacity Heating capacity Btu/h (kW) Btu/h (kW)
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 107
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (8) Outdoor unit Model U-72MF2U94 U-96MF2U94 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Nominal Cooling capacity Heating capacity Btu/h (kW) Btu/h (kW) 72,000 (21.1) 81,000 (23.7) 96,000 (28
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 108
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (9) Outdoor unit Model U-120MF2U94 U-144MF2U94 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Nominal Cooling capacity Heating capacity Btu/h (kW) Btu/h (kW) 120,000 (35.2) 135,000 (39.6) 144,000
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 109
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (10) Combination Model Name WU-168MF2U94 WU-192MF2U94 Outdoor unit Single Model Name U-72MF2U94 U-96MF2U94 U-72MF2U94 U-120MF2U94 Performance test condition AHRI Standard 1230 AHRI Standard 1230 Nominal Cooling
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 110
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (11) Combination Model Name WU-216MF2U94 WU-240MF2U94 Outdoor unit Single Model Name U-72MF2U94 U-72MF2U94 U-72MF2U94 U-72MF2U94 U-72MF2U94 U-96MF2U94 Performance test condition AHRI Standard 1230 AHRI Standard
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 111
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (12) Combination Model Name WU-264MF2U94 WU-288MF2U94 Outdoor unit Single Model Name U-72MF2U94 U-72MF2U94 U-120MF2U94 U-72MF2U94 U-72MF2U94 U-144MF2U94 Performance test condition AHRI Standard 1230 AHRI Standard
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 112
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (13) Combination Model Name WU-312MF2U94 WU-336MF2U94 Outdoor unit Single Model Name U-72MF2U94 U-120MF2U94 U-72MF2U94 U-120MF2U94 U-120MF2U94 U-144MF2U94 Performance test condition AHRI Standard 1230 AHRI Standard
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 113
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications (14) Combination Model Name WU-360MF2U94 Outdoor unit Single Model Name U-120MF2U94 U-120MF2U94 U-120MF2U94 Performance test condition AHRI Standard 1230 Nominal Cooling capacity Heating capacity Btu/h (kW) Btu/h (
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 114
    - Ducted 336,000 9.3 19.3 23.3 360,000 3.50 256,000 2.40 WU-336MF2U9 Non-Ducted - - - - - - - - Mixed Ducted and Non-Ducted - - - - - - - - 8 Ducted 360,000 9.3 18.0 22.8 386,000 3.30 270,000 2.40 WU-360MF2U9 Non-Ducted - - - - - - - - Mixed Ducted and Non-Ducted
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 115
    2.64 Ducted 192,000 10.5 19.0 25.8 206,000 3.40 148,000 2.50 3 WU-192MF2U94 Non-Ducted 192,000 11.0 23.6 24.9 202,000 3.48 146,000 2.62 Non-Ducted 264,000 10.55 20.75 22.85 280,000 3.37 188,000 2.58 Ducted WU-288MF2U94 Non-Ducted 288,000 9.8 18.5 19.3 300,000 3.25 200,000 2.52 6 288
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 116
    B: 28-47/64 (730) (Installation hole pitch) A: 37-61/64 (964) (Installation hole pitch) G D E E 6 DF D D D Fig. 4-1 2 support area per each leg (×2) must install vibration insulator material and mount. The area of dimension marked with the asterisk (*) must cover
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 117
    ) (90) (2,390) B : inch 7-3/32 100 8-17/64 98-13/16 U-72MF2U94 U-96MF2U94 U-120MF2U94 U-144MF2U94 Installation hole pitch (mm) (180) (2,540) (210) (2,510) WU-168MF2U94 WU-192MF2U94 C : inch 7-3/32 100 8-17/64 98-13/16 Installation hole pitch (mm) (180) (2,540) (210) (2,510) 7 8 4 - 19 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 118
    1. Outdoor Unit 3WAY VRF SYSTEM Unit Specifications WU-216MF2U9, WU-240MF2U9, WU-264MF2U9, WU-288MF2U9 WU-312MF2U9, WU-336MF2U9, WU-360MF2U9 WU-216MF2U94, WU-240MF2U94, WU-264MF2U94, WU-288MF2U94 WU-312MF2U94, WU-336MF2U94, WU-360MF2U94 D 46-29/64(1,180) E D 46-29/64(1,180) 46-29/64(1,180)
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 119
    11..OOuutdtdoooroUr nUitnit 33WWAAYY VVRRFF SSYYSSTTEEMM UUnniitt SSppeecciiffiiccaatitoionnss 1-5. Refrigerant Flow Diagram U-72MF2U9 / U-96MF2U9 U-72MF2U94 / U-96MF2U94 Outside air Electronic control valve Solenoid valve Solenoid valve 4-way valve Oil separator Solenoid valve High pressure
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 120
    11..OOuutdtdoooroUr nUitnit U-120MF2U9 / U-144MF2U9 U-120MF2U94 / U-144MF2U94 Electronic control valve Outside air Solenoid valve 4-way valve Solenoid valve Electronic control valve 1 4-way valve Solenoid valve Solenoid valve Fpluusgible 2 Solenoid valve 3 Solenoid valve 33WWAAYY VVRRFF
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 121
    11..OOuutdtdoooroUr nUitnit 1-6. Noise Criterion Curves Octave Band Level (dB) (0dB = 0.0002 bar) MODEL SOUND LEVEL dB(A) (Cooling/Heating) CONDITION U-72MF2U9 U-72MF2U94 53.0 (Quiet mode 50.0) 3.3 ft in front at height of 4.9 ft 90 80 70 NC -70 60 NC -60 50 NC -50 40 NC -40 30 NC -30
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 122
    - MEMO - 4 - 24
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 123
    Contents Test Run 5. TEST RUN *Refer to the SERVICE MANUAL & TEST RUN SERVICE MANUAL (SM830246) 1 2 3 4 5 6 7 8 5 - 1 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 124
    - MEMO - 1 2 3 4 5 6 7 8 9 5 - 2
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 125
    CCoonntteennttss EElelcectrtricicaallDDaattaa 6. ELECTRICAL DATA 1. Outdoor Unit ...6-2 (1) Electric Wiring Diagram U-72MF2U9 6-2 (2) Electric Wiring Diagram U-96MF2U9 6-4 (3) Electric Wiring Diagram U-120MF2U9 6-6 (4) Electric Wiring Diagram U-144MF2U9 6-8 (5) Electric Wiring Diagram U-
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 126
    11.. OOuuttddoooorr UUnniitt (1) Electric Wiring Diagram U-72MF2U9 1 2 3 4 5 6 7 8 8 9 6 - 2 EElelecctrtricicaallDDaattaa
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 127
    11.. OOuuttddoooorr UUnniitt Schematic Diagram U-72MF2U9 6 - 23 E&leMFcDtrUiScJDaBlMD%aBtUaB 1 2 3 4 5 6 7 8 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 128
    11.. OOuuttddoooorr UUnniitt (2) Electric Wiring Diagram U-96MF2U9 1 2 3 4 5 6 7 8 8 9 6 - 4 EElelecctrtricicaallDDaattaa
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 129
    11.. OOuuttddoooorr UUnniitt Schematic Diagram U-96MF2U9 6 - 25 E&leMFcDtrUiScJDaBlMD%aBtUaB 1 2 3 4 5 6 7 8 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 130
    11.. OOuuttddoooorr UUnniitt (3) Electric Wiring Diagram U-120MF2U9 1 2 3 4 5 6 7 8 8 9 66 - 26 E&leMFcDtrUiScJDaBlMD%aBtUaB
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 131
    11.. OOuuttddoooorr UUnniitt Schematic Diagram U-120MF2U9 6 - 27 E&leMFcDtrUiScJDaBlMD%aBtUaB 1 2 3 4 5 6 7 8 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 132
    11.. OOuuttddoooorr UUnniitt (4) Electric Wiring Diagram U-144MF2U9 1 2 3 4 5 6 7 8 8 9 6 - 28 E&leMFcDtrUiScJDaBlMD%aBtUaB
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 133
    11.. OOuuttddoooorr UUnniitt Schematic Diagram U-144MF2U9 6 - 29 E&leMFcDtrUiScJDaBlMD%aBtUaB 1 2 3 4 5 6 7 8 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 134
    1 2 3 4 5 6 7 8 8 9 11.. OOuuttddoooorr UUnniitt (5) Electric Wiring Diagram U-72MF2U94,U-96MF2U94 8FA2-5251-426-00-2 GRN GRN RED WHT GRN WHT WHT WHT WHT WHT WHT WHT RED RED BLK BLK WHT ELECTRIC WIRING DIAGRAM 460V 60Hz 3-PH TO INDOOR TO OUTDOOR UNIT SUB UNIT TERMINAL L1 L2 L3 BOARD
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 135
    EElelcectrtricicaallDDaattaa 1 2 3 4 5 6 7 8 9 11.. OOuuttddoooorr UUnniitt Schematic Diagram U-72MF2U94,U-96MF2U94 6 - 11 TERMINAL PLATE 3P L1 L1 L2 L2 L3 L3 8FA2-5251-426-00-2 FUSE604 (4A500V) FUSE603 (T3.15A L250V) ~ ~ L1 L2 L3 FG1 W FG2 W FUSE600(30A500V) L1-OUT W FUSE601(30A500V) LF LF
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 136
    1 2 3 4 5 6 7 8 8 9 11.. OOuuttddoooorr UUnniitt (6) Electric Wiring Diagram U-120MF2U94,U-144MF2U94 8FA2-5251-425-00-2 RED WHT BLK GRN GRN RED WHT GRN WHT WHT WHT WHT WHT WHT WHT RED RED RED RED BLK WHT GRN GRN GRN WHT WHT WHT WHT WHT WHT WHT WHT ELECTRIC WIRING DIAGRAM 460V 60Hz 3-PH
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 137
    11.. OOuuttddoooorr UUnniitt Schematic Diagram U-120MF2U94,U-144MF2U94 6 - 13 8FA2-5251-425-00-2 TERMINAL BOARD 3P L1 L1 L2 L2 L3 L3 FUSE604 (4A500V) FUSE603 (T3.15A L250V) ~ FUSE604 (4A500V) FUSE603 (T3.15A L250V) ~ ~ L1 L2 L3 FG1 W FG2 W FUSE600(30A500V) L1-OUT W FUSE601(30A500V) LF LF L2-
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 138
    - MEMO - 6 - 14
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 139
    CCoonntteennttss PCB and Functions 7. PCB AND FUNCTIONS 1. Outdoor Unit Control PCB 7-2 1-1. Outdoor Unit Control PCB CR-72MF2U9 / A748186 7-2 1-2. Outdoor Unit Control PCB CR-144MF2U9 / A748187 7-3 1-3. Outdoor Unit Control PCB ACXA73-02070 7-4 1-4. Outdoor Unit HIC PCB A747843 7-5
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 140
    1. Outdoor Unit Control PCB PCB and Functions 1-1. Outdoor Unit Control PCB CR-72MF2U9 / A748186 (U-72MF2U9 / U-96MF2U9 ) Terminal pin (CN67) HIC3(CN43) RC1 plug (CN75) OC plug (CN76) RC plug (CN73) 1 EMG plug (CN69) 2 Alarm LED (LED1) Alarm LED (LED2) SW5 3 EEPROM LED (LED3) SW6 4 5
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 141
    1. Outdoor Unit Control PCB 1-2. Outdoor Unit Control PCB CR-144MF2U9 / A748187 (U-120MF2U9 / U-144MF2U9 ) Terminal pin (CN67) HIC7(CN78) HIC3(CN43) RC1 plug (CN75) OC plug (CN76) RC plug (CN73) EMG plug (CN69) PCB and Functions Alarm LED (LED1) Alarm LED (LED2) 1 EEPROM LED (LED3) EEPROM
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 142
    1. Outdoor Unit Control PCB PCB and Functions 1-3. Outdoor Unit Control PCB ACXA73-02070 (U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94) CN34 CN33 LPS(CN49) OIL1,2(CN54) HPS(CN46) DISCH1(CN55) DISCH2(CN56) EXL1,2(CN60) TO(CN53) SW4 SW3 SW2 SW1 CN22 CN23 CN25 CN24 EXG1,2(CN61) SCT(
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 143
    1. Outdoor Unit Control PCB 1-4. Outdoor Unit HIC PCB A747843 (U-72MF2U9 / U-120MF2U9 / U-144MF2U9) PCB and Functions 1 2 3 PUVWN 1-5. Outdoor Unit HIC PCB A747846 (U-96MF2U9) 4 5 6 7 8 P NU VW 7 - 5 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 144
    1. Outdoor Unit Control PCB 1-6. Outdoor Unit HIC PCB ACXA73-02090 (U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94) PCB and Functions 1 2 3 4 5 6 P U V W NU NV NW 7 8 9 7 - 6
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 145
    1. Outdoor Unit Control PCB 1-7. Outdoor Unit Filter PCB A747842 (U-72MF2U9 / U-120MF2U9 / U-144MF2U9) A747845 (U-96MF2U9) ACXA73-02080 (U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94) 7 - 7 PCB and Functions 1 2 3 4 5 6 7 8 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 146
    11.. OOuuttddoooorr UUnniitt CCoonnttrrooll PPCCBB 1-8. Outdoor Unit FAN PCB A747844 (U-72MF2U9 / U-96MF2U9 / U-120MF2U9 / U-144MF2U9) 1 2 3 P W V UN 4 ACXA73-02100 (U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94) 5 P 6 U V W 7 NU NV 8 NW 9 7 - 8 PCB and Functions PCB and
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 147
    1. Outdoor Unit Control PCB 1-9. Outdoor Unit Relay PCB ACXA73-02110 (U-72MF2U94 / U-96MF2U94 / U-120MF2U94 / U-144MF2U94) 7 - 9 PCB and Functions 1 2 3 4 5 6 7 8 9
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 148
    1. Outdoor Unit Control PCB PCB and Functions 1-10. Functions A. ADD pin (2P, White) (CN30) Auto address setting pin • Short-circuit this pin for 1 second or longer to automatically set the addresses at the indoor units that are connected to that outdoor unit and are within the same system. •
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 149
    systems into a single communications circuit, when using, refer to the item "5. Auto Address Setting" under the section "6. TEST RUN" in the Service Manual. LED1, 2 • LED 1 and 2 blink alternately while auto address setting is in progress. • Display the alarm contents for alarms which were
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 150
    1. Outdoor Unit Control PCB PCB and Functions Table 7-1. Setting the System Address [SW1: Rotary switch (Black), SW2: 2P DIP (Black)] Outdoor system address SW1 setting SW2 setting 1P 2P (10s digit) (20s digit) 1 1 OFF OFF 2 2 OFF OFF 3 3 OFF OFF 4 4 OFF OFF 5 5 OFF OFF
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 151
    Contents Capacity Table 8. CAPACITY TABLE 1. Capacity Ratio of Outdoor Unit 8-1-2 1-1. U-72MF2U9 (Cooling 8-1-2 1-2. U-72MF2U9 (Heating 8-1-4 1-3. U-96MF2U9 (Cooling 8-1-6 1-4. U-96MF2U9 (Heating 8-1-8 1-5. U-120MF2U9 (Cooling 8-1-10 1-6. U-120MF2U9 (Heating 8-1-12 1-7. U-144MF2U9 (
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 152
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-1. U-72MF2U9 (Cooling) Combination(%) : Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 59.9 3.06 59.9 3.06 59.9 3.06 59.9 3.06 59.9 3.06 59.9 3.08 59.9 3.14 59
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 153
    1. Capacity Ratio of Outdoor Unit Capacity Table U-72MF2U9 (Cooling) Combination(%) : Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 36.9 1.48 36.9 1.48 36.9 1.48 36.9 1.48 36.9 1.48 36.9 1.48 36.9 1.48 36.9 1.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 154
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-2. U-72MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 155
    1. Capacity Ratio of Outdoor Unit Capacity Table U-72MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0 64
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 156
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-3. U-96MF2U9 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 79.9 4.82 79.9 4.82 79.9 4.82 79.9 4.82 79.9 4.84 79.9 4.88 79.9 4.98 79
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 157
    1. Capacity Ratio of Outdoor Unit Capacity Table U-96MF2U9 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.32 49.2 2.41
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 158
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-4. U-96MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 159
    1. Capacity Ratio of Outdoor Unit Capacity Table U-96MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0 64.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 160
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-5. U-120MF2U9 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 99.8 6.25 99.8 6.25 99.8 6.25 99.8 6.25 99.8 6.27 99.8 6.30 99.8 6.40 99
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 161
    1. Capacity Ratio of Outdoor Unit Capacity Table U-120MF2U9 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.01 61.4 3.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 162
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-6. U-120MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 163
    1. Capacity Ratio of Outdoor Unit Capacity Table U-120MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0 64
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 164
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-7. U-144MF2U9 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 119.8 7.21 119.8 7.21 119.8 7.22 119.8 7.22 119.8 7.25 119.8 7.31 119.8
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 165
    1. Capacity Ratio of Outdoor Unit Capacity Table U-144MF2U9 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.48 73.7 3.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 166
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-8. U-144MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 167
    1. Capacity Ratio of Outdoor Unit Capacity Table U-144MF2U9 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0 64
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 168
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-9. U-72MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 59.9 3.06 59.9 3.06 59.9 3.06 59.9 3.06 59.9 3.06 59.9 3.08 59.9 3.14 59
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 169
    1. Capacity Ratio of Outdoor Unit Capacity Table U-72MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 36.9 1.49 36.9 1.49 36.9 1.49 36.9 1.49 36.9 1.48 36.9 1.48 36.9 1.48 36.9 1.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 170
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-10. U-72MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 171
    1. Capacity Ratio of Outdoor Unit Capacity Table U-72MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0 64
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 172
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-11. U-96MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 79.9 4.82 79.9 4.82 79.9 4.82 79.9 4.82 79.9 4.84 79.9 4.88 79.9 4.98
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 173
    1. Capacity Ratio of Outdoor Unit Capacity Table U-96MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.31 49.2 2.32 49.2 2.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 174
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-12. U-96MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 175
    1. Capacity Ratio of Outdoor Unit Capacity Table U-96MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0 64
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 176
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-13. U-120MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 99.8 6.25 99.8 6.25 99.8 6.25 99.8 6.25 99.8 6.27 99.8 6.30 99.8 6.40
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 177
    1. Capacity Ratio of Outdoor Unit Capacity Table U-120MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.00 61.4 3.01 61.4 3.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 178
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-14. U-120MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 179
    1. Capacity Ratio of Outdoor Unit Capacity Table U-120MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 180
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-15. U-144MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 119.8 7.21 119.8 7.21 119.8 7.22 119.8 7.22 119.8 7.25 119.8 7.31 119.8
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 181
    1. Capacity Ratio of Outdoor Unit Capacity Table U-144MF2U94 (Cooling) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB 14 23 32 36 46 55 65 75 85 95 104 110 115 122 57 TC PI MBH kW 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.45 73.7 3.48 73.7 3.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 182
    1. Capacity Ratio of Outdoor Unit Capacity Table 1-16. U-144MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 130% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 183
    1. Capacity Ratio of Outdoor Unit Capacity Table U-144MF2U94 (Heating) Combination(%) :Indoor/outdoor capacity ratio 80% Outdoor air temp. °FDB -12.8 -3.6 2.9 9.3 16.9 22.2 28.7 35.2 39.5 43.8 47.0 51.3 58.8 64.2 69.6 °FWB -13.0 -4.0 2.0 8.0 15.0 20.0 26.0 32.0 36.0 40.0 43.0 47.0 54.0 59.0
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 184
    2. Cooling Capacity of Indoor Unit Capacity Table 2-1. Concealed duct - Medium Static (Type F2) Indoor Unit : S-07MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 185
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 186
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 187
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-15MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 15.0 MBH 14 TC 9.6 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 188
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 19.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 189
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-24MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 25.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 190
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-36MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 36.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 191
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-48MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 47.8 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 192
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-54MF2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 54.6 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 193
    2. Cooling Capacity of Indoor Unit Capacity Table 2-2. Wall Mounted (Type K2) Indoor Unit : S-07MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 194
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 195
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 196
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 18.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 197
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-24MK2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 25.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 198
    2. Cooling Capacity of Indoor Unit Capacity Table 2-3. 4-Way Cassette 24"×24" (Type Y2) Indoor Unit : S-07MY2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 199
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MY2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 200
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MY2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 201
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MY2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 19.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 202
    2. Cooling Capacity of Indoor Unit Capacity Table 2-4. Concealed duct - Low Static (Type M2) Indoor Unit : S-07MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 203
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 204
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 205
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-15MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 15.0 MBH 14 TC 9.6 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 206
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MM2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 19.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 207
    2. Cooling Capacity of Indoor Unit Capacity Table 2-5. 4-Way Cassette 36"×36" (Type U2) Indoor Unit : S-07MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 208
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 209
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: 12.0 MBH AIR FLOW RATE: 494 CFM EVAPORATOR AIR INTAKE. TEMP CONDENSER
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 210
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-24MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 25.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 211
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-36MU2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 36.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 212
    2. Cooling Capacity of Indoor Unit Capacity Table 2-6. Ceiling (Type T2) Indoor Unit : S-12MT2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 213
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MT2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 19.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 214
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-24MT2U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 25.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 215
    2. Cooling Capacity of Indoor Unit Capacity Table 2-7. 1-Way Cassette (Type D1) Indoor Unit : S-07MD1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 216
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MD1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 217
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MD1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 218
    2. Cooling Capacity of Indoor Unit Capacity Table 2-8. Concealed duct - High Static (Type E1) Indoor Unit : S-36ME1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE.
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 219
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-48ME1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 47.8 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 220
    2. Cooling Capacity of Indoor Unit Capacity Table 2-9. Floor Standing (Type P1) Indoor Unit : S-07MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 221
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 222
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 223
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-15MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 15.0 MBH 14 TC 9.6 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 224
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 19.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 225
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-24MP1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 24.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 226
    2. Cooling Capacity of Indoor Unit Capacity Table 2-10. Concealed Floor Standing (Type R1) Indoor Unit : S-07MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 227
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-09MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 9.6 MBH 14 TC 6.1 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 228
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-12MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 12.0 MBH 14 TC 7.7 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 229
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-15MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 15.0 MBH 14 TC 9.6 AIR
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 230
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-18MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 19.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 231
    2. Cooling Capacity of Indoor Unit Capacity Table Indoor Unit : S-24MR1U6 Outdoor Unit : U-144MF2U9 Power supply : 208 - 230V 1phase-60Hz TC : Total Cooling Capacity (MBH) SHC : Sensible Heat Capacity (MBH) RATING CAPACITY: EVAPORATOR AIR INTAKE. TEMP °FW.B. °FD.B. 24.0 MBH AIR FLOW RATE:
  • Panasonic WU-216MF2U9 | - Technical Data Manual - Page 232
    201808
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211
  • 212
  • 213
  • 214
  • 215
  • 216
  • 217
  • 218
  • 219
  • 220
  • 221
  • 222
  • 223
  • 224
  • 225
  • 226
  • 227
  • 228
  • 229
  • 230
  • 231
  • 232

3WAY VRF
System
U-72MF2U9
U-96MF2U9
U-120MF2U9
U-144MF2U9
U-72MF2U94
U-96MF2U94
U-120MF2U94
U-144MF2U94
REFERENCE NO.
TD831183-03
Order No. SBPAC1509016CE
Model No.
To be connecting Indoor Units
This air conditioner uses the refrigerant R410A.
7
9
12
15
18
24
36
48
54
Y2
D1
F2
M2
E1
T2
K2
P1
R1
Concealed Floor Standing
Outdoor Unit
72
96
12
1
0
44
Nominal Capacity
MF2
3WAY VRF System
U-72MF2U9
U-96MF2U9
U-120MF2U9
U-144MF2U9
U-72MF2U94
U-96MF2U94
U-120MF2U94
U-144MF2U94
Outdoor Unit Type
Type
Indoor Units
Nominal Capacity
U2
4-Way Cassette 36"x36"
Indoor Unit Type
Type
S-12MY2U6
S-12MD1U6
S-12MF2U6
S-12MM2U6
S-09MD1U6
S-09MF2U6
S-09MM2U6
S-07MD1U6
S-12MU2U6
S-09MU2U6
S-07MU2U6
S-09MY2U6
S-07MY2U6
S-07MF2U6
S-07MM2U6
S-12MT2U6
S-12MK2U6
S-12MP1U6
S-12MR1U6
S-15MF2U6
S-15MM2U6
S-15MP1U6
S-15MR1U6
S-09MK2U6
S-09MP1U6
S-09MR1U6
S-07MK2U6
S-07MP1U6
S-07MR1U6
S-18MY2U6
S-18MF2U6
S-18MM2U6
S-18MT2U6
S-18MK2U6
S-18MP1U6
S-18MR1U6
S-24MU2U6
S-24MF2U6
S-36MU2U6
S-36MF2U6
S-36ME1U6
S-48MF2U6
S-54MF2U6
S-48ME1U6
S-24MT2U6
S-24MK2U6
S-24MP1U6
S-24MR1U6
Concealed Duct
-High Static
Concealed Duct
-Low Static
Concealed Duct
-Medium Static
4-Way Cassette 24"x24"
1-Way Cassette
Ceiling
Wall Mounted
Floor Standing