Rheem Professional Electric Series Use and Care Manual - Page 20

Wiring Diagrams, Electric Water Heaters for, Phase Applications

Page 20 highlights

FIG. A-1 H Wiring Diagrams - Therm-O-Disc Thermostats (Type 59T) DOUBLE ELEMENT DOUBLE ELEMENT SIMULTANEOUS OPERATION SIMULTANEOUS OPERATION WITH 4 WIRE OUTLET DOUBLE ELEMENT NON-SIMULTANEOUS DOUBLE ELEMENT NON-SIMULTANEOUS WITH 4 WIRE OUTLET ! DOUBLE ELEMENT NON-SIMULTANEOUS WITH 3 WIRE OUTLET BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL G N BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL TO SECOND POWER SOURCE, "OFF PEAK" METER, OR TIMER BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL TM2 TM1 L1 G* L2 L1 G* L2 BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL L1 G* L2 BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL L1 G* L2 CONNECTOR TO "OFF PEAK" METER (TIMER) BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL TM2 L1 G* L2 JUNCTION BOX (ECO) & HIGH TEMP. LIMIT UPPER THERMOSTAT BLUE BLUE RED TM 1 BLACK TM 2 YELLOW RED JUNCTION BOX JUNCTION BOX YELLOW JUNCTION BOX BLACK BLUE (10 GA) YELLOW (10 GA) JUNCTION BOX RED (10 GA) BLACK (10 GA) JUNCTION BOX BLACK BLUE 1 THERMOSTAT & HIGH TEMP. 2 LIMIT (ECO) 1 WHITE 2 BLACK HEATING ELEMENT SINGLE ELEMENT 120 V ONLY BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION L1 G* L2 BLACK (10 GA) 1 3 2 4 1 2 YELLOW LOWER THERMOSTAT & HIGH TEMP LIMIT (ECO) UPPER HEATING ELEMENT BLUE RED (10 GA) BLACK (10 GA) UPPER THERMOSTAT & HIGH TEMP. LIMIT (ECO) 1 3 2 4 1 2 YELLOW LOWER THERMOSTAT & HIGH TEMP LIMIT (ECO) UPPER HEATING ELEMENT BLUE RED (10 GA) UPPER THERMOSTAT & HIGH TEMP. LIMIT (ECO) YELLOW BLACK RED UPPER THERMOSTAT 1 3 & HIGH TEMP. LIMIT (ECO) 2 4 1 4 2 1 3 2 4 1 4 2 BLUE YELLOW UPPER HEATING ELEMENT UPPER HEATING ELEMENT UPPER THERMOSTAT & HIGH TEMP. LIMIT (ECO) BLUE YELLOW BLACK 1 3 2 4 1 4 2 LOWER THERMOSTAT & HIGH TEMP LIMIT (ECO) UPPER HEATING ELEMENT RED BLACK BLUE JUNCTIO N RE BLAC 1 3 THERMOST AT 2 4 & HIGH 1 2 1 3 2 4 1 2 1 3 2 4 1 2 1 LOWER THERMOSTAT 2 1 1 1 2 2 LOWER 2 THERMOSTAT BLAC RE BLACK RED BLACK RED BLACK BLACK BLACK HEATIN G SINGLE ELEMENT LOWER HEATING ELEMENT FIG. A-2 FIG. B * Grounding conductor may be required. Refer to Wiring Section of Manual LOWER HEATING ELEMENT FIG. C LOWER HEATING ELEMENT FIG. D LOWER HEATING ELEMENT LOWER HEATING ELEMENT FIG. E FIG. F ! This water heater is factory equipped for two (2) wire connection to electrical power. For use with "off-peak" meter (timer) remove wire nut from red and black leads and connect to "off-peak" meter (timer). THIS ELECTRIC WATER HEATER IS WIRED AS INDICATED ABOVE OR BELOW UPPER THERMOSTAT & HIGH TEMP. LIMIT (ECO) Wiring Diagrams Electric Water Heaters for 3 - Phase Applications Therm-O-Disc Thermostats (Type 59T) For the connection of this water heater to a 3-Phase Branch Circuit, connect field wiring to the water heater as indicated in the appropriate wiring diagram at right. A separate junction box is being supplied with this water heater (check bottom of carton) to accomodate wiring and conduit connections. Install the Junction Box as shown on the Installation/Instruction Sheet included in the plastic bag attached to the heater. 20 BLACK (10 GA) DOUBLE ELEMENT SIMULTANEOUS OPERATION 3- PHASE BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL L1 L3 L2 G* BLUE (10 GA) YELLOW (10 GA) UPPER THERMOSTAT & HIGH TEMP. LIMIT (ECO) RED (10 GA) 1 3 2 4 1 2 BLUE YELLOW LOWER THERMOSTAT & HIGH TEMP LIMIT (ECO) UPPER HEATING ELEMENT 1 3 2 4 1 2 LOWER HEATING ELEMENT FIG. G BLACK RED BLACK DOUBLE ELEMENT NON-SIMULTANEOUS 3- PHASE BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL L1 L2 L3 G* BLUE YELLOW BLUE RED 1 3 2 4 1 4 2 YELLOW LOWER THERMOSTAT & HIGH TEMP LIMIT (ECO) UPPER HEATING ELEMENT 1 2 1 2 LOWER HEATING ELEMENT FIG. H BLACK

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

Grounding conductor may be required.
Refer to Wiring Section of Manual
*
This water heater is factory equipped for two (2) wire connection to
electrical power. For use with "off-peak" meter (timer) remove wire
nut from red and black leads and connect to "off-peak" meter (timer).
!
Wiring Diagrams — Therm-O-Disc Thermostats (Type 59T)
SINGLE ELEMENT
DOUBLE ELEMENT
SIMULTANEOUS OPERATION
DOUBLE ELEMENT
SIMULTANEOUS OPERATION
WITH 4 WIRE OUTLET
DOUBLE ELEMENT
NON-SIMULTANEOUS
DOUBLE ELEMENT
NON-SIMULTANEOUS
WITH 4 WIRE OUTLET
!
DOUBLE ELEMENT
NON-SIMULTANEOUS
WITH 3 WIRE OUTLET
FIG. A-1
FIG. A-2
FIG. B
FIG. C
FIG. D
FIG. E
FIG. F
2
1
2
THERMOSTAT
& HIGH TEMP.
LIMIT (ECO)
HEATING
ELEMENT
WHITE
BLACK
BLACK
H
JUNCTION
BOX
N
1
G
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
120 V ONLY
2
1
2
THERMOST
AT
& HIGH
HEATIN
G
RE
BLAC
BLAC
L1
G
*
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION
JUNCTIO
N
4
L2
RE
1
3
SINGLE ELEMENT
2
UPPER THERMOSTAT
& HIGH TEMP. LIMIT
(ECO)
UPPER
HEATING
ELEMENT
BLUE
L1
JUNCTION
BOX
4
L2
1
3
BLACK
RED
BLACK
LOWER
HEATING
ELEMENT
LOWER
THERMOSTAT
& HIGH TEMP
LIMIT (ECO)
1
2
1
1
2
BLUE
CONNECTOR TO "OFF PEAK"
METER (TIMER)
TM2
4
YELLOW
YELLOW
2
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
BLACK
LOWER
HEATING
ELEMENT
2
UPPER THERMOSTAT
& HIGH TEMP.
LIMIT (ECO)
UPPER
HEATING
ELEMENT
BLUE
YELLOW
BLACK
L1
JUNCTION
BOX
4
L2
RED
1
3
1
2
BLACK
RED
LOWER
THERMOSTAT
1
2
4
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
2
1
2
UPPER THERMOSTAT
& HIGH TEMP. LIMIT
(ECO)
UPPER
HEATING
ELEMENT
BLUE
YELLOW
L1
JUNCTION
BOX
4
L2
RED
1
3
1
2
4
BLACK
BLUE
BLACK
BLUE
YELLOW
LOWER
THERMOSTAT
LOWER
HEATING
ELEMENT
TM 1
BLACK
TM 2
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
G
*
G
*
G
*
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
UPPER THERMOSTAT
& HIGH TEMP. LIMIT (ECO)
2
UPPER
HEATING
ELEMENT
BLUE
L1
JUNCTION BOX
4
L2
1
3
RED
(10 GA)
BLACK
LOWER
HEATING
ELEMENT
LOWER
THERMOSTAT
& HIGH TEMP
LIMIT (ECO)
1
2
4
1
3
1
2
RED
2
BLACK
(10 GA)
YELLOW
BLACK
(10 GA)
RED
(10 GA)
G
*
2
UPPER THERMOSTAT
& HIGH TEMP. LIMIT (ECO)
UPPER
HEATING
ELEMENT
BLUE
L1
BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
JUNCTION BOX
4
L2
1
3
BLACK (10 GA)
RED (10 GA)
BLACK
LOWER
HEATING
ELEMENT
LOWER
THERMOSTAT
& HIGH TEMP
LIMIT (ECO)
1
2
4
1
3
1
2
RED
2
BLUE
(10 GA)
TO SECOND POWER SOURCE,
"OFF PEAK" METER, OR TIMER
TM2
TM1
YELLOW
(10 GA)
YELLOW
G
*
THIS ELECTRIC WATER HEATER IS WIRED AS INDICATED ABOVE OR BELOW
Wiring Diagrams
Electric Water Heaters for
3 - Phase Applications
Therm-O-Disc Thermostats
(Type 59T)
For the connection of this
water heat
er to a 3-Phase Branch
Circuit, con
nect field wiring to
the water heater as indicated in
the ap
propriate wiring diagram
at right. A sep
arate junction box
is being supplied with this water
heater (check bot
tom of carton)
to accomodate wir
ing and con-
duit con
nections. Install the
Junction Box as shown on the
Installation/Instruction Sheet
includ
ed in the plastic bag
attached to the heater.
DOUBLE ELEMENT
SIMULTANEOUS OPERATION
DOUBLE ELEMENT
NON-SIMULTANEOUS
FIG. G
FIG. H
2
UPPER THERMOSTAT
& HIGH TEMP. LIMIT (ECO)
UPPER
HEATING
ELEMENT
BLUE
4
L3
BLACK
BLACK
LOWER
HEATING
ELEMENT
LOWER
THERMOSTAT
& HIGH TEMP
LIMIT (ECO)
1
1
2
RED
2
BLUE
YELLOW
G
*
YELLOW
3
L2
1
1
L1
2
4
3- PHASE BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
2
UPPER THERMOSTAT
& HIGH TEMP. LIMIT (ECO)
UPPER
HEATING
ELEMENT
BLUE
3- PHASE BRANCH CIRCUIT
TO ELECTRICAL
DISTRIBUTION PANEL
4
L3
BLACK (10 GA)
RED (10 GA)
BLACK
LOWER
HEATING
ELEMENT
LOWER
THERMOSTAT
& HIGH TEMP
LIMIT (ECO)
1
4
1
2
RED
2
BLUE (10 GA)
YELLOW
G
*
YELLOW (10 GA)
3
3
L2
1
1
L1
2
20