Panamax M4320-PRO Manual - Page 5

Profile 1 P1, Profile 2 P2, Profile 3 P3, Profile 4 P4

Page 5 highlights

Preset Profile Information PROFILE 1 (P1) DEFAULT OUTLET SEQUENCING (preset profile P1, by outlet #s): With switching on and off BREAKER or holding both REBOOT buttons. Start up: 1→(1 sec)→2→(1 sec)→3→(1 sec)→4→(1 sec)→5→(1 sec)→6→(1 sec)→7→(5 sec)→8 Shut down: 8→(5 sec)→7→(5 sec)→6→(1 sec)→5→(1 sec)→4→(1 sec)→3→(1 sec)→2→(1 sec)→1 Reboot 1: 1(off)→(30 sec)→1(on) Reboot 2: 2(off)→(30 sec)→2(on) DC TRIGGER ON: 7(on)→(5 sec)→8(on) DC TRIGGER OFF: 8(off)→(5 sec)→7(off) PROFILE 2 (P2) A/V + MODEM OUTLET SEQUENCING (profile P2, by outlet #s): With switching on and off BREAKER or holding both REBOOT buttons. Start up: 1→(15 sec)→2→(1 sec)→3→(1 sec)→4→(1 sec)→5→(1 sec)→6→(1 sec)→7→(5 sec)→8 Shut down: 8→(5 sec)→7→(5 sec)→6→(1 sec)→5→(1 sec)→4→(1 sec)→3→(1 sec)→2→(1 sec)→1 Reboot 1: 1 and 2 (off)→(30 sec)→1 and 2 (on) Reboot 2: 3(off)→(30 sec)→3(on) DC TRIGGER ON: 7(on)→(5 sec)→8(on) DC TRIGGER OFF: 8(off)→(5 sec)→7(off) PROFILE 3 (P3) A/V + EXTENDED DELAYS OUTLET SEQUENCING (profile P3, by outlet #s): With switching on and off BREAKER or holding both REBOOT buttons. Start up: 1→(10 sec)→2→(10 sec)→3→(10 sec)→4→(10 sec)→5→(10 sec)→6→(10 sec)→7→(20 sec)→8 Shut down: 8→(20 sec)→7→(20 sec)→6→(10 sec)→5→(10 sec)→4→(10 sec)→3→(10 sec)→2→(10 sec)→1 Reboot 1: 1 and 6 (off)→(45 sec)→1 and 6 (on) Reboot 2: 3(off)→(45 sec)→3(on) DC TRIGGER ON: 5(on)→(20 sec)→7(on)→(20 sec)→8 (on) DC TRIGGER OFF: 8(off)→(20 sec)→7(off)→(30 sec)→5(off) PROFILE 4 (P4) NETWORK + CONTROL DELAYS OUTLET SEQUENCING (profile P4, by outlet #s): With switching on and off BREAKER or holding both REBOOT buttons. Start up: 1→(15 sec)→2→(15 sec)→3→(5 sec)→4→(5 sec)→5→(5 sec)→6→(5 sec)→7→(10 sec)→8 Shut down: 8→(10 sec)→7→(10 sec)→6→(5 sec)→5→(5 sec)→4→(5 sec)→3 outlets 1 and 2 are always on Reboot 1: 1(off)→(30 sec)→1(on) Reboot 2: 2 and 3(off)→(30 sec)→2 and 3(on) DC TRIGGER ON: 7(on)→(10 sec)→8(on) DC TRIGGER OFF: 8(off)→(10 sec)→7(off) 3

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14

Preset Profile Information
3
DEFAULT OUTLET SEQUENCING (preset profile P1, by outlet #s):
Start up: 1→(1 sec)→2→(1 sec)→3→(1 sec)→4→(1 sec)→5→(1 sec)→6→(1 sec)→7→(5 sec)→8
Shut down: 8→(5 sec)→7→(5 sec)→6→(1 sec)→5→(1 sec)→4→(1 sec)→3→(1 sec)→2→(1 sec)→1
Reboot 1: 1(off)→(30 sec)→1(on)
Reboot 2: 2(off)→(30 sec)→2(on)
DC TRIGGER ON: 7(on)→(5 sec)→8(on)
DC TRIGGER OFF: 8(off)→(5 sec)→7(off)
With switching on and off
BREAKER or holding both
REBOOT buttons.
A/V + MODEM OUTLET SEQUENCING (profile P2, by outlet #s):
Start up: 1→(15 sec)→2→(1 sec)→3→(1 sec)→4→(1 sec)→5→(1 sec)→6→(1 sec)→7→(5 sec)→8
Shut down: 8→(5 sec)→7→(5 sec)→6→(1 sec)→5→(1 sec)→4→(1 sec)→3→(1 sec)→2→(1 sec)→1
Reboot 1: 1 and 2 (off)→(30 sec)→1 and 2 (on)
Reboot 2: 3(off)→(30 sec)→3(on)
DC TRIGGER ON: 7(on)→(5 sec)→8(on)
DC TRIGGER OFF: 8(off)→(5 sec)→7(off)
With switching on and off
BREAKER or holding both
REBOOT buttons.
A/V + EXTENDED DELAYS OUTLET SEQUENCING (profile P3, by outlet #s):
Start up: 1→(10 sec)→2→(10 sec)→3→(10 sec)→4→(10 sec)→5→(10 sec)→6→(10 sec)→7→(20 sec)→8
Shut down: 8→(20 sec)→7→(20 sec)→6→(10 sec)→5→(10 sec)→4→(10 sec)→3→(10 sec)→2→(10 sec)→1
Reboot 1: 1 and 6 (off)→(45 sec)→1 and 6 (on)
Reboot 2: 3(off)→(45 sec)→3(on)
DC TRIGGER ON: 5(on)→(20 sec)→7(on)→(20 sec)→8 (on)
DC TRIGGER OFF: 8(off)→(20 sec)→7(off)→(30 sec)→5(off)
With switching on and off
BREAKER or holding both
REBOOT buttons.
NETWORK + CONTROL DELAYS OUTLET SEQUENCING (profile P4, by outlet #s):
Start up: 1→(15 sec)→2→(15 sec)→3→(5 sec)→4→(5 sec)→5→(5 sec)→6→(5 sec)→7→(10 sec)→8
Shut down: 8→(10 sec)→7→(10 sec)→6→(5 sec)→5→(5 sec)→4→(5 sec)→3 outlets 1 and 2 are always on
Reboot 1: 1(off)→(30 sec)→1(on)
Reboot 2: 2 and 3(off)→(30 sec)→2 and 3(on)
DC TRIGGER ON: 7(on)→(10 sec)→8(on)
DC TRIGGER OFF: 8(off)→(10 sec)→7(off)
With switching on and off
BREAKER or holding both
REBOOT buttons.
PROFILE 1 (P1)
PROFILE 2 (P2)
PROFILE 3 (P3)
PROFILE 4 (P4)