CyberPower PR1000LCDRT1U Datasheet - Page 2

Cost-effective feature-rich power protection for networking, servers and telecommunications equipment

Page 2 highlights

PR1000LCDRM1U Smart App Sinewave UPS Cost-effective feature-rich power protection for networking, servers and telecommunications equipment. GENERAL UPS Topology Energy Saving Active PFC Compatible INPUT Voltage Frequency Range Input Voltage Range Plug Type Plug Style Cord Length OUTPUT VA Watts Automatic Voltage Regulation On Battery Voltage On Battery Frequency On Battery Waveform Outlet Type Outlets - Total Outlets - Critical Load Outlets - Battery & Surge Protected Outlets - Surge-Only Protected Rated Power Factor Overload Protection Transfer Time BATTERY Runtime at Half Load Runtime at Full Load Battery Type Battery Size Hot-Swappable Battery Quantity User Replaceable Typical Recharge Time Replacement Battery Line Interactive GreenPower UPS™ Bypass Technology Yes Nominal 120V VAC 57 - 63 Hz 80 - 150 VAC NEMA 5-15P Right Angle, 45° Offset Right 10 ft 1,000 VA 800 W Boost 1 +30% Boost 2 +14% Buck -12% 120 VAC ± 5% 60 Hz ± 1% Sine Wave NEMA 5-15R 7 3 6 1 0.8 Internal Circuitry Limiting Circuit Breaker 10ms 13 minutes 3.5 minutes Sealed Lead-Acid 6V/9Ah Yes 4 Yes Less than 6 hours (90% charged) RB0690X4B SURGE PROTECTION & FILTERING Surge Suppression 1,030 Joules EMI/RFI Filtration Yes MANAGEMENT & COMMUNICATIONS Multifunction LCD Panel HID Compliant USB Port Displays: Current/Load Level, Runtime, Battery Level, Battery In Use, Input Voltage, Output Voltage, Overload, Silent Mode, Normal Mode Yes Serial Port Yes EPO Port Yes LED Indicators Power On, Wiring Fault Audible Alarms On Battery, Low Battery, Overload Software SNMP / HTTP Remote Monitoring PHYSICAL PowerPanel® Business Edition Yes, with optional RMCARD202, RMCARD203 or RMCARD205 Rack Size 1U Form Factor Rack Dimensions (WxHxD) (in.) 17.25 x 1.75 x 19.5 Weight (lbs.) 35.9 ENVIRONMENTAL Operating Temperature 32 - 104 °F (0 - 40 °C) Operating Humidity 0 - 95% (non-condensing) Storage Temperature 5 - 113 °F (-15 - 45 °C) Maximum Operating Elevation 10,000 ft (3,000 m) Maximum Storage Elevation 50,000 ft (15,000 m) AC Mode Thermal Dissipation 63 BTU/Hr CERTIFICATIONS Safety UL1778 4th cUL CSA C22.2 No 107.3-05 FCC/DOC Class A Environmental RoHS Compliant WARRANTY Product Warranty 3 Years Limited Connected Equipment Guarantee Lifetime CEG Amount $400,000 ©2016 Cyber Power Systems (USA), Inc. All rights reserved. CyberPower reserves the right to change, without prior notice, product offerings or specifications.

  • 1
  • 2

PR1000LCDRM1U Smart App Sinewave UPS
Cost-effective feature-rich power protection for networking, servers and telecommunications equipment.
©2±²6³Cyber³Power³Systems³(USA)´³Incµ³All³rights³reservedµ³CyberPower³reserves³the³right³to³change´³without³prior³notice´³product³offerings³or³specificationsµ
GENERAL
UPS Topology
Line Interactive
Energy Saving
GreenPower UPS™ Bypass Technology
Active PFC Compatible
Yes
INPUT
Voltage
Nominal 120V VAC
Frequency Range
57 – 63 Hz
Input Voltage Range
80 – 150 VAC
Plug Type
NEMA 5-15P
Plug Style
Right Angle, 45° Offset Right
Cord Length
10 ft
OUTPUT
VA
1,000 VA
Watts
800 W
Automatic Voltage Regulation
Boost 1 +30%
Boost 2 +14%
Buck -12%
On Battery Voltage
120 VAC ± 5%
On Battery Frequency
60 Hz ± 1%
On Battery Waveform
Sine Wave
Outlet Type
NEMA 5-15R
Outlets - Total
7
Outlets - Critical Load
3
Outlets - Battery & Surge Protected
6
Outlets - Surge-Only Protected
1
Rated Power Factor
0.8
Overload Protection
Internal Circuitry Limiting
Circuit Breaker
Transfer Time
10ms
BATTERY
Runtime at Half Load
13 minutes
Runtime at Full Load
3.5 minutes
Battery Type
Sealed Lead-Acid
Battery Size
6V/9Ah
Hot-Swappable
Yes
Battery Quantity
4
User Replaceable
Yes
Typical Recharge Time
Less than 6 hours (90% charged)
Replacement Battery
RB0690X4B
SURGE PROTECTION & FILTERING
Surge Suppression
1,030 Joules
EMI/RFI Filtration
Yes
MANAGEMENT & COMMUNICATIONS
Multifunction LCD Panel
Displays: Current/Load Level,
Runtime, Battery Level, Battery In
Use, Input Voltage, Output Voltage,
Overload, Silent Mode, Normal Mode
HID Compliant USB Port
Yes
Serial Port
Yes
EPO Port
Yes
LED Indicators
Power On, Wiring Fault
Audible Alarms
On Battery, Low Battery, Overload
Software
PowerPanel® Business Edition
SNMP / HTTP Remote Monitoring
Yes, with optional RMCARD202,
RMCARD203 or RMCARD205
PHYSICAL
Rack Size
1U
Form Factor
Rack
Dimensions (WxHxD) (in.)
17.25 x 1.75 x 19.5
Weight (lbs.)
35.9
ENVIRONMENTAL
Operating Temperature
32 – 104 °F (0 – 40 °C)
Operating Humidity
0 – 95% (non-condensing)
Storage Temperature
5 – 113 °F (-15 – 45 °C)
Maximum Operating Elevation
10,000 ft (3,000 m)
Maximum Storage Elevation
50,000 ft (15,000 m)
AC Mode Thermal Dissipation
63 BTU/Hr
CERTIFICATIONS
Safety
UL1778 4th
cUL CSA C22.2 No 107.3-05
FCC/DOC Class A
Environmental
RoHS Compliant
WARRANTY
Product Warranty
3 Years Limited
Connected Equipment Guarantee
Lifetime
CEG Amount
$400,000