Asko TL751XXL User manual 20 200 20 Asko TL751 XXL EN - Page 36

wire connection: Direct wire

Page 36 highlights

3-wire receptacle (NEMA type10-30R) Electrical requirements 4-wire connection: Direct wire Caution! Grounding through the neutral conductor is prohibited for 1. New branch-circuit installations. 2. Mobile homes. 3. Recreational vehicles 4. Areas where local codes prohibit grounding through the neutral conductor. Prepare minimum 5 ft. (1.52 m) of length in order for dryer to be replaced. First, peel 5" (12.7 cm) of covering material from end. Strip 5 inches of ground wire insulation. After cutting 1 1/2" (3.8 cm) from 3 other wires peel insulation back 1" (2.5 cm). Make ends of 3 wires a hook shape. Then, put the hooked shape end of the wire under the screw of the terminal block (hooked end facing rightward) and pinch the hook together and tighten the screw securely. 1. Connect neutral wire (white) of power 4-wire direct cord to center terminal block screw. 2. Connect red and black wires to the left and right terminal block screws. 3. Make sure that the strain relief screw is tightened. Be sure that all terminal block nuts are on tight and power cord is in right position. 3-wire direct 36 Customer Care Center 1-800-898-1879 www.askousa.com

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47

36
Customer Care Center
1-800-898-1879
www.askousa.com
Electrical requirements
4-wire connection: Direct wire
Caution!
Grounding through the
neutral conductor is
prohibited for
New branch-circuit
1.
installations.
Mobile homes.
2.
Recreational vehicles
3.
Areas where local codes prohibit
4.
grounding through the neutral
conductor.
Prepare minimum 5 ft. (1.52 m) of length in
order for dryer to be replaced.
First, peel 5” (12.7 cm) of covering material
from end. Strip 5 inches of ground wire
insulation. After cutting 1 1/2” (3.8 cm) from
3 other wires peel insulation back 1” (2.5
cm). Make ends of 3 wires a hook shape.
Then, put the hooked shape end of the
wire under the screw of the terminal block
(hooked end facing rightward) and pinch
the hook together and tighten the screw
securely.
Connect neutral wire (white) of power
1.
cord to center terminal block screw.
Connect red and black wires to the left
2.
and right terminal block screws.
Make sure that the strain relief screw is
3.
tightened.
Be sure that all terminal block nuts are on
tight and power cord is in right position.