Rheem RASL-JEC Installation Instructions

Rheem RASL-JEC Manual

Rheem RASL-JEC manual content summary:

  • Rheem RASL-JEC | Installation Instructions - Page 1
    INSTALLATION INSTRUCTIONS AIR-COOLED CONDENSING UNITS (-)ASL-JEC 18 SEER EQUIPPED WITH THE COMFORT CONTROL2 SYSTEM™ AND FEATURING DUAL DRIVE COMPRESSORS IN SELECT MODELS Featuring Earth-Friendly R-410A Refrigerant [ ] INDICATES METRIC CONVERSIONS ISO
  • Rheem RASL-JEC | Installation Instructions - Page 2
    for Installing & Servicing R-410A Models 9 4.2 Specifications of R-410A 10 4.3 Quick Reference Guide for 17.1 Remote Outdoor Temperature Model 37 18.0 TROUBLESHOOTING 37 18.1 Comfort Control2 System™ System Chart 40 18.5 General Trouble Shooting Chart 41 18.6 Service Analyzer Charts 42-46 18.7
  • Rheem RASL-JEC | Installation Instructions - Page 3
    , ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE
  • Rheem RASL-JEC | Installation Instructions - Page 4
    at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment. ! CAUTION Only use evaporators the compressor. This can result in compressor failure. ! CAUTION When coil is installed over a finished ceiling and/or living area, it is recommended that a
  • Rheem RASL-JEC | Installation Instructions - Page 5
    series of condensing units are designed to operate using the Comfort Control2 System™ or traditional 24VAC controls. These units are equipped with the Comfort Control2. Your installation controls. This installation instruction manual contains complete instructions for installation and setup using
  • Rheem RASL-JEC | Installation Instructions - Page 6
    INSTALLATION 060 = 60000 BTU/HR H L = DESIGN SERIES (R-410A) ACCAECSCESSS PANPEANLEL AALLLOLWO24W0 [6120 m4m"] SERVICE FITTING LOW LINE VOLTAGE 7⁄8" HIGH LINE VOLTAGE 11⁄4" LOW LINE VOLTAGE 7⁄8" VAPOR LINE CONNECTION LIQUID LINE CONNECTION 2.4 ELECTRICAL & PHYSICAL DATA TABLE 1 (-)ASL-JEC
  • Rheem RASL-JEC | Installation Instructions - Page 7
    Installation Instruction Manual and reference the applicable Engineering Specification Sheet when installing to be installed in an area where contaminants are likely to be a problem, special some protection, but cannot violate minimum airflow and service access clearances. • Elevating the unit off its
  • Rheem RASL-JEC | Installation Instructions - Page 8
    of other equipment horizontally installed in proximity to the costs. • Locate the unit where water run off will not create a problem discharge, or 24-inch service, clearances. 3.5 Customer Satisfaction -Down Method INSTRUCTIONS IMPORTANT: These instructions are intended as a guide to securing
  • Rheem RASL-JEC | Installation Instructions - Page 9
    FIGURE 2 RECOMMENDED ELEVATED INSTALLATION STEP 3: Using basepad as a guide, mark spots on concrete where 4 holes assembly per unit's installation instructions. 4.0 REFRIGERANT CONNECTIONS All units are factory charged with Refrigerant 410A. All models are supplied with service valves. Keep tube
  • Rheem RASL-JEC | Installation Instructions - Page 10
    safely with nitrogen or a mixture of R-410A and nitrogen. 4.3 Quick Reference Guide For R-410A • R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A. • R-410A refrigerant cylinders are pink
  • Rheem RASL-JEC | Installation Instructions - Page 11
    OIL OR DEBRIS. 6.0 INDOOR COIL REFER TO INDOOR COIL MANUFACTURER'S INSTALLATION INSTRUCTIONS. IMPORTANT: The manufacturer is not responsible for the performance and 6.1 Location Do not install the indoor coil in the return duct system of a gas or oil furnace. Provide a service inlet to the coil for
  • Rheem RASL-JEC | Installation Instructions - Page 12
    size permitted to minimize the system charge. 3. Tables 4, 5, and 6 may be used for sizing horizontal runs. 7.4 Tubing Installation Observe the following when installing correctly sized type "L" refrigerant tubing between the condensing unit and evaporator coil: • If a portion of the liquid line
  • Rheem RASL-JEC | Installation Instructions - Page 13
    TABLE 4 (-)ASL LIQUID LINE SIZING LIQUID LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL R-410A System Capacity Model Line Size Connection Size (Inch I.D.) [mm] Line Size (Inch O.D.) [mm] -024 -036 -039 -048 -060 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 1/4" [6.35]* 5/16" [7.93]
  • Rheem RASL-JEC | Installation Instructions - Page 14
    TABLE 5 (-)ASL SUCTION LINE SIZING SUCTION LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL R-410A System Capacity Model Line Size Connection Size (Inch I.D.) [mm] Line Size (Inch O.D.) [mm] -024 -036 & -039 -048 -060 3/4" [19.05] 3/4" [19.05] 7/8" [22.22] 7/8" [22.22] 5/8" [15.88] 3/4" [19.05]*
  • Rheem RASL-JEC | Installation Instructions - Page 15
    temporary hangers, then straighten the tubing and install permanent hangers. Line must be adequately supported. • The vapor line must be insulated tubing between the outdoor unit and indoor coil. Flow dry nitrogen into a service port and through the tubing while brazing. • After brazing - use an
  • Rheem RASL-JEC | Installation Instructions - Page 16
    8.0 DUAL DRIVE COMPRESSORS The -039, -048, & -060 condensing units contain two compressors to deliver maximum efficiency and comfort. The Dual Drive Compressors are sized to increase run times at first stage operation (partial capacity). When additional capacity is needed, a two stage thermostat
  • Rheem RASL-JEC | Installation Instructions - Page 17
    JEC control. The two controls are identical and interchangeable. This allows the controls to be swapped for troubleshooting be accessed by a service tool or the thermostat. As with any JEC unit, the airflow .) 10.0 HARD START COMPONENTS Factory-installed start components are standard on all models
  • Rheem RASL-JEC | Installation Instructions - Page 18
    OVERLOAD HAS HAD TIME TO RESET BEFORE CONDEMNING THE COMPRESSOR. 11.1 Evacuation Procedure Evacuation is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture
  • Rheem RASL-JEC | Installation Instructions - Page 19
    Communications Line 2 Low Volt Fuse • If required replace with 3 A automotive ATC style blade fuse Low Pressure Control (LPC Input) • Low-pressure control is factory installed • Low pressure control is an automatic resetting device High Pressure Control (HPC Input) • High-pressure control is factory
  • Rheem RASL-JEC | Installation Instructions - Page 20
    fault history for the compressor it controls. Fault codes for compressor A can be retrieved using a service tool or via the installer menus. The fault codes for compressor B are accessible by two methods.: 1. Using a service tool plugged directly into the compressor B Comfort Control2 board. 20
  • Rheem RASL-JEC | Installation Instructions - Page 21
    serial com- 13.X Serial Cmounmicamtinugnniectwaotriko. n ICC Control Operation 12.4 Comfort Control2 ICC Control Operation Installation VeInrsiftiaclalattiioonn Verification • 24V AC po•w2e4rVoAnCRp&owCemr ounsRt b&eCpmruesstebnet aptretsheenItCatCthfeoIrCiCt tfooroitpteoroapteerate • Line voltag
  • Rheem RASL-JEC | Installation Instructions - Page 22
    segment LEDs followed by a "21". IMPORTANT: This mode of active protection must be manually deactivated. AIaf3mc)tIthbMILieiMvoePeLncOPtPkPORteCreTdoRmoAtRTeppNAcoAeetcTArntiNtoa:osicvtrnTutetThir:hvwePrieesirTietosPmhht(rbei3oossec)odttlmeiofetocitwonmtolidofo-e5ecans°CkocFf-toofo,ivduCratehectto
  • Rheem RASL-JEC | Installation Instructions - Page 23
    will display a flashing "L" followed by a flashing "07" when an open start IMcirPcOuitRcToAndNitiTo:n oTchciusrms.ode of active protection must be manually deactivated. 5) Open Run Circuit Lockout • The ICC will display a flashing "L" followed by a flashing "7" when an open start circuit condition
  • Rheem RASL-JEC | Installation Instructions - Page 24
    Test Manoddrel(eTaesest. Button on the ICC) • • EnTtheer TEST mode bcayupsreesstshinegICthCe tToEdSoTthbeutftoolnlowwiitnhgan insulated probe for one (1) second an1d) reRleasseets. the ICC from any active protection lockout mode • • T123)))h23I"f))ceRRE"tTh,nREeeeE"sesneCeeS3resgtt-T"erss•mi,
  • Rheem RASL-JEC | Installation Instructions - Page 25
    c - Anti-short cycle timer (3 minutes) or • The unit has received a command for first stage Minimum run timer (30 seconds) active cooling during an active anti-short cycle timer or minimum run timer. 12.7 FLASHING • Wait until unit timer has expired or press the COMFORT CONTROL2 SYSTEM™
  • Rheem RASL-JEC | Installation Instructions - Page 26
    four (4) compressor cycles is less than three TTToooFFLLeeCCrrwooggruummAAAeeEErrbbittttAoolDDooCCNNNaaeepplttppmmffchheessdooTTTooeeootrreeinninbnbpprraaff:::vseeooccssiieettttpeeeuurroollrrTTTppttlllnnaarroohhmmaPooeehhheettttllyrrrwweerriiippeerrorrLLffsssiiaiieerraaooeetsssseeoommmennddrreefee((
  • Rheem RASL-JEC | Installation Instructions - Page 27
    Fault 21 - Low Pressure Control Open and u•niUt nit has low refrigerant charge DFFLuLLEaAADl 7CSSs-HHoDSFdeIIiLesgNNCL2TNfopAmo1pGGh2looraSee1ent-ytrneHthaI-t:rLCetoITioANolCfhwC2F22TLCC2T2T2FLLC22TLinTcGT2LCre78979988a89dah2thh22oh2sooor9h2Poiuutei9e99le9nnnnv-------e9ponrl-tl9ttttetetIIIeI---tw-
  • Rheem RASL-JEC | Installation Instructions - Page 28
    CONVENTIONAL THERMOSTAT WIRING Thermostat Load - Amps 12.8 Conventional 24VAC Thermostat Control Wiring The (-)ASL series of heat pumps allow the installer to use conventional 24VAC control wiring and a conventional thermostat for proper unit operation. IMPORTANT: The preferred method of unit
  • Rheem RASL-JEC | Installation Instructions - Page 29
    (-)HPN Air Handler W1 W2 Y1 Y2 R C G ODD (-)ASL Condensing Unit Y Y1 Y/BL Y2 R R BR C W/R L WIRING INFORMATION Line Voltage -Field Installed -Factory Standard *See Section 5.11 for proper DIP switch selection. FIGURE 10 TYPICAL TWO-STAGE THERMOSTAT: CONDENSING UNIT WITH ELECTRIC HEAT
  • Rheem RASL-JEC | Installation Instructions - Page 30
    size the 24-volt control w 1. Using a service tool plugged directly into the compressor Comfort Control2 2. board !!!! 12.11 ICC Control O13p.eXraItiConCwCitohnCtroonlveOnptieornaatlioThnewrmitohstCatoWnvireinntgional Thermosta Installation Verification • 24V AC power on RI&nCstamlluasttiobne
  • Rheem RASL-JEC | Installation Instructions - Page 31
    fsroammecocanltlinfuoirngcotooloinpgeroapteeraantidonfla, sthheaICC will locLk"oount tthhee dcuoaml p7r-essesgomr etontkLeEepDsitfforlolomwecdonbtyinau"i2n1g".to operate and flash a L" on the 7sIeMgPmOeRntTLAENDT:s fTohlilsowmeodebyofaa"c2ti1ve".protection must be manually reset. 4 31
  • Rheem RASL-JEC | Installation Instructions - Page 32
    LL2299--OOppeennhhigighhppreressssuurereccoonntrtorol l IMPORTANT: This mode of active protection must be manually reset. I3M) LPoOcRkeTdARNoTto:r This mode of active protection must be manually deactivated. • The ICC will dispAlacytaivfelaPsrhointegc"tLio"nfo-lloCwoeddebLy4a-flLasohciknegd"0ro4t
  • Rheem RASL-JEC | Installation Instructions - Page 33
    IMPORTANT: This mode of active protection must be manually deactivated. Exiting Active Compressor Protection Lockout Three are threEexmiteinthgoAdscttiovereCseotmthpereICssCorafPteror taenctaicotnivLeopcrkooteucttion lockout: 1) Cycle Tthhereleinaerveotlhtraegeemtoethoedusntiot reset the ICC
  • Rheem RASL-JEC | Installation Instructions - Page 34
    CONVENTIONAL THERMOSTAT WIRING • A "0" will be displayed with no faults are stored • The ICC will automatically exit the FAULT RECALL mode after displaying stored faults IMPORTANT: The ICC stores the previous two weeks of history faults. The com- FapuleltteRsetocraeldl Mfauoldt ehi(
  • Rheem RASL-JEC | Installation Instructions - Page 35
    be checked to the charge table attached to the service panel and adjusted, if required. Allow a increases the possibility of high humidity problems. Low indoor airflow reduces total are too small, they also cause noise. The installers should balance the air distribution system to ensure proper
  • Rheem RASL-JEC | Installation Instructions - Page 36
    in the cooling and heating mode. The service port on the liquid service valve (small valve) and suction (large valve installation, evacuation of interconnecting tubing and indoor coil is adequate; otherwise, evacuate the entire system. Use the factory charge shown in Table 1 of these instructions
  • Rheem RASL-JEC | Installation Instructions - Page 37
    installed away from the outdoor unit for better thermostat temperature display. 18.0 TROUBLESHOOTING IMPORTANT: The JEC series problems but only to guide the technician's troubleshooting. Through a series Install Config to move back up press the Menu button. See the Installation Instructions. 37
  • Rheem RASL-JEC | Installation Instructions - Page 38
    Control2 System™ needs information specific to the unit the control is installed in. This information is called shared data because it is distributed control gets this information is by the memory card that should be installed on the old control. Remove the memory card from the old control
  • Rheem RASL-JEC | Installation Instructions - Page 39
    Checks Flow Chart Thermostat call For cooling, no cooling Outdoor Unit Running? Yes No Refer to panel cover/documentation for Fault Code Troubleshooting. Check fault history for other faults. 7-Segment display lit? Yes No Check control voltage (R and C) to control Y1 LED lit? Yes No
  • Rheem RASL-JEC | Installation Instructions - Page 40
    18.4 Cooling Mechanical Checks Flow Chart Thermostat calling, but unit not cooling Electrical Chart Pressure problems? High Head Pressure Low Head Pressure Low Suction Pressure Dirty Outdoor Coil Low on Charge Dirty Filters Inoperative Outdoor Fan Open IPR Valve Dirty Indoor
  • Rheem RASL-JEC | Installation Instructions - Page 41
    18.5 General Trouble Shooting Chart ! WARNING DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY should be approximately 400 CFM per ton. • Charge per procedure attached to unit service panel • Recover refrigerant, evacuate & recharge, add filter drier • At compressor terminals
  • Rheem RASL-JEC | Installation Instructions - Page 42
    18.6 Service Analyzer Charts COMPRESSOR OVERHEATING SYMPTOMS High superheat problem corrected before diagnosis continues Correct and complete diagnosis Have problem corrected Check system charge Clean coil Replace fan motor Replace fan blade Replace with correct rotation motor Correct installation
  • Rheem RASL-JEC | Installation Instructions - Page 43
    (3 phase) POSSIBLE CAUSE Poor evacuation on installation or during service Non-condensibles air Wrong refrigerant Copper tubing cuttings or unit Re-check wiring diagram Wrong unit Power supply problem Wrong unit Power supply problem Wiring undersized Loose connections Check incoming power and fusing
  • Rheem RASL-JEC | Installation Instructions - Page 44
    out of calibration, Customer misuse CHECK OR REMEDIES Replace crankcase heater Check Piping guidelines Check and adjust charge CHECK OR REMEDIES Review pipe size guidelines Check TEV application CHECK OR REMEDIES Secure the bulb and insulate Relocate bulb Use correct replacement Adjust, if possible
  • Rheem RASL-JEC | Installation Instructions - Page 45
    flooded evaporator Compressor in cold location Any of the causes listed under Symptoms of Problem #2 CHECK OR REMEDIES Recover charge, install filter-drier, evacuate system, recharge Recover charge, install filter-drier, evacuate system, recharge Correct the charge Remove restriction in liquid line
  • Rheem RASL-JEC | Installation Instructions - Page 46
    External equalizer line not connected or line plugged Sensing bulb lost its operating charge Valve body damaged during soldering or by improper installation CHECK OR REMEDIES Ensure air flow is equally distributed through evaporator Check for blocked distributor tubes Ensure blower is moving proper
  • Rheem RASL-JEC | Installation Instructions - Page 47
    612.8 18.7 Subcooling Calculation 1. Measure the liquid pressure at the liquid line service valve. 2. Convert the liquid line pressure to saturated temperature. See Table CONDITIONING SYSTEM TROUBLESHOOTING TIPS AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPS SYSTEM PROBLEM Overcharge INDICATORS
  • Rheem RASL-JEC | Installation Instructions - Page 48
    19.0 WIRING DIAGRAMS FIGURE 13 WIRING DIAGRAM FOR (-)ASL-024JEC & 036JEC 48
  • Rheem RASL-JEC | Installation Instructions - Page 49
    FIGURE 14 WIRING DIAGRAM FOR (-)ASL-039JEC, 048JEC, & 060JEC (DUAL DRIVE) 49
  • Rheem RASL-JEC | Installation Instructions - Page 50
    50
  • Rheem RASL-JEC | Installation Instructions - Page 51
    51
  • Rheem RASL-JEC | Installation Instructions - Page 52
    52 CM 1108
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

92-101691-05-02
SUPERSEDES 92-101691-05-01
AIR-COOLED CONDENSING UNITS
(-)ASL-JEC 18 SEER EQUIPPED WITH THE
COMFORT CONTROL
2
SYSTEMâ„¢
AND FEATURING DUAL DRIVE COMPRESSORS IN
SELECT MODELS
INSTALLATION INSTRUCTIONS
[ ] INDICATES METRIC CONVERSIONS
ISO 9001:2000
Featuring Earth-Friendly
R-410A Refrigerant