LG LMN120HE Service Manual - Page 72
Error Code
View all LG LMN120HE manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 72 highlights
Troubleshooting Guide Error Code I Trouble Shooting Error code Title 01 Indoor air sensor 02 Indoor inlet pipe sensor 06 Indoor outlet pipe sensor Cause of error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error Check point & Normal condition Normal resistor : 10KΩ / at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged) Normal resistor : 5KΩ/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged) Normal resistor : 5KΩ/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged) 10KΩ Ω 2.5Vdc V Check the resistance / voltage ❑ Check Point 1. Unplug the sensor on Indoor unit PCB. 2. Estimate the resistance of each sensor 3. If the resistance of the sensor is 10KΩ/5KΩ at 25°C, then sensor is normal 4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. ➔ Change the sensor. 5. Plug the sensor on Indoor unit PCB and Power ON. 6. Estimate the voltage of each sensor. 7. If the voltage of the sensor is 2.5Vdc / at 25°C, then sensor is normal. 8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ➔ Repair or Change the PCB 72 Multi type Air Conditioner