Honeywell YRTH7500D1009 Quick Start Guide - Page 2

System Setup, Preferences optional, Wiring Notes - security

Page 2 highlights

12a System Setup Step 1 Press and release the left button. 72 Fri System Cool 6:30 PM Fan Auto Set To 72 System & Fan Schedule Clock & More MCR33839 Step 2 Press and hold the center button until the screen changes (approximately 5 seconds). System Fan Auto Heat Off Cool System Fan Done MCR33840 NOTE: Some functions may not appear due to thermostat model or previous selections made. Step 3 1 Press s t to change setting. 2 Press NEXT to advance to next function. 3 Press DONE to save & exit. 0120 20 Go Back Next Done MCR33841 Function 0120* Year Setting (first two digits) 0130* Year Setting (second two digits) 0140* Month Setting 0150* Date Setting 0170 Select System Type 0180 Heating Fan Control Settings & Options 20 = Year 20xx 21 = Year 21xx 01 - 99 (i.e., 2001 - 2099) 01 - 12 (i.e., January - December) 01 - 31 1 Heat/cool: Gas, oil or electric heating with central air conditioning. 2 Heat pump: Heat pump without backup or auxiliary heat. 3 Heat only: Gas, oil or electric heat without central air conditioning. 4 Heat only with fan: Gas, oil or electric heat without central air conditioning. 5 Hot water heat only (no fan): Gas, oil or hot water heat without central air conditioning. 6 Cool only: Central air conditioning only. 7 Heat pump: Heat pump with backup or auxiliary heating. 8 Heat/Cool Multiple stages: 2 heat stages (wires on W and W2), 2 cooling stages (wires on Y and Y2). 9 Heat/Cool Multiple stages: 2 heat stages (wires on W and W2), 1 cooling stage (wire on Y). 10 Heat/Cool Multiple stages: 1 heat stage (wire on W), 2 cooling stages (wires on Y and Y2). 0 Gas or oil heat: Use this setting if you have a gas or oil heating system (system controls fan operation). 1 Electric heat: Use this setting if you have an electric heating system (thermostat controls fan operation). 12b Preferences (optional) Use the Setup and Navigation steps in 12a to set Display Preferences. Function Settings & Options 0300 Manual/Auto Changeover 0 Manual changeover (Heat/Cool/Off). 1 Automatic changeover (Heat/Cool/Auto/Off). Automatically turns on Heat or Cool based on room temperature. Note: System maintains minimum 3°F difference between heat and cool settings. 0320 Temperature Format 0 Fahrenheit (°F/°C) 1 Celsius 0330 Daylight Saving Time 0 Off: No adjustment for daylight saving time. On/Off 1 On: Auto-change to daylight saving time (for areas that do not use the new 2007 DST calendar). 2 On: Auto-change to daylight saving time (2007 and beyond, for areas that use the new 2007 DST calendar). 0500 Furnace Filter Change 0 Off (no reminder) Reminder 1 Reminder in about 1 month 2 Reminder in about 3 months 3 Reminder in about 6 months 4 Reminder in about 9 months 5 Reminder in about 1 year 6 Reminder in about 3 years 0530 Smart Response® 1 On 0 Off Technology 0600 Maximum Heat Temperature Limit 90°F (other options: 40-89°F [4-32°C]) 0610 Minimum Cool Temperature Limit 50°F (other options: 51-99°F [11-37°C]) 0640 Clock Format 12 12-hour clock (i.e., "3:30 pm") 24 24-hour clock (i.e., "15:30") 0190 Heat Pump 0 Changeover Valve (for heat pumps 1 only) 0240 Heating Cycle Rate 5 9 3 1 0270 Emergency Heat Cycle Rate (heat pumps only) * Functions set in Step 10. Cooling changeover valve: Use this setting if you connected a wire labeled "O" to the O/B terminal (see page 22). Heating changeover valve: Use this setting if you connected a wire labeled "B" to the O/B terminal (see page 23). Gas or oil furnace: Standard gas/oil furnace (less than 90% efficiency). Electric furnace: Electric heating systems. Hot water or high-efficiency furnace: Hot water system or gas furnace (more than 90% efficiency). Gas/oil steam or gravity system: Steam or gravity heat systems. Settings 5, 9, 3, or 1 recommended. Other settings: 2, 4, 6, 7, 8, 10, 11, 12. The number indicates how frequently the system cycles on and off to maintain the set temperature. A higher number means the system is on and off for shorter amounts of time, a lower number means longer on and off times. When these settings are set to match the system type, the thermostat controls temperature more accurately. Wiring Notes Conventional system Alternate wiring (conventional systems) Remove metal jumper connecting R and Rc only if you must connect both R and Rc wires. If your old thermostat had both R and RH wires, remove metal jumper. Connect the R wire to the Rc terminal, and the RH wire to the R terminal. If your old thermostat had only 1 C or C1 wire, connect it to the C terminal. If your old thermostat had 2 C or C1 wires, wrap each separately with electrical tape and do not connect them. C C 3 G G Y Y W W RC Rc 2 R R 2 W2 W2 Y2 Y2 MCR32160 OYG Heat pump Connect wires: Heat Pump 1. Match each labeled wire with same letter on new thermostat. 2. Use a screwdriver to loosen screws, insert wires into hole under screw, then tighten screws until wire is secure. 3. If E and Aux do not each have a wire connected, use a small piece of wire to connect them to each other. 4. Push any excess wire back into the wall opening. Labels don't match? If labels do not match letters on thermostat, see Alternate wiring (heat pump system only) HEAT PUMP C G Y O/B RC R R Alternate wiring (heat pump system only) Leave metal jumper in place, connecting R & Rc terminals. If your old thermostat had both V and VR wires, stop now and contact a qualified contractor for help. If your old thermostat had separate O and B wires, attach the B wire to the C terminal. If another wire is attached to the C terminal, stop now and contact a qualified contractor for help. If your old thermostat had Y1, W1 and W2 wires, stop now and contact a qualified contractor for help. If L terminal is used, C terminal wire must be connected (contact a 5 contractor if there is no C wire). If E and Aux terminals do not each have a wire connected, use a small 6 piece of wire to connect them to each other. 35 C G Y 3 O/B RC 2R 4 6 AUX 6E 5L Aux HEAT PUMP Aux E L MCR33552 MCR32161 Customer assistance For assistance with this product, please visit http://yourhome.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502. 69-2722-01

  • 1
  • 2

MCR33841
Next
Go Back
Done
20
0120
Alternate wiring (heat pump system only)
Leave metal jumper in place, connecting
R
&
Rc
terminals.
If your old thermostat had both
V
and
VR
wires, stop now and contact a
qualified contractor for help.
If your old thermostat had separate
O
and
B
wires, attach the
B
wire to
the
C
terminal. If another wire is attached to the
C
terminal, stop now
and contact a qualified contractor for help.
If your old thermostat had
Y1
,
W1
and
W2
wires, stop now and contact
a qualified contractor for help.
If
L
terminal is used,
C
terminal wire must be connected (contact a
contractor if there is no
C
wire).
If
E
and
Aux
terminals do not each have a wire connected, use a small
piece of wire to connect them to each other.
Use the Setup and Navigation steps in 12a to set Display Preferences.
Step 3
1 Press
s t
to change setting.
2 Press
NEXT
to advance to next function.
3 Press
DONE
to save & exit.
Alternate wiring (conventional systems)
Remove metal jumper connecting
R
and
Rc
only if
you must connect both
R
and
Rc
wires.
If your old thermostat had both
R
and
RH
wires,
remove metal jumper. Connect the
R
wire to the
Rc
terminal, and the
RH
wire to the
R
terminal.
If your old thermostat had only 1
C
or
C1
wire,
connect it to the
C
terminal. If your old thermostat
had 2
C
or
C1
wires, wrap each separately with
electrical tape and do not connect them.
C
G
Y
W
RC
R
W2
Y2
Y2
W2
W
Y
G
MCR32160
R
2
Rc
2
C
3
Conventional system
Connect wires: Heat Pump
1. Match each labeled wire with same letter on new thermostat.
2. Use a screwdriver to loosen screws, insert wires into hole under
screw, then tighten screws until wire is secure.
3. If
E
and
Aux
do not each have a wire connected, use a small
piece of wire to connect them to each other.
4. Push any excess wire back into the wall opening.
Labels don’t match?
If labels do not match letters on thermostat, see Alternate wiring
(heat pump system only)
Heat pump
2
3
5
3
5
4
6
6
MCR32161
C
G
Y
O/B
RC
R
AUX
E
L
5
6
69-2722—01
Function
Settings & Options
0300
Manual/Auto
Changeover
0
Manual changeover (Heat/Cool/Off).
1
Automatic changeover (Heat/Cool/Auto/Off). Automatically turns on Heat or Cool based on room
temperature. Note: System maintains minimum 3°F difference between heat and cool settings.
0320
Temperature Format
(°F/°C)
0
Fahrenheit
1
Celsius
0330
Daylight Saving Time
On/Off
0
Off: No adjustment for daylight saving time.
1
On: Auto-change to daylight saving time (for areas that do not use the new 2007 DST calendar).
2
On: Auto-change to daylight saving time (2007 and beyond, for areas that use the new 2007 DST calendar).
0500
Furnace Filter Change
Reminder
0
Off (no reminder)
1
Reminder in about 1 month
2
Reminder in about 3 months
3
Reminder in about 6 months
4
Reminder in about 9 months
5
Reminder in about 1 year
6
Reminder in about 3 years
0530
Smart
Response
®
Technology
1
On
0
Off
0600
Maximum Heat
Temperature Limit
90°F
(other options: 40-89°F [4-32°C])
0610
Minimum Cool
Temperature Limit
50°F
(other options: 51-99°F [11-37°C])
0640
Clock Format
12
12-hour clock (i.e., “3:30 pm”)
24
24-hour clock (i.e., “15:30”)
12a
System Setup
12b
Preferences (optional)
Wiring Notes
Step 1
Press and release the left button.
Step 2
Press and hold the center button until the screen
changes (approximately 5 seconds).
Customer assistance
For assistance with this product, please visit
or call Honeywell Customer Care toll-free at
1-800-468-1502
.
MCR33839
System & Fan
Schedule
Clock & More
72
6:30
Fri
System
Cool
Fan
Auto
Set To
PM
72
MCR33840
System
Fan
Done
System
Heat Off Cool
Fan
Auto
MCR33552
Aux
E
L
C
G
Y
O/B
RC
R
HEAT PUMP
Y
G
R
Aux
O
HEAT PUMP
NOTE:
Some functions may not appear due to
thermostat model or previous selections made.
Function
Settings & Options
0120*
Year Setting
(first two digits)
20
= Year 20xx
21
= Year 21xx
0130*
Year Setting
(second two
digits)
01
-
99
(i.e., 2001 - 2099)
0140*
Month Setting
01
-
12
(i.e., January - December)
0150*
Date Setting
01
-
31
0170
Select System
Type
1
Heat/cool:
Gas, oil or electric heating with central air conditioning.
2
Heat pump:
Heat pump without backup or auxiliary heat.
3
Heat only:
Gas, oil or electric heat without central air conditioning.
4
Heat only with fan:
Gas, oil or electric heat without central air conditioning.
5
Hot water heat only (no fan):
Gas, oil or hot water heat without central air conditioning.
6
Cool only:
Central air conditioning only.
7
Heat pump:
Heat pump with backup or auxiliary heating.
8
Heat/Cool Multiple stages:
2 heat stages (wires on
W
and
W2
), 2 cooling stages (wires on
Y
and
Y2
).
9
Heat/Cool Multiple stages:
2 heat stages (wires on
W
and
W2
), 1 cooling stage (wire on
Y
).
10
Heat/Cool Multiple stages:
1 heat stage (wire on
W
), 2 cooling stages (wires on
Y
and
Y2
).
0180
Heating Fan
Control
0
Gas or oil heat:
Use this setting if you have a gas or oil heating system (system controls fan operation).
1
Electric heat:
Use this setting if you have an electric heating system (thermostat controls fan operation).
0190
Heat Pump
Changeover Valve
(for heat pumps
only)
0
Cooling changeover valve:
Use this setting if you connected a wire labeled “O” to the O/B terminal (see
page 22).
1
Heating changeover valve:
Use this setting if you connected a wire labeled “B” to the O/B terminal (see
page 23).
0240
Heating Cycle Rate
5
Gas or oil furnace:
Standard gas/oil furnace (less than 90% efficiency).
9
Electric furnace:
Electric heating systems.
3
Hot water or high-efficiency furnace:
Hot water system or gas furnace (more than 90% efficiency).
1
Gas/oil steam or gravity system:
Steam or gravity heat systems.
Settings 5, 9, 3, or 1 recommended. Other settings: 2, 4, 6, 7, 8, 10, 11, 12.
The number indicates how frequently the system cycles on and off to maintain the set temperature.
A higher number means the system is on and off for shorter amounts of time, a lower number means
longer on and off times. When these settings are set to match the system type, the thermostat controls
temperature more accurately.
0270
Emergency Heat
Cycle Rate (heat
pumps only)
*
Functions set in Step 10.