    Split System Submittal Data System: 36PET2U6 Indoor: S-36PT2U6 Outdoor: U-36PE1U6 Single Zone Heat Pump - Ceiling Mounted Job Name: Location: Engineer: Submitted to: Submitted by: Reference: Approval: Date: Construction: Unit#: Drawing#: Rated Conditions Indoor 80°F DB / 67°F WB 70°F DB / 60°F WB
  • Panasonic 36PET2U6 | 36PET2U6 Submittal Sheet - Page 2
    Failure Automatic Restart Heating/Cooling Automatic Changeover Self-Diagnosis Air Filter Microprocessor Remote Purchased Separately Thermostat 24 Hr. Program N/A Manual Automatic Built-In Built-In Built-In Washable, Anti-Mold Options Refrigerant Line Set Fresh Air Intake Econavi Avaliable With
  • Panasonic 36PET2U6 | 36PET2U6 Submittal Sheet - Page 3
    (Suspension bolt pitch) Indoor Dimensions 1-4 $IMENSIONAL Data )NDOOR Unit 
  • Panasonic 36PET2U6 | 36PET2U6 Submittal Sheet - Page 4
    1-4. Dimensional Data OutdOoutodrooDr Uimnit:eUn-2s6PioE1nUs6, U-26PS1U6 U-36PE1U6, U-36PS1U6 1. Specifications 1 Panasonic North America Air Conditioning Division 1690 Roberts Blvd., NW, Suite 110 Kennesaw, GA 30144 us.panasonic.com/aircon 1-68
  • 1
  • 2
  • 3
  • 4

Split System Submittal Data
System:
36PET2U6
Indoor:
S-36PT2U6
Outdoor:
U-36PE1U6
Single Zone Heat Pump - Ceiling Mounted
General Data
Power (V/P/Hz)
230/208/1/60
Circuit Ampacity (A)
15-30 Indoor-Outdoor
Fuse Size, Max. (A)
15-30 Indoor-Outdoor
Compressor
DC Rotary Inverter
No. Used
1
R.L. Amps - L.R. (A)
15.7 - 17.5
Rated Conditions
Indoor
Outdoor
80°F DB / 67°F WB
95°F DB / 75°F
WB
70°F DB / 60°F WB
47°F DB / 43°F WB
70°F DB / 60°F WB
17°F DB / 15°F WB
Outdoor Unit
Fan type
Propeller
No. used
1
Dia & Length (in.)
18-7/64
Type Drive - No. Speeds
DC Motor-Variable
No. Poles (RPM)
8 - 800
No. Motors (W)
1 - 90
CFM (High)
1,942
F.L. Amps (A)
13.8
Coil Type
Aluminum Fin & Copper Pipe
Fin Type - Pipe Type
Slit Plate - Inner Rifled
Rows - F.P.I.
1 - 15.9
Face Area (sq.ft.)
7.26
Tube Size (in)
3/8”
Indoor Unit
Fan Type
Sirocco Fan
No. used
4
Dia & Length (in.)
5-26/32”
No. Speeds
3 & Auto
No. Poles (RPM, High)
8P - 1,040
No. Motors (W)
DC 1-111
CFM (HI/Med/Lo)
1,059/883/812
Indoor Sound Rating (Hi) (dB-A)
42
F.L. Amps (A)
0.67
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type
Slit Plate - Inner Rifled
Rows - Fins per inch
3 - 1 / 16”
Face Area (sq. ft.)
4.76
Tube Size (in.)
9/32”
Drain Connection Size (in.)
1-1/4”
Refrigerant
R410A
Lbs. - R410a
6.2
Control
Electric Expansion Valve
Connection
Flare
Line Length, Max (ft.)
165
Line Difference, Max (ft.)
50 (outdoor lower),
100 (outdoor higher)
Line Size (in. O.D. Discharge)
3/8"
Line Size (in. O.D. Suction)
5/8"
Dimensions (HxWxD)
Indoor Unit (Uncrated) (in.)
9-1/4 x 62-19/32 x 27-11/64
Outdoor Unit (Uncrated) (in.)
30-23/32 x 37 x 13 3/8
Weight (lbs.)
(Indoor) Net
88
(Outdoor) Net
143