Haier AU60NAIEAA User Manual - Page 5

Installation Procedure

Page 5 highlights

Installation Procedure Installation of outdoor unit 1. Accessories "Edging" for protection of electric wires from an opening edge. Edging 2. Selection of the place of installation Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user. Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting. (1) Open space requirement around the unit Air inlet L3 L2 500 Air (Servicing inlet space) Air outlet L1 Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the outlet air-flow hole. (3).A one meter distance should be kept from the unit top (4).Don't block the surroundings of the unit with sundries Case Distance I II L1 open open L2 300 300 L3 150 300 Unit: mm III 500 open 150 NO Wind direction (2) Installation where the area with strong winds. Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction. 4

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15

Note :
(1). Fix the parts with screws
(2).Don't intake the strong wind directly to the
outlet air-flow hole.
(3).A one meter distance should be kept from the
unit top
(4).Don't block the surroundings of the unit with
sundries
Installation Procedure
2. Selection of the place of installation
1. Accessories
"Edging" for protection of electric wires from an
opening edge.
Select the place of installation satisfying the following conditions and, at the
same time, obtain a consent from the client or user.
Edging
Place where air circulates.
Place free from heat radiation from other heat sources.
Place where drain water may be discharged.
Place where noise and hot air may not disturb the neighborhood.
Place where there is not heavy snowfall in the winter time.
Place where obstacles do not exist near the air inlet and air outlet .
Place where the air outlet may not be exposed to a strong wind.
Place surrounded at four sides are not suitable for installation. A 1m or more
of overhead space is needed for the unit.
Mount guide-louvers to place where short-circuit is a possibility.
When installing several units, secure sufficient suction space to avoid short
circuiting.
Wind direction
NO
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced
toward wind direction.
(1) Open space requirement around the unit
L
2
L
3
L
1
500
(Servicing
space)
Air outlet
Air inlet
Air
inlet
Case
Distance
Unit: mm
open
open
open
500
150
150
300
300
300
L
1
L
2
L
3
I
II
III
Installation of outdoor unit
4