Honeywell T8090T Owner's Manual - Page 20
Voltage at Clock Terminals
View all Honeywell T8090T manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
Voltage at Clock Terminals AC VOLTAGE AT C-R TERMINALS 0 Vac Up to 15 Vac. 15 to 30 Vac. POSSIBLE CAUSE CHECK ACTION 1. System power is Off. 1. Restore power. 2. Short in clock power supply wiring. 2. Replace wiring. 3. Limit switch contacts stuck open. 3. Free or replace limit switch. 4. Transformer supplying power is burned out. 4. Replace transformer. 1. System transformer used to power 1. Use additional (separate) the clock is inadequate. transformer. 2. Additional (separate) transformer used to power the clock has inadequate voltage. 2. Install transformer with proper secondary voltage. 1. Spring fingers on thermostat are 1. Rebend spring fingers to a 45 not making proper contact with the degree angle to assure proper subbase terminals. contact. 2. Clock has failed. 2. Replace the thermostat. 20 69-0432-1