Rheem RASL-JEC Installation Instructions - Page 39

Electrical Checks Flow Chart

Page 39 highlights

18.3 Electrical Checks Flow Chart Thermostat call For cooling, no cooling Outdoor Unit Running? Yes No Refer to panel cover/documentation for Fault Code Troubleshooting. Check fault history for other faults. 7-Segment display lit? Yes No Check control voltage (R and C) to control Y1 LED lit? Yes No No call received. 24V Systems: Check thermostat, control wiring Comm Systems: Check comm. wiring, T-Stat No Flashing Mode Character Waiting for Anti-S.C. Delay to clear Yes No Alternating "C" and "##" (Code) Yes Note: For solid comm LED, check comm wiring, term/bus switches at ICC and AH ctrls. Control in Lockout Mode. Check fault history and refer to Diagnostic Chart. SEE PANEL COVER OR OTHER DOCUMENTATION FOR FAULT CODE TROUBLESHOOTING. 39

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

39
18.3 Electrical Checks Flow Chart
No
No
No
No
Yes
Yes
Yes
Yes
Outdoor Unit
Running?
7-Segment display lit?
Flashing Mode Character
Alternating ā€œCā€ and ā€œ##ā€ (Code)
SEE PANEL COVER OR
OTHER DOCUMENTATION
FOR FAULT CODE
TROUBLESHOOTING.
Control in Lockout Mode.
Check fault history and refer to
Diagnostic Chart.
Note: For solid comm LED, check
comm wiring, term/bus switches at
ICC and AH ctrls.
Refer to panel cover/documentation
for Fault Code Troubleshooting.
Check fault history for other faults.
Check control voltage (R and C)
to control
Waiting for Anti-S.C. Delay to clear
Thermostat call
For cooling, no cooling
No
Yes
Y1 LED lit?
No call received.
24V Systems: Check thermostat,
control wiring
Comm Systems: Check comm.
wiring, T-Stat