Fluke 902 Fluke 902 HVAC Clamp Meter Datasheet
Fluke 902 Manual
View all Fluke 902 manuals
Add to My Manuals
Save this manual to your list of manuals |
Fluke 902 manual content summary:
- Fluke 902 | Fluke 902 HVAC Clamp Meter Datasheet - Page 1
of quality Fluke clamp meters by delivering the features necessary to diagnose and repair HVAC systems. Combined with True RMS technology and a CAT III 600 V rating, the Fluke 902 helps technicians do their jobs safely and accurately. N10140 Use the Fluke 902 to: • Capture flue gas temperatures - Fluke 902 | Fluke 902 HVAC Clamp Meter Datasheet - Page 2
Information Fluke-902 HVAC Clamp Meter Included AA alkaline batteries (2) Users manual (w/safety information) Soft carrying case TL75 Test Leads (1 pair) 80BK Integrated DMM Temperature Probe (1) Optional accessories H3 Clamp Meter Holster • Rugged fabric holster includes flap for lead storage
Technical Data
Fluke 902
True-rms HVAC Clamp Meter
Use the Fluke 902 to:
•
Capture flue gas temperatures
•
Conduct flame rod testing
•
Measure start and run motor capacitors
•
Measure performance of variable frequency drives
Features include:
•
Capacitance
•
DC current to 200 uA
•
Contact temperature (K-type thermocouple)
•
True-rms
•
Min/Max
•
Hold
Heating, ventilation, air conditioning (HVAC)
technicians require a service tool that can
consistently keep up with their demands.
The Fluke 902 expands the existing line of
quality Fluke clamp meters by delivering the
features necessary to diagnose and repair
HVAC systems.
Combined with True RMS
technology and a CAT III 600 V rating, the
Fluke 902 helps technicians do their jobs
safely and accurately.
N10140
Specifications
Feature
Range
Accuracy
Voltage dc
0 to 600.0 V
1 % ± 5 counts
Voltage ac
(true-rms)
0 to 600.0 V
1 % ± 5 counts (50/60 Hz)
Current ac
(true-rms)
0 to 600.0 A
2.0 % ± 5 counts (50/60 Hz)
Current dc
0 to 200.0 µA
1.0 % ± 5 counts
Resistance
0 to 9999
W
1.5 % ± 5 counts
Continuity
<= 30
W
Temperature*
(Type-K
thermocouple)
-10 °C to 400 °C
(-14 °F to 752 °F)
-40 °C to -10 °C
(-40 °F to -14 °F)
± 1.0 % + 0.8 °C
(± 1.0 % + 1.5 °F) typical
± 5.0 % + 1.5 °C
(± 5.0 % + 3.3 °F) typical
Capacitance
1 µF to 1000 µF
1.9 % ± 2 counts
Warranty
Three-years