Outdoor unit Outdoor unit 1.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe Connecting the pipe of gas side first makes working easier. The max vertical distance between the indoor unit and the outdoor unit is 5 m. Half union Flare nut Forced fastening without careful centering may damage the threads and cause a leakage of gas. Spanner Torque wrench Be careful that matters, such as wastes of sands, etc. shall not enter the pipe. 2.Attaching Drain-Elbow Pipe Diameter ( ) Fastening torque Liquid side 6.35mm(1/4") Liquid side 9.52mm(3/8") Gas side 9.52mm(3/8") Gas side 12.7mm(1/2") Gas side 15.88mm(5/8") 18N.m 40N.m 40N.m 50N.m 60N.m If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.) 3.Purging Method: Push the air out of the indoor unit and piping as followes: Tighten the caps on the valves with specified torque. Tighten torque N.m Valve rod 7-9 Valve cap 20-25 When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k 24k) refrigerant shall be added per exceeding meter. Charge according to the following list. for 5k 7k 9k 10k 12k 13k 18k Piping length 5m 7m 10m Piping length for 22k 24k 5m 7m 10m Additional amount No need 40g 100g Additional amount No need 120g 300g 20m 900g Indoor unit A Outdoor unit B A B Indoor unit Outdoor unit Max.Elevation: for 5K 7K 9K 10K 12K 13K: B=5m for 18K 22K 24K: B=10m Max. Length: for 5K 7K 9K 10K: A=7m for 12K 13K: A=10m for 18K 22K 24K: A=20m 4 Outdoor unit A B Oil trap C Indoor unit CAUTION In case more than 5 metres,oil trap C should be installed every 5~7m.

  • 1
  • 2
  • 3
  • 4

Outdoor unit
1.Connection of pipes
2.Attaching Drain-Elbow
To bend a pipe, give the roundness as large as possible not to crush the pipe
Connecting the pipe of gas side first makes working easier.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)
Half union
Flare nut
Spanner
Torque wrench
4
Outdoor unit
Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.
Be careful that matters, such as wastes of sands, etc.
shall not enter the pipe.
3.Purging Method:
Push the air out of the indoor unit and piping as followes:
Tighten the caps on the valves with specified torque.
Valve rod
Valve cap
7-9
20-25
Tighten torque N.m
When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k
24k) refrigerant shall be
added per exceeding meter. Charge according to the following list.
Piping length
Additional amount
5m
7m
No need
40g
10m
100g
for 5k 7k 9k 10k 12k 13k 18k
for
22k 24k
Max. Length:
for 5K 7K 9K 10K: A=7m
for 12K 13K:
A=10m
for 18K 22K 24K: A=20m
Max.Elevation:
for
5K 7K 9K 10K 12K 13K: B=5m
for 18K 22K 24K: B=10m
Piping length
Additional amount
5m
7m
No need
120g
10m
300g
20m
900g
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
B
A
C
Outdoor unit
Indoor unit
Oil trap
A
B
CAUTION
In case more than 5 metres
oil trap
should be installed every 5~7m.
C
Pipe Diameter
(
)
Liquid side
6.35mm(1/4")
Gas side
9.52mm(3/8")
Fastening torque
18N.m
40N.m
Gas side
12.7mm(1/2")
50N.m
Gas side
15.88mm(5/8")
60N.m
Liquid side
9.52mm(3/8")
40N.m