Haier AU482FIERA Installation Manual - Page 72

High pressure overhigh protection

Page 72 highlights

6. High pressure overhigh protection Are connectors of pressure switch in good condition? yes Is high pressure switch activated? yes no Check and reconnect no replace PCB Is pressure value detected by pressure gauge above 3MPa? yes no Replace high pressure switch Are stop valves in suction pipe and liquid pipe of outdoor unit open? yes Is piping twisted or deformed? no no Open stop valve yes Repair or replacement if outdoor fan motor work properly during cooling cycle? and if indoor fan motor and indoor EEV work properly during heating cycle? no Check fan motor or indoor EEV yes Is filter or heat exchanger dirty? no yes cleaning Is system overfed? Is there air in system? Is reading of discharging pipe pressure gauge oscillatory? yes Evacuate and recharge 71

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76

replace PCB
no
no
switch
in good condition?
yes
yes
Check and reconnect
Is high pressure switch activated?
no
Is pressure value detected by
no
Replace high pressure switch
yes
yes
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
no
Is piping twisted or deformed?
Open stop valve
yes
Repair or
replacement
no
if outdoor fan motor work properly during cooling
cycle? and if indoor fan motor and indoor EEV
work properly during heating cycle?
Check fan motor
or indoor EEV
yes
Is filter or heat exchanger dirty?
no
yes
cleaning
Is system overfed? Is there air in system?
Is reading of discharging pipe pressure
gauge oscillatory?
yes
Evacuate and recharge
6. High pressure overhigh protection
Are connectors of pressure
pressure gauge above 3MPa?
71