Environmental Corrosive Dust NOTE: Applies to data center and non-data center environments. • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. Gaseous Contamination NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity. Copper Coupon Corrosion Rate Silver Coupon Corrosion Rate
![](/manual_guide/products/dell-powervault-dx6112-getting-started-guide-0b92709/9.png)
Environmental
Corrosive Dust
NOTE:
Applies to data center and non-data center
environments.
•
Air must be free of corrosive dust.
•
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
Gaseous Contamination
NOTE:
Maximum corrosive contaminant levels measured at
≤
50% relative humidity.
Copper Coupon Corrosion Rate
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
Silver Coupon Corrosion Rate
<200 Å/month as defined by AHSRAE TC9.9.