GE GE80T06AAG Use and Care Manual - Page 7

Relief Valve, To Fill the Water Heater, Condensation

Page 7 highlights

Safety Instructions Installation Instructions Operating Instructions A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must remain installed in the opening provided and marked for the purpose on the water heater. No valve of any type should be installed between the relief valve and the tank. Local codes shall govern the installation of relief valves. Relief Valve WARNING: The pressure rating of the relief valve must not exceed 150 PSI, the maximum working pressure of the water heater as marked on the rating plate. The BTUH rating of the relief valve must not be less than the input rating of the water heater as indicated on the rating label located on the front of the heater (1 watt=3.412 BTUH). Connect the outlet of the relief valve to a suitable open drain so that the discharge water cannot contact live electrical parts or persons and to eliminate potential water damage. Piping used should be of a type approved for hot water distribution. The discharge line must be no smaller than the outlet of the valve and must pitch downward from the valve to allow complete drainage (by gravity) of the relief valve and discharge line. The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed in the discharge line. To Fill the Water Heater WARNING: The tank must be full of water before heater is turned on. The water heater warranty does not cover damage or failure resulting from operation with an empty or partially empty tank. (Refer to the Certificate of Limited Warranty for complete terms and conditions.) Make certain the drain valve is completely closed. Open the shut-off valve in the cold water supply line. Open each hot water faucet slowly to allow the air to vent from the water heater and piping. A steady flow of water from the hot water faucet(s) indicates a full water heater. Condensation Condensation can form on the tank when it is first filled with water. Condensation might also occur with a heavy water draw and very cold inlet water temperature. This condition is not unusual, and will disappear after the water becomes heated. If, however, the condensation continues, examine the piping and fittings for possible leaks. Additional information on this subject may be found at www.rheem.com under "Library". Scroll down to the Technical Service Bulletins 1300 Series Section and choose Bulletin #1303. Care and Cleaning Troubleshooting Tips Customer Service 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

WARNING: The pressure
rating of the relief valve
must not exceed 150 PSI,
the maximum working
pressure of the water
heater as marked on
the rating plate.
A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves
and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must
remain installed in the opening provided and marked for the purpose on the water heater. No valve of any
type should be installed between the relief valve and the tank. Local codes shall govern the installation of
relief valves.
Relief Valve
The BTUH rating of the relief valve must
not be less than the input rating of the
water heater as indicated on the rating
label located on the front of the heater
(1 watt=3.412 BTUH).
Connect the outlet of the relief valve
to a suitable open drain so that the
discharge water cannot contact live
electrical parts or persons and to
eliminate potential water damage.
Piping used should be of a type approved
for hot water distribution. The discharge
line must be no smaller than the outlet
of the valve and must pitch downward
from the valve to allow complete
drainage (by gravity) of the relief valve
and discharge line. The end of the
discharge line should not be threaded or
concealed and should be protected from
freezing. No valve of any type, restriction
or reducer coupling should be installed in
the discharge line.
To Fill the Water Heater
WARNING: The tank must be full of
water before heater is turned on. The
water heater warranty does not cover
damage or failure resulting from
operation with an empty or partially
empty tank.
(Refer to the Certificate of
Limited Warranty for complete terms
and conditions.)
Make certain the drain valve is completely
closed.
Open the shut-off valve in the cold water
supply line.
Open each hot water faucet slowly to
allow the air to vent from the water
heater and piping.
A steady flow of water from the hot water
faucet(s) indicates a full water heater.
7
Safety Instructions
Installation Instructions
Operating Instructions
Care and Cleaning
Troubleshooting Tips
Customer Service
Condensation
Condensation can form on the tank
when it is first filled with water.
Condensation might also occur with a
heavy water draw and very cold inlet
water temperature.
This condition is not unusual, and will
disappear after the water becomes
heated.
If, however, the condensation
continues, examine the piping and
fittings for possible leaks.
Additional information on this subject
may be found at
www
.rheem.com
under “Library”. Scroll down to the
Technical Service Bulletins 1300 Series
Section and choose Bulletin #1303.