CyberPower CP1350AVRLCD Function Setup Guide - Page 2

Function, LCD Display, Options, Default, Description

Page 2 highlights

Function Sensitivity Low Battery Warning LCD Display Options Low Medium High Escape to Function Menu 5~8 mins Escape to Function Menu Self Test (Battery Test) Audible Alarm YES Escape to Function Menu b.on b.off Escape to Function Menu 3 Default Medium 5 mins Description If the connected equipment can tolerate more power events (Example: unstable power often associated with stormy weather), select Low Sensitivity. The UPS will go to Battery Mode less often. If the connected equipment is more sensitive to power events, select High Sensitivity. The UPS will go to Battery Mode more often. The audible alarm will sound when the remaining runtime is less than the value selected. Function LCD Auto Off Last Fault Reason LCD Display Options L.on (Auto Off is on) L.oFF (Auto Off is off) Escape to Function Menu No Action In Line Mode, select YES to perform a Self Test on the battery. Back to Default Settings YES Default L.on Description "L.on" (Auto Off is on): In Line Mode, LCD screen will off automatically after 1 min of inactivity; in Battery Mode, LCD screen is always on. "L.oFF" (Auto Off is off): LCD screen is always on. No Action There is no setting in this page. This page will only show the error code for last fault reason. E01 : Charger fault (Over Charge). E02 : Charger fault (No Charge) E11 : Battery Fault E21 : Output short. E22 : Over load. Select Yes to restore the UPS factory default settings. b.on "b.on" is buzzer enable; "b.oFF" is buzzer disable. If b.oFF is selected, the unit will mute all alarms except for fault or overload condition. You can also set the audible alarm with the MUTE button mentioned before. Return to Status Display Escape to Function Menu -- Press the ENTER Button to leave setup mode and go back to the Status Display. All rights reserved. Reproduction without permission is prohibited. 4

  • 1
  • 2

3
4
Function
LCD Display
Options
Default
Description
Sensitivity
Low
Medium
High
Escape to
Function
Menu
Medium
If the connected equipment
can tolerate more power
events (Example: unstable
power often associated with
stormy weather), select Low
Sensitivity. The UPS will go to
Battery Mode less often. If the
connected equipment is more
sensitive to power events,
select High Sensitivity. The
UPS will go to Battery Mode
more often.
Low Battery Warning
5~8 mins
Escape to
Function
Menu
5 mins
The audible alarm will sound
when the remaining runtime
is less than the value
selected.
Self Test
(Battery Test)
YES
Escape to
Function
Menu
No Action
In Line Mode, select YES to
perform a Self Test on the
battery.
Audible Alarm
b.on
b.off
Escape to
Function
Menu
b.on
“b.on” is buzzer enable;
“b.oFF” is buzzer disable.
If b.oFF is selected, the unit
will mute all alarms except for
fault or overload condition.
You can also set the audible
alarm with the MUTE button
mentioned before.
Function
LCD Display
Options
Default
Description
LCD Auto Off
L.on (Auto Off is on)
L.oFF (Auto Off is off)
Escape to
Function
Menu
L.on
“L.on” (Auto Off is on): In Line
Mode, LCD screen will off
automatically after 1 min of
inactivity; in Battery Mode,
LCD screen is always on.
“L.oFF” (Auto Off is off): LCD
screen is always on.
Last Fault Reason
There is no setting in this
page. This page will only
show the error code for last
fault reason.
E01 : Charger fault (Over
Charge).
E02 : Charger fault (No
Charge)
E11 : Battery Fault
E21 : Output short.
E22 : Over load.
Back to Default Settings
YES
Escape to
Function
Menu
No Action
Select Yes to restore the UPS
factory default settings.
Return to Status Display
--
Press the ENTER Button to
leave setup mode and go
back to the Status Display.