Honeywell C7089U1006 Owner's Manual

Honeywell C7089U1006 Manual

Honeywell C7089U1006 manual content summary:

  • Honeywell C7089U1006 | Owner's Manual - Page 1
    (10) with 60 (1524) leadwires. INSTALLATION INSTRUCTIONS Location and Mounting (Fig. 1) Mount the sensor where: • cannot tamper with settings. • there is good air circulation. • it can measure true outdoor ambient temperature. • surface is flat. • wire distance between C7089 and thermostat is less
  • Honeywell C7089U1006 | Owner's Manual - Page 2
    light dimming circuits, electric motors or welding equipment. - Avoid poor wiring connections. - Avoid intermittent or missing building earth ground. Wiring must comply with applicable codes, ordinances and regulations: 1. Wire the C7089 Outdoor Sensor to S1 and S2 terminals on the thermostat. If
  • Honeywell C7089U1006 | Owner's Manual - Page 3
    C7089B Outdoor Sensor to absorb outdoor air for a minimum of twenty minutes before taking a reading. With an accurate thermometer (±1°F [0.5°C]) measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading. To verify sensor resistance, remove one wire
  • Honeywell C7089U1006 | Owner's Manual - Page 4
    66 18.9 Ohms of Resistance 47092 44732 42506 40394 38400 36519 34743 33063 31475 29975 28558 27219 25949 24749 23613 22537 21516 20546 19626 18754 17926 17136 16387 15675 14999 14356 13743 13161 12607 Table 1. Sensor Resistance at Outdoor Temperature (Continued). Outdoor Temperature °F °C 68
  • Honeywell C7089U1006 | Owner's Manual - Page 5
    CARACTÉRISTIQUES TECHNIQUES Gamme de température ambiante de service : -40 à 49 °C (-40 à 120 installer le capteur : • dans un endroit où il est directement exposé aux rayons du soleil; • où de l'air Installer la pince de retenue. Avant d'installer ce produit... 1. Lire attentivement les instructions
  • Honeywell C7089U1006 | Owner's Manual - Page 6
    des chocs électriques ou endommager le matériel. Couper l'alimentation électrique avant d'effectuer le raccordement. Tout le câblage doit être conforme au code du bâtiment et aux règlements locaux. 1. Raccorder le capteur extérieur C7089 aux bornes S1 et S2 du thermostat. Si le conducteur fourni
  • Honeywell C7089U1006 | Owner's Manual - Page 7
    Une fois le capteur installé et le numé permettre au capteur de température extérieure C7089 d'absorber l'air extérieur pendant au moins 20 minutes avant de mesurer la raccordement du C7189. Mesurer la résistance du capteur à l'aide d'un ohm-mètre. Vérifier ensuite la précision du capteur à l'aide du
  • Honeywell C7089U1006 | Owner's Manual - Page 8
    capteur à la température extérieure. (suite) Température extérieure °F °C Ohms de résistance 78 25,6 9795 80 26,7 9398 82 27,8 9020 84 28,9 Solutions de régulation et d'automatisation Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35
  • Honeywell C7089U1006 | Owner's Manual - Page 9
    200 pies (60 m). No instale el sensor: • bajo luz del sol directa. • donde sople aire frío o caliente sobre el sensor. La línea de descarga desde M7514 Figura 1. Ubicaciones típicas del sensor exterior. ® Marca registrada de EE.UU. Copyright © 2004 Honeywell International Inc. • • Todos los
  • Honeywell C7089U1006 | Owner's Manual - Page 10
    tierra física al edificio esté intermitente o que no haya tierra física. El cableado debe cumplir con los códigos, ordenanzas y reglamentos aplicables: 1. Cablee el sensor exterior C7089 a las terminales S1 y S2 en el termostato. Si el cable guía incluido con el C7089 no es lo suficiente largo (60
  • Honeywell C7089U1006 | Owner's Manual - Page 11
    . Vea la tabla 1. VERIFICACIÓN Permita que el sensor exterior C7089 absorba el aire exterior por un mínimo de veinte minutos antes de puede recalibrar en el campo. Tabla 1. Resistencia del sensor a temperatura exterior. Temperatura exterior °F °C Ohm de resistencia -20 -28.9 106926 -18 -27
  • Honeywell C7089U1006 | Owner's Manual - Page 12
    13743 64 17.8 13161 Tabla 1. Resistencia del sensor a temperatura exterior. Temperatura exterior °F °C Ohm de resistencia 66 18.9 12607 68 20.0 48.9 4317 Automatización y control desenlace Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive 35,
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12

fi U.S. Registered Trademark
Copyright ' 2004 Honeywell International Inc.
°
°
All Rights Reserved
69-1709EFS
INSTALLATION INSTRUCTIONS
C7089
Outdoor Sensor
(USE WITH TH8000 AND TH7000 THERMOSTATS)
APPLICATION
This C7089 Outdoor Sensor is used with theTH8000 and
TH7000 Thermostat families.
SPECIFICATIONS
Operating Ambient Temperature Range:
-40 to 120±F (-40 to 49±C).
Display Range:
-40 to 127±F (-40 to 53±C).
Sensor Accuracy:
+/-1.5±F at 70±F (+/-.84 at 21±C)
Operating Relative Humidity:
5% to 95% non-condensing.
Dimensions in in. (mm):
2-1/4 (57) x 3/8 (10) with 60 (1524) leadwires.
INSTALLATION
When Installing this Product°
1.
Read
these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2.
C
heck the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3.
In
staller must be a trained, experienced service
technician.
4.
A
fter installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power supply before connecting
wiring.
Location and Mounting (Fig. 1)
Mount the sensor where:
°
cannot tamper with settings.
°
there is good air circulation.
°
it can measure true outdoor ambient temperature.
°
surface is flat.
°
wire distance between C7089 and thermostat is less
than 200 feet.
Do
not
mount the sensor:
°
in direct sunlight.
°
where hot or cold air blows on the sensor. Discharge
line from an outdoor compressor unit, vent or fan
causes inaccurate temperature readings.
°
where snow, ice or debris can cover it.
Use the following steps to mount the sensor:
1.
R
emove the sensor from the mounting clip.
2.
Mark the area on the location selected for
mounting the sensor mounting clip.
3.
Mount the clip.
Fig. 1. Typical locations for outdoor sensor.
M7514