Tripp Lite 9PX1500RT Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 27
HotSwap MBP module operation, UPS start-up with the HotSwap MBP module, HotSwap MBP module test
View all Tripp Lite 9PX1500RT manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 27 highlights
ENGLISH 3. Installation 9PX 2200GRT & 9PX 3000GRT 5 1 MBP 6 7 28 29 30 31 32 33 34 35 36 15 LOAD HotSwap MBP module operation 1. Connect the input 36 on the HotSwap MBP module to the AC-power source. 2. Connect the UPS input cable 1 to the "UPS Input socket" 35 on the HotSwap MBP module. 3. Connect the UPS outlet 5 to the "UPS Output" 34 on the HotSwap MBP module (using the cable 28 supplied for G models). These cables and the connectors are marked in red. 4. C onnect the equipment to the outlets 29 on the HotSwap MBP module. These outlets differ, depending on the version of the HotSwap MBP module. Caution: when using HotSwap MBP, do not use UPS outlets to directly power equipment. As operating the bypass switch 33 will cut supply voltage to the equipment. 31 32 33 The HotSwap MBP module has a rotary switch 33 with two positions: Normal the load is supplied by the UPS, LED 31 is on. Bypass the load is supplied directly by the AC-power source. LED 32 is on. UPS start-up with the HotSwap MBP module 1. Check that the UPS is correctly connected to the HotSwap MBP module. 2. Set switch 33 to Normal position. 3. Start the UPS by pressing the ON/OFF button on the UPS control panel. The load is supplied by the UPS. LED 31 "UPS ON - OK to switch" on the HotSwap MBP module goes ON. HotSwap MBP module test 1. Set switch 33 to Bypass position and check that the load is still supplied. 2. Set switch 33 back to Normal position. 9PX 1-3 KVA US_EN Page 27