Safety and Regulatory Information Disconnect Devices NOTE Specific countries require a derating factor for the wire size when running multiple conductors in the same power cord. It is recommended to use only power cord conductors sized for this derating factor. Table 1-1 Recommended Wire Sizes Current 0-25 Amps 25-32 Amps 32-40 Amps 40-63 Amps 63-80 Amps Wire Size 2.5 mm (14 AWG) 4 mm (12 AWG) 6 mm (10 AWG) 10 mm (8 AWG) 16 mm (6 AWG) Derating Factor 4 mm (12 AWG) 6 mm (10 AWG) 10 mm (8 AWG) 16 mm (6 AWG) 25mm (4 AWG) Disconnect Devices Disconnect devices or circuit breakers must be used to protect the system against abnormal hazards. Table 1-2 details the circuit breaker specifications. Table 1-2 Wall Disconnect Device Circuit Breaker Specification Agency approvals: Interrupt capacity Breaker type Voltage rating Input Source Circuit Interruption Ground UL, CSA, VDE 5,000 amperes Magnetic trip 250V minimum 3-pole+PE, 420V minimum 4-pole+PE 3 pole + PE or 4-pole + PE Simultaneous trip of all poles The protective earth (PE) ground wire is not switched WARNING Provide a disconnect device to protect against abnormal hazards. Systems configured with a full complement of cells, memory, and I/O and connected to a 5-wire source must have a maximum 24A 3-phase with neutral (4-pole) circuit breaker installed as part of the building installation. Systems configured with a full complement of cells, memory, and I/O and connected to a 4-wire source must have a maximum 44A 3-phase (3-pole) circuit breaker installed as part of the building installation. Chapter 1 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

Chapter 1
Safety and Regulatory Information
Disconnect Devices
9
NOTE
Specific countries require a derating factor for the wire size when running multiple conductors
in the same power cord. It is recommended to use only power cord conductors sized for this
derating factor.
Disconnect Devices
Disconnect devices or circuit breakers must be used to protect the system against abnormal hazards.
Table 1-2 details the circuit breaker specifications.
WARNING
Provide a disconnect device to protect against abnormal hazards.
Systems configured with a full complement of cells, memory, and I/O and connected
to a 5-wire source must have a maximum 24A 3-phase with neutral (4-pole) circuit
breaker installed as part of the building installation.
Systems configured with a full complement of cells, memory, and I/O and connected
to a 4-wire source must have a maximum 44A 3-phase (3-pole) circuit breaker
installed as part of the building installation.
Table 1-1
Recommended Wire Sizes
Current
Wire Size
Derating Factor
0-25 Amps
2.5 mm (14 AWG)
4 mm (12 AWG)
25-32 Amps
4 mm (12 AWG)
6 mm (10 AWG)
32-40 Amps
6 mm (10 AWG)
10 mm (8 AWG)
40-63 Amps
10 mm (8 AWG)
16 mm (6 AWG)
63-80 Amps
16 mm (6 AWG)
25mm (4 AWG)
Table 1-2
Wall Disconnect Device Circuit Breaker Specification
Agency approvals:
UL, CSA, VDE
Interrupt capacity
5,000 amperes
Breaker type
Magnetic trip
Voltage rating
250V minimum 3-pole+PE, 420V minimum 4-pole+PE
Input Source
3 pole + PE or 4-pole + PE
Circuit Interruption
Simultaneous trip of all poles
Ground
The protective earth (PE) ground wire is not switched