3. Connect remaining wires 2. Attach direct wire cable to strain relief Connect remaining wires to outer terminal block screws. Tighten screws. Finally, reinsert tab of terminal block cover into slot of dryer rear panel. Secure cover with hold-down screw. Now, go to "Venting Requirements". Direct Wire Put direct wire cable through the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Tighten strain relief screw against the direct wire cable. If your wiring looks like this: 4-wire direct connection: Go to "4-Wire Direct Connection" on this page. 3-wire direct connection: Go to "3-Wire Direct Connection" on page 10. 4-wire Direct Wire Connection IMPORTANT: A 4-wire connection is required for mobile homes and where local codes do not permit 3-wire connections. 1. Prepare your 4-wire cable for direct connection (251"mm) Direct Wire Connection Direct wire strain relief 1. Attach direct wire strain relief A B C (127 5" mm) Direct wire cable must have 5 ft. (1.52 m) of extra length so dryer may be moved if needed. Strip 5" (127 mm) of outer covering from end of cable, leaving bare ground wire at 5" (127 mm). Cut 11/2" (38 mm) from remaining 3 wires. Strip insulation back 1" (25 mm). Shape ends of wires into hooks. Unscrew the removable conduit connector (A) and any screws from a 3/4" (19 mm) UL listed strain relief (UL marking on strain relief). Put the threaded section of the strain relief (C) through the hole below the terminal block opening (B). Reaching inside the terminal block opening, screw the removable conduit connector (A) onto the strain relief threads. 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

9
3.
Connect remaining wires
Connect remaining wires to outer terminal block screws.
Tighten screws. Finally, reinsert tab of terminal block cover
into slot of dryer rear panel. Secure cover with hold-down
screw. Now, go to "Venting Requirements".
Direct Wire
Unscrew the removable conduit connector (A) and any
screws from a 3/4" (19 mm) UL listed strain relief (UL marking
on strain relief). Put the threaded section of the strain relief
(C) through the hole below the terminal block opening (B).
Reaching inside the terminal block opening, screw the
removable conduit connector (A) onto the strain relief threads.
C
B
A
1.
Attach direct wire strain relief
Put direct wire cable through the strain relief. The strain
relief should have a tight fit with the dryer cabinet and be in
a horizontal position. Tighten strain relief screw against the
direct wire cable.
2.
Attach direct wire cable
to strain relief
Direct wire strain relief
DIRECT WIRE CONNECTION
3-wire direct connection:
Go to "3-Wire Direct Connection"
on page 10.
4-wire direct connection:
Go to "4-Wire Direct Connection"
on this page.
If your wiring looks like this:
4-WIRE DIRECT WIRE CONNECTION
IMPORTANT:
A 4-wire connection is required for mobile
homes and where local codes do not permit 3-wire connections.
Direct wire cable must have 5 ft. (1.52 m) of extra length so
dryer may be moved if needed.
Strip 5" (127 mm) of outer covering from end of cable,
leaving bare ground wire at 5" (127 mm). Cut 1
1
/
2
" (38 mm)
from remaining 3 wires. Strip insulation back 1" (25 mm).
Shape ends of wires into hooks.
1"
(25 mm)
5"
(127 mm)
1.
Prepare your 4-wire cable for
direct connection