Table 17 Site Inspection Checklist, continued

Page 31 highlights

Table 17 Site Inspection Checklist (continued) Check either Yes or No. If No, include comment number or date. 11. Are floor tiles in good condition and properly braced? 12. Is floor tile underside shiny or painted? If painted, judge the need for particulate test. Power and Lighting Number Area or Condition Yes No 13. Are lighting levels adequate for maintenance? 14. Are ac outlets available for servicing needs (for example, laptop)? 15. Does the input voltage correspond to equipment specifications? 15a. Is dual source power used? If so, identify types and evaluate grounding. 16. Does the input frequency correspond to equipment specifications? 17. Are lightning arrestors installed inside the building? 18. Is power conditioning equipment installed? 19. Is a dedicated branch circuit available for equipment? 20. Is the dedicated branch circuit less than 75 feet (22.86 m)? 21. Are the input circuit breakers adequate for equipment loads? Safety Number Area or Condition Yes No 22. Is an emergency power shutoff switch available? 23. Is a telephone available for emergency purposes? 24. Does the computer room have a fire protection system? 25. Does the computer room have antistatic flooring installed? 26. Do any equipment servicing hazards exist (loose ground wires, poor lighting, and so on)? Cooling Number Area or Condition Yes No 27. Can cooling be maintained between 5°C (41 °F) and 35°C (95 °F) (up to 1,525 m/5,000 ft)? Derate 1°C/305 m (34 °F/1,000 ft) above 1,525 m/5,000 ft and up to 3,048 m/10,000 ft. 28. Can temperature changes be held to 5°C (41 °F) per hour with tape media? Can temperature changes be held to 20°C (68 °F) per hour without tape media? 29. Can humidity level be maintained at 40% to 55% at 35°C (95 °F) noncondensing? 30. Are air-conditioning filters installed and clean? Storage Number Area or Condition Yes No 31. Are cabinets available for tape and disc media? 32. Is shelving available for documentation? Comment or Date Sample Site Inspection Checklist for Site Preparation 31

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104

Table 17 Site Inspection Checklist
(continued)
Comment or Date
Check either Yes or No. If No, include comment number or date.
Are floor tiles in good condition and properly braced?
11.
Is floor tile underside shiny or painted? If painted, judge the need
for particulate test.
12.
Power and Lighting
No
Yes
Area or Condition
Number
Are lighting levels adequate for maintenance?
13.
Are ac outlets available for servicing needs (for example, laptop)?
14.
Does the input voltage correspond to equipment specifications?
15.
Is dual source power used? If so, identify types and evaluate
grounding.
15a.
Does the input frequency correspond to equipment specifications?
16.
Are lightning arrestors installed inside the building?
17.
Is power conditioning equipment installed?
18.
Is a dedicated branch circuit available for equipment?
19.
Is the dedicated branch circuit less than 75 feet (22.86 m)?
20.
Are the input circuit breakers adequate for equipment loads?
21.
Safety
No
Yes
Area or Condition
Number
Is an emergency power shutoff switch available?
22.
Is a telephone available for emergency purposes?
23.
Does the computer room have a fire protection system?
24.
Does the computer room have antistatic flooring installed?
25.
Do any equipment servicing hazards exist (loose ground wires,
poor lighting, and so on)?
26.
Cooling
No
Yes
Area or Condition
Number
Can cooling be maintained between 5°C (41 °F) and 35°C (95
°F) (up to 1,525 m/5,000 ft)? Derate 1°C/305 m (34 °F/1,000
ft) above 1,525 m/5,000 ft and up to 3,048 m/10,000 ft.
27.
Can temperature changes be held to 5°C (41 °F) per hour with
tape media? Can temperature changes be held to 20°C (68 °F)
per hour without tape media?
28.
Can humidity level be maintained at 40% to 55% at 35°C (95 °F)
noncondensing?
29.
Are air-conditioning filters installed and clean?
30.
Storage
No
Yes
Area or Condition
Number
Are cabinets available for tape and disc media?
31.
Is shelving available for documentation?
32.
Sample Site Inspection Checklist for Site Preparation
31