CyberPower CP1500AVRT User Manual - Page 2

Input, Output, Battery Mode, Normal Mode

Page 2 highlights

DEFINITIONS FOR ILLUMINATED LED INDICATORS On Line On Off Off On/Off On Battery Off Flashes while beeping Flashes while beeping Off/On On/Off Off/On On/Off Off/On AVR Off Off Off Off Off Off Overload Off Off Off On Off Off Alarm Off Normal Condition Beep twice every 30 seconds Rapid beeping every 1/2 second Constant tone Constant tone Utility Failure - The UPS is providing power to battery protected outlets from its battery. Utility Failure - The UPS is providing battery power. Rapid beeping indicates the unit will run out of power shortly. Overload Fault - Occurs when connected equipment exceeds the listed capacity of the UPS. Turn the UPS off, unplug at least one piece of equipment from battery outlets, wait 10 seconds, reset the circuit breaker and turn the unit on. Short Fault - Unplug at least one piece of equipment from battery outlets and turn the UPS on again. UPS Fault - Contact CyberPower Systems for support. Beep every 2 seconds Charger Fault - Contact CyberPower Systems for support. FUNCTION SETUP GUIDE - SENSITIVITY SETUP Even when the UPS is operating normally (on line mode), the AC input voltage may not be stable all the time. Sensitive equipment may be prone to damage caused by unexpected voltage fluctuations. Use the following steps to adjust the sensitivity of the UPS unit: 1. Please make sure the UPS is in LINE MODE and operating in a normal condition. 2. To Enter the Sensitivity Setup mode, press the MUTE Button for 6 seconds until all indicators flash rapidly. 3. The unit will show the current sensitivity setting, as shown in the following table. 4. To select Low Sensitivity setting: shortly press MUTE button until one red indicator flashes. 5. To select Medium Sensitivity setting, shortly press the MUTE button until red and yellow indicators flash. 6. To select High Sensitivity setting, shortly press the MUTE button until green, yellow and red indicators flash. 7. To set up a level of sensitivity, hold down the MUTE button until the green indicator (the first one) illuminates. 8. Once in setup mode, if there is no action within 7 seconds, the unit will exit setup mode without changing any settings. Indicators Illuminate 1 (Red) 2 (Yellow, Red) 3 (Green, Yellow, Red) Sensitivity Low Medium (Default) High Description If the connected equipment can tolerate more power events (example: unstable power often associated with stormy weather), select Low Sensitivity and the UPS will go to Battery Mode less often. The UPS will go to Battery Mode if the power is unstable. If the connected equipment is more sensitive to power events, select High Sensitivity and the UPS will go to Battery Mode more often. TROUBLESHOOTING Problem Circuit breaker button is projecting from the back of the unit. The UPS does not perform expected runtime. The UPS will not turn on. Possible Cause Circuit breaker has been tripped due to an overload. Battery not fully charged. Battery is worn out. The on/off switch is designed to prevent damage from rapidly turning it off and on. The unit is not connected to an AC outlet. The battery is worn out. Mechanical problem. Solution Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker by pressing the button, and then turn the UPS on. Recharge the battery by leaving the UPS plugged in. Contact CyberPower Systems about replacement batteries at: cyberpowersystems.com/support. Turn the UPS off. Wait 10 seconds and then turn the UPS on. The unit must be connected to a 120V 60Hz outlet. Contact CyberPower Systems about replacement batteries at: cyberpowersystems.com/support. Contact CyberPower Systems at: cyberpowersystems.com/support. The USB / serial cable is not connected. Connect the USB / serial cable to the UPS unit and an open USB / serial port on the back of the computer. You must use the cable that came with the unit. PowerPanel® Personal is inactive (all icons are gray). The USB / serial cable is connected to the wrong port. Check the back of the computer for an additional USB / serial port. Move the cable to this port. The unit is not providing battery power. Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS back on. This should reset the unit. Additional troubleshooting information can be found at "Support" at www.CyberPowerSystems.com TECHNICAL SPECIFICATIONS Series Model Capacity Nominal Input Voltage Input Frequency On-Battery Output Voltage Max. Load for UPS Outlets (5 Outlets) Max. Load for Full-Time Surge Protection outlets (10 Outlets) On-Battery Output Wave Form Operating Temperature Operating Relative Humidity Size (W x H x D) Net Weight Battery Type Typical Battery Recharge Time Typical Battery Life Recommended Battery Safety Approvals CP900AVR CP900AVR2 900VA / 560W CP1200AVR CP1200AVR2 1,200VA / 720W CP1500AVRT CP1500AVRT2 1,500VA / 900W 120V 60 Hz ± 3 Hz 120Vac ± 5% 900VA / 560W 1,200VA / 720W 1,500VA / 900W 12 A 12 A 12.5 A Simulated Sine Wave + 32°F to 104° F / 0° C to 40° C 0 to 95% non-condensing 3.9" x 9.8" x 13.7" (99 x 249 x 348 mm) 21.83 lbs / 9.9 kg 21.83 lbs / 9.9 kg 24.1 lbs / 10.91 kg CyberPower / RB1270X2C CyberPower / RB1270X2C CyberPower / RB1290X2 8 hours to 90% capacity from total discharge 3 to 6 years, depending on number of discharge/recharge cycles Sealed Maintenance Free Lead Acid Battery UL1778 (UPS), CSA C22.2 No. 107, FCC/DoC Class B SYSTEM FUNCTION BLOCK DIAGRAM Input EMI Filter Surge Suppressor AVR Output Normal Mode Battery Mode Charger AC / DC Battery Inverter CYBERPOWER GREENPOWER UPS™ TECHNOLOGY Advanced Energy-Saving Design The GreenPower UPS™ has a high-efficiency charger, which makes it the most energy-efficient UPS in its class. The advanced high-frequency charging system significantly improves charging efficiency GREENPOWER UPS™ Energy-Saving Technology and conserves energy. As a result of this advanced design, the GreenPower UPS™ uses less energy compared to competitive models. The GreenPower UPS™ is manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive making it one of the most environmental- ly-friendly UPS systems on the market today. FCC COMPLIANCE STATEMENT This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment to an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/TV technician for help. Warning: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Canadian Compliance Statement CAN ICES-3 (B)/NMB-3(B) LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE Please visit www.CyberPowerSystems.com for a copy of the Limited Warranty and Connected Equipment Guarantee. Where Can I Get More Information? The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded. CyberPower is the warrantor under this Limited Warranty. For further information please feel free to contact CyberPower at: Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400 Shakopee, MN 55379 call us at (877) 297-6937; or submit a web ticket online at: cyberpowersystems.com/support. Cyber Power Systems (USA), Inc. encourages environmentally sound methods for disposal and recycling of its UPS products. Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state. WARNING: This product can expose you to chemicals including bisphenol A (BPA) and styrene, which is known to the State of California to cause reproductive harm and cancer. For more information, go to www.P65Warnings.ca.gov. © 2021 CyberPower Systems (USA), Inc. PowerPanel® Personal is a trademark of Cyber Power Systems(USA) Inc. All rights reserved. All other trademarks are the property of their respective owners.

  • 1
  • 2

DEFINITIONS FOR ILLUMINATED LED INDICATORS
On Line
On Battery
AVR
Overload
Alarm
Condition
On
Off
Off
Off
Off
Normal
Off
Flashes while
beeping
Off
Off
Beep twice
every 30
seconds
Utility Failure -
The UPS is providing power to battery protected outlets from
its battery.
Off
Flashes while
beeping
Off
Off
Rapid beeping
every
1/2 second
Utility Failure -
The UPS is providing battery power. Rapid beeping indicates the
unit will run out of power shortly.
On/Off
Off/On
Off
On
Constant tone
Overload Fault -
Occurs when connected equipment exceeds the listed capacity
of the UPS. Turn the UPS off, unplug at least one piece of equipment from battery
outlets, wait 10 seconds, reset the circuit breaker and turn the unit on.
On/Off
Off/On
Off
Off
Constant tone
Short Fault -
Unplug at least one piece of equipment from battery outlets and
turn the UPS on again.
UPS Fault –
Contact CyberPower Systems for support.
On/Off
Off/On
Off
Off
Beep every
2 seconds
Charger Fault -
Contact CyberPower Systems for support.
FUNCTION SETUP GUIDE – SENSITIVITY SETUP
Indicators Illuminate
Sensitivity
Description
1 (Red)
Low
If the connected equipment can tolerate more power events (example: unstable power often associated with stormy
weather), select Low Sensitivity and the UPS will go to Battery Mode less often.
2 (Yellow, Red)
Medium (Default)
The UPS will go to Battery Mode if the power is unstable.
3 (Green, Yellow, Red)
High
If the connected equipment is more sensitive to power events, select High Sensitivity and the UPS will go to Battery
Mode more often.
Even when the UPS is operating normally (on line mode), the AC input voltage may not be
stable all the time. Sensitive equipment may be prone to damage caused by unexpected
voltage fluctuations. Use the following steps to adjust the sensitivity of the UPS unit:
1. Please make sure the UPS is in
LINE MODE
and operating in a normal condition.
2. To Enter the Sensitivity Setup mode, press the MUTE Button for 6 seconds until all
indicators flash rapidly.
3. The unit will show the current sensitivity setting, as shown in the following table.
4. To select Low Sensitivity setting: shortly press MUTE button until one red indicator
flashes.
5. To select Medium Sensitivity setting, shortly press the MUTE button until red and yellow
indicators flash.
6. To select High Sensitivity setting, shortly press the MUTE button until green, yellow and
red indicators flash.
7. To set up a level of sensitivity, hold down the MUTE button until the green indicator (the
first one) illuminates.
8. Once in setup mode, if there is no action within 7 seconds, the unit will exit setup mode
without changing any settings.
TROUBLESHOOTING
Problem
Possible Cause
Solution
Circuit breaker button is
projecting from the back of
the unit.
Circuit breaker has been tripped due to
an overload.
Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit
breaker by pressing the button, and then turn the UPS on.
The UPS does not perform
expected runtime.
Battery not fully charged.
Recharge the battery by leaving the UPS plugged in.
Battery is worn out.
Contact CyberPower Systems about replacement batteries at: cyberpowersystems.com/support.
The UPS will not turn on.
The on/off switch is designed to prevent
damage from rapidly turning it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The unit is not connected to an AC outlet.
The unit must be connected to a 120V 60Hz outlet.
The battery is worn out.
Contact CyberPower Systems about replacement batteries at: cyberpowersystems.com/support.
Mechanical problem.
Contact CyberPower Systems at: cyberpowersystems.com/support.
PowerPanel® Personal is
inactive (all icons are gray).
The USB / serial cable is not
connected.
Connect the USB / serial cable to the UPS unit and an open USB / serial port on the back of the
computer. You must use the cable that came with the unit.
The USB / serial cable is connected to the
wrong port.
Check the back of the computer for an additional USB / serial port. Move the cable to this port.
The unit is not providing battery power.
Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS back on.
This should reset the unit.
Additional troubleshooting information can be found at “Support” at www.CyberPowerSystems.com
TECHNICAL SPECIFICATIONS
Series
CP900AVR
CP1200AVR
CP1500AVRT
Model
CP900AVR2
CP1200AVR2
CP1500AVRT2
Capacity
900VA / 560W
1,200VA / 720W
1,500VA / 900W
Nominal Input Voltage
120V
Input Frequency
60 Hz ± 3 Hz
On-Battery Output Voltage
120Vac ± 5%
Max. Load for UPS Outlets (5 Outlets)
900VA / 560W
1,200VA / 720W
1,500VA / 900W
Max. Load for Full-Time Surge Protection outlets (10 Outlets)
12 A
12 A
12.5 A
On-Battery Output Wave Form
Simulated Sine Wave
Operating Temperature
+ 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity
0 to 95% non-condensing
Size (W x H x D)
3.9" x 9.8" x 13.7" (99 x 249 x 348 mm)
Net Weight
21.83 lbs / 9.9 kg
21.83 lbs / 9.9 kg
24.1 lbs / 10.91 kg
Battery Type
CyberPower / RB1270X2C
CyberPower / RB1270X2C
CyberPower / RB1290X2
Typical Battery Recharge Time
8 hours to 90% capacity from total discharge
Typical Battery Life
3 to 6 years, depending on number of discharge/recharge cycles
Recommended Battery
Sealed Maintenance Free Lead Acid Battery
Safety Approvals
UL1778 (UPS), CSA C22.2 No. 107, FCC/DoC Class B
SYSTEM FUNCTION BLOCK DIAGRAM
Input
Output
Battery Mode
Normal Mode
EMI
Filter
Surge
Suppressor
Inverter
Charger
AC / DC
Battery
AVR
Advanced Energy-Saving Design
The GreenPower UPS™ has a high-efficiency charger, which makes
it the most energy-efficient UPS in its class. The advanced high-fre-
quency charging system significantly improves charging efficiency
and conserves energy. As a result of this advanced design, the
GreenPower UPS™ uses less energy compared to competitive
models. The GreenPower UPS™ is manufactured in accordance with the Restriction
on Hazardous Substances (RoHS) directive making it one of the most environmental-
ly-friendly UPS systems on the market today.
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
G
REEN
P
OWER
UPS
Energy-Saving Technology
This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful interfer-
ence, and (2) this device must accept any interference received, including interfer-
ence that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installa-
tion. This equipment generates, uses, and can radiate radio frequency energy and,
if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interfer-
ence will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment to an outlet on a circuit different from that to which the
receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Warning: Changes or modifications not expressly approved by the party responsible
for compliance could void the user’s authority to operate the equipment.
Canadian Compliance Statement
CAN ICES-3 (B)/NMB-3(B)
FCC COMPLIANCE STATEMENT
Please visit www.CyberPowerSystems.com for a copy of the Limited Warranty and
Connected Equipment Guarantee.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International
Sale of Goods is expressly excluded. CyberPower is the warrantor under this Limited
Warranty. For further information please feel free to contact CyberPower at:
Cyber Power Systems (USA), Inc.
4241 12th Ave E., STE 400
Shakopee, MN 55379
call us at
(877) 297-6937
; or submit a web ticket online at:
cyberpowersystems.com/support
.
Cyber Power Systems (USA), Inc. encourages environmentally sound methods for
disposal and recycling of its UPS products. Please dispose and/or recycle your UPS and
batteries in accordance to the local regulations of your state.
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
WARNING: This product can expose you to chemicals including bisphenol A (BPA) and
styrene, which is known to the State of California to cause reproductive harm and cancer.
For more information, go to www.P65Warnings.ca.gov.
© 2021 CyberPower Systems (USA), Inc. PowerPanel® Personal is a trademark of
Cyber Power Systems(USA) Inc.
All rights reserved. All other trademarks are the property of their respective owners.