CyberPower OL6KRT Datasheet - Page 2

Ol6krt Smart App, Online Ups System, Specifications Cont.

Page 2 highlights

OL6KRT SMART APP ONLINE UPS SYSTEM SPECIFICATIONS CONT. OUTPUT CONT. Watts 5,400 (5.4 kW) at 220, 230, 240 V input 4,860 (4.86 kW) at 208 V input 4,320 (4.32 kW) at 200 V input Power Factor 0.9 Waveform (Battery Mode) Sine wave Nominal Voltage (Battery 200, 208, 220, 230, Mode) 240 V ±2% (configurable) Frequency 50/60 Hz ±0.25 Hz (auto-sensing/configurable) ECO Mode Bypass Voltage Range ±10%, ±15% (configurable) Harmonic Distortion

  • 1
  • 2
  • 3

OL6KRT SMART APP
ONLINE UPS SYSTEM
SPECIFICATIONS CONT.
OUTPUT CONT.
Watts
5,400 (5.4 kW) at 220, 230, 240
V input
4,860 (4.86 kW) at 208 V input
4,320 (4.32 kW) at 200 V input
Power Factor
0.9
Waveform (Battery
Mode)
Sine wave
Nominal Voltage (Battery
Mode)
200, 208, 220, 230,
240 V ±2% (configurable)
Frequency
50/60 Hz ±0.25 Hz
(auto-sensing/configurable)
ECO Mode Bypass
Voltage Range
±10%, ±15% (configurable)
Harmonic Distortion
<3% at linear load,
<5% at non-linear load
Crest Factor
3:1
Outlets - Total
4
Outlet Type
(2) NEMA L6-20R,
(2) NEMA L6-30R
Overload Protection
Line Mode:
105% to 125% load for 1 min
126% to 150% load for 10 s
Battery Mode:
105% to 130% load for 10 s
131% to 150% load for 2 s
Short Circuit Protection
UPS Output Cut off
Immediately or Input Fuse/
Circuit Breaker Protection
Bypass
Internal Bypass
(Automatic and Manual)
Transfer Time
0 ms
BATTERY
Runtime at Half Load
15 min
Runtime at Full Load
5.4 min
Battery Type
Sealed lead acid
Battery Size
12 V/7 Ah
Battery Quantity
20
Replaceable
Yes
Replacement Battery
(2) RB1270X10
Hot Swappable
Yes
BATTERY CONT.
Typical Recharge Time
4 h (0% to 90%)
Smart Battery
Management (SMB) Mode
Yes
Extended Battery
Module (EBM)
Optional BP240V30ART3U
or BP240VL3U01
SURGE PROTECTION AND FILTERING
Surge Protection
2430 Joules,
per IEC 61000-4-5 Level 3
Phone RJ-11 / Ethernet
Surge Protection RJ-45
1-In / 1-Out (Combo)
EMI/RFI Filtration
Yes
MANAGEMENT AND COMMUNICATION
LCD Control Panel
Access 50 information status
and configuration settings via
the Information and
Configuration Menus, in addition
to an Event Log Menu.
Rotatable LCD Control
Panel Option
Yes
Removable LCD Control
Panel Option
Yes - Requires DB26 cable
(not included)
HID Compliant USB Port
Yes
Serial Port
Yes
Emergency Power Off
(EPO) Port
Yes
Dry Contact Port
Yes
Cables Included
USB cable, serial cable,
phone cable
LED Indicators
Power On (White)
Line Mode (Green)
Battery Mode (Yellow)
Bypass Mode (Yellow)
Fault (Red)
Replace Battery (Red)
Audible Alarms
Battery Mode, Battery Low,
Overload, UPS Fault
Software
PowerPanel® Business Edition
Upgradeable Firmware
Yes
Expansion Slot
Yes - RMCARD205 pre-installed