Dell PowerEdge T440 EMC Technical Specifications - Page 12

Table 16. Particulate contamination specifications continued

Page 12 highlights

Table 16. Particulate contamination specifications (continued) Particulate contamination Specifications NOTE: This condition applies to data center and nondata center environments. Corrosive dust • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and nondata center environments. Table 17. Gaseous contamination specifications Gaseous contamination Specifications Copper coupon corrosion rate

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

Table 16. Particulate contamination specifications (continued)
Particulate
contamination
Specifications
NOTE:
This condition applies to data center and nondata center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and nondata center environments.
Table 17. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 defines, ANSI/ISA71.04-2013.
Silver coupon corrosion rate
<200 Å/month defines, ANSI/ISA71.04-2013.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
12
Technical specifications