Dell PowerSwitch S5212F-ON EMC PowerSwitch S5200F-ON Series Setup Guide - Page 24

Table 2. Environmental parameters, Table 3. AC power requirements, Parameter, Specifications

Page 24 highlights

Table 2. Environmental parameters Parameter Operating temperature Operating humidity Storage temperature Storage humidity Maximum thermal output Maximum operational altitude Maximum non-operational altitude Shock Table 3. AC power requirements Parameter Power supply Maximum current draw per system Maximum power consumption Typical power consumption 24 Specifications Specifications 0° to 45°C (32°F to 113°F) continuously NOTE: Reduce maximum temperature by 1°C/125 meters (1°F/228 feet) above 950 meters (3,117 feet). 5% to 85% (RH), non-condensing -40° to 70°C (-40° to 158°F ) 5% to 90%, non-condensing S5232F-ON: 635W = 2167 BTU/Hr S5248F-ON: 647W = 2208 BTU/Hr S5296F-ON: 893W = 3047 BTU/Hr S5224F-ON: 455W = 1552 BTU/Hr S5212F-ON: 304W = 1037 BTU/Hr 10,000 feet (3,048 meters) 39,370 feet (12,000 meters) Dell EMC Spec SV0115 Specifications S5232F-ON: 100-240 VAC 50/60 Hz S5248F-ON: 100-240 VAC 50/60 Hz S5296F-ON: 100-240 VAC 50/60 Hz S5224F-ON: 100-240 VAC 50/60 Hz S5212F-ON: 100-240 VAC 50/60 Hz S5232F-ON: 5.8A@110VAC and 2.4A@220VAC S5248F-ON: 5.8A@110VAC and 2.4A@220VAC S5296F-ON: 8.2A@110VAC and 4.1A@220VAC S5224F-ON: 4.2A@110VAC and 2.1A@220VAC S5212F-ON: 2.8A@110VAC and 1.4A@220VAC S5232F-ON: 635W maximum S5248F-ON: 647W maximum S5296F-ON: 893W maximum S5224F-ON: 455W maximum S5212F-ON: 304W maximum S5232F-ON: 490W typical S5248F-ON: 420W typical S5296F-ON: 607W typical S5224F-ON: 280W typical S5212F-ON: 208W typical

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26

Table 2. Environmental parameters
Parameter
Specifications
Operating temperature
0° to 45°C (32°F to 113°F) continuously
NOTE:
Reduce maximum temperature by 1°C/125
meters (1°F/228 feet) above 950 meters (3,117 feet).
Operating humidity
5% to 85% (RH), non-condensing
Storage temperature
–40° to 70°C (–40° to 158°F )
Storage humidity
5% to 90%, non-condensing
Maximum thermal output
S5232F-ON: 635W = 2167 BTU/Hr
S5248F-ON: 647W = 2208 BTU/Hr
S5296F-ON: 893W = 3047 BTU/Hr
S5224F-ON: 455W = 1552 BTU/Hr
S5212F-ON: 304W = 1037 BTU/Hr
Maximum operational altitude
10,000 feet (3,048 meters)
Maximum non-operational altitude
39,370 feet (12,000 meters)
Shock
Dell EMC Spec SV0115
Table 3. AC power requirements
Parameter
Specifications
Power supply
S5232F-ON: 100–240 VAC 50/60 Hz
S5248F-ON: 100–240 VAC 50/60 Hz
S5296F-ON: 100–240 VAC 50/60 Hz
S5224F-ON: 100-240 VAC 50/60 Hz
S5212F-ON: 100-240 VAC 50/60 Hz
Maximum current draw per system
S5232F-ON: 5.8A@110VAC and 2.4A@220VAC
S5248F-ON: 5.8A@110VAC and 2.4A@220VAC
S5296F-ON: 8.2A@110VAC and 4.1A@220VAC
S5224F-ON: 4.2A@110VAC and 2.1A@220VAC
S5212F-ON: 2.8A@110VAC and 1.4A@220VAC
Maximum power consumption
S5232F-ON: 635W maximum
S5248F-ON: 647W maximum
S5296F-ON: 893W maximum
S5224F-ON: 455W maximum
S5212F-ON: 304W maximum
Typical power consumption
S5232F-ON: 490W typical
S5248F-ON: 420W typical
S5296F-ON: 607W typical
S5224F-ON: 280W typical
S5212F-ON: 208W typical