HMP155ATemperature and Relative Humidity Probe current at 12 volts. Approximately 2 seconds is required for the sensor to warm up after power is switched on. At measurement rates slower than once per 5 seconds, the overall power consumption (datalogger and sensors) may be reduced by switching power to the HMP155A. Most current Campbell Scientific dataloggers have a built-in switched 12 volts that can be used to control power. NOTE HMP155 sensors purchased directly from Vaisala with serial numbers < E4430001 require approximately 5 seconds warm up time. The CR9000, CR510, CR500, CR7, CR10, and 21X dataloggers do not have a built-in switched 12 V. Users with these dataloggers can power the sensor continuously or purchase the model SW12V to switch power. The -L option on the model HMP155A Temperature and Relative Humidity probe (HMP155A-L) indicates that the cable length is user specified. TABLE 5-1 gives the recommended lead length. Add 2 ft to the cable length if the enclosure is mounted to the leg base of a CM106B, CM110, CM115, or CM120 tripod. TABLE 5-1. Recommended Lead Lengths 2 m Height Mast/Leg CM202 9 ft 11 ft CM106B 14 ft Atop a tripod or tower via a 2 ft crossarm CM110 CM115 CM120 UT10 UT20 14 ft 19 ft 24 ft 14 ft 24 ft UT30 37 ft The probe's cable can terminate in: • Pigtails that connect directly to a Campbell Scientific datalogger (option -PT). • Connector that attaches to a prewired enclosure (option -PW). Refer to www.campbellsci.com/prewired-enclosures for more information. 6. Specifications Features: • Well-suited for long-term, unattended applications • Accurate and rugged • Compatible with Campbell Scientific CRBasic dataloggers: CR200(X) series, CR800 series, CR1000, CR3000, CR5000, and CR9000(X). Also compatible with Edlog dataloggers: CR500, CR510, CR10(X), CR23X, 21X, and CR7 Operating temperature range for humidity measurement: Storage temperature range: Electromagnetic compatibility: -80° to +60°C -112° to +140°F) -80° to +60°C -112° to +140°F) Complies with EMC standard EN61326-1, Electrical equipment for measurement 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

HMP155ATemperature and Relative Humidity Probe
current at 12 volts.
Approximately 2 seconds is required for the sensor to
warm up after power is switched on.
At measurement rates slower than once
per 5 seconds, the overall power consumption (datalogger and sensors) may be
reduced by switching power to the HMP155A.
Most current Campbell
Scientific dataloggers have a built-in switched 12 volts that can be used to
control power.
HMP155 sensors purchased directly from Vaisala with serial
numbers < E4430001 require approximately 5 seconds warm up
time.
The CR9000, CR510, CR500, CR7, CR10, and 21X dataloggers do not have a
built-in switched 12 V.
Users with these dataloggers can power the sensor
continuously or purchase the model SW12V to switch power.
The -L option on the model HMP155A Temperature and Relative Humidity
probe (HMP155A-L) indicates that the cable length is user specified.
TABLE
5-1 gives the recommended lead length. Add 2 ft to the cable length if the
enclosure is mounted to the leg base of a CM106B, CM110, CM115, or
CM120 tripod.
TABLE 5-1.
Recommended Lead Lengths
2 m Height
Atop a tripod or tower via a 2 ft crossarm
Mast/Leg
CM202
CM106B
CM110
CM115
CM120
UT10
UT20
UT30
9 ft
11 ft
14 ft
14 ft
19 ft
24 ft
14 ft
24 ft
37 ft
The probe’s cable can terminate in:
Pigtails that connect directly to a Campbell Scientific datalogger
(option –PT).
Connector that attaches to a prewired enclosure (option –PW).
Refer
to
www.campbellsci.com/prewired-enclosures
for more information.
6.
Specifications
Features:
Well-suited for long-term, unattended applications
Accurate and rugged
Compatible with Campbell Scientific CRBasic dataloggers:
CR200(X) series, CR800 series, CR1000, CR3000, CR5000, and
CR9000(X).
Also compatible with Edlog dataloggers: CR500,
CR510, CR10(X), CR23X, 21X, and CR7
Operating temperature range
for humidity measurement:
–80° to +60°C –112° to +140°F)
Storage temperature range:
–80° to +60°C –112° to +140°F)
Electromagnetic compatibility:
Complies with EMC standard EN61326-1,
Electrical equipment for measurement
NOTE