Seagate ST2000NM0031 Constellation ES.1 SAS Product Manual - Page 38
Power dissipation
View all Seagate ST2000NM0031 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 38 highlights
7.4 Power dissipation 2TB models in 3Gb operation Please refer to Table 2 for power dissipation numbers. To obtain operating power for typical random read operations, refer to the following I/O rate curve (see Figure 4). Locate the typical I/O rate for a drive in your system on the horizontal axis and read the corresponding +5 volt current, +12 volt current, and total watts on the vertical axis. To calculate BTUs per hour, multiply watts by 3.4123. Figure 4. 2TB models (3Gb) DC current and power vs. input/output operations per second Note. For power details about SED vs. non-SED drive, please refer to section 7.8. 30 Constellation ES.1 SAS Product Manual, Rev. E
30
Constellation ES.1 SAS Product Manual, Rev. E
7.4
Power dissipation
2TB models in 3Gb operation
Please refer to Table 2 for power dissipation numbers.
To obtain operating power for typical random read operations, refer to the following I/O rate curve (see Figure
4). Locate the typical I/O rate for a drive in your system on the horizontal axis and read the corresponding +5
volt current, +12 volt current, and total watts on the vertical axis. To calculate BTUs per hour, multiply watts by
3.4123.
Figure 4.
2TB models (3Gb) DC current and power vs. input/output operations per second
Note.
For power details about SED vs. non-SED drive, please refer to section 7.8.