LG LMU360CE Service Manual - Page 38
Charging
View all LG LMU360CE manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 38 highlights
Charging Charging s Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line. Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant charge has to be adjusted. s Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot). Max total length Max length of Capacity (Btu/h) of all pipes each pipe (A+B+C) (A/B/C) Min length of each pipe (A/B/C) Max Elevation between each indoor unit and outdoor unit (h1) Max elevation between indoor units (h2) Additional Refrigerant 36k 45m(150ft) 15m(50ft) 3m(10ft) 7.5m(25ft) 7.5m(25ft) 20g/m(0.22oz/ft) Example: A 80ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A Important: If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit. 38 Multi type Air Conditioner