LG LCN340CP Service Manual - Page 47

Troubleshooting CH61, CH62

Page 47 highlights

Troubleshooting CH61, CH62 Troubleshooting Guide Display code 61 Title Condenser pipe sensor temp. high Cause of error Check point & Normal condition • Condenser pipe sensor detected high temp.(65°C)(149°F) • Check the load condition. • Check the sensor of Condenser pipe sensor. 62 Heat sink sensor temp. high • Heat sink sensor detected high temp.(85°C)(185°F) • Check the fan is locked. • Check the sensor of heat sink. Toff °C T2 °C T1 °C Heat Sink temp. COMP Frequency (Hz) Normal Normal Check Point • CH 61 1. Check the install condition for over load. (Refrigerant, Pipe length, Blocked, ...) OFF Normal • CH 62 1. Check the fan is locked. 2. Check the Outdoor temp. is very high. Service Manual 47

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61

Service Manual
47
Troubleshooting Guide
Troubleshooting CH61, CH62
61
62
Condenser
pipe sensor
temp. high
Heat sink sensor
temp. high
Condenser pipe sensor
detected high
temp.(65
°
C)(149
°
F)
Heat sink sensor
detected high
temp.(85
°
C)(185
°
F)
Check the load condition.
Check the sensor of Condenser pipe sensor.
Check the fan is locked.
Check the sensor of heat sink.
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
CH 61
1. Check the install condition for over load.
(Refrigerant, Pipe length, Blocked,
)
CH 62
1. Check the fan is locked.
2. Check the Outdoor temp. is very high.
COMP Frequency
(Hz)
Toff
°
C
T1
°
C
T2
°
C
OFF
Normal
Normal
Normal
Heat Sink temp.