Fluke CO-220 FE CO-220 Instruction Sheet - Page 7

Specifications

Page 7 highlights

CO-220 English Instruction Sheet Page 7 Specifications Temperature Operating: Storage: Humidity (non-condensing) < 3 weeks > 3 weeks Measurement range Measurement resolution Accuracy Sensor type Typical sensor life Temperature Coefficient Self Test Battery Typical battery life Certification 0 oC to +50 oC -30 oC to +50 oC 0-99 % RH 0-90 % RH 0 to 1000 PPM 1 PPM for 0 - 200 PPM; 5 PPM for 200 - 1000 PPM 5 % or ± 2 PPM (whichever is greater) Stabilized electrochemical Gas-specific (CO) 3 years Add 0.4 % per °C > 25 °C Add 0.6 % per °C < 20 °C < 20 seconds 9 V, NEDA 1604A or IEC 6LR61, or equivalent. 500 hours P

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

CO-220 English Instruction Sheet
Page
7
Specifications
Temperature
Operating:
Storage:
0
o
C to +50
o
C
-
30
o
C to +50
o
C
Humidity (non-condensing)
< 3 weeks
> 3 weeks
0-99 % RH
0-90 % RH
Measurement range
0 to 1000 PPM
Measurement
resolution
1 PPM for 0 - 200 PPM;
5 PPM for 200 - 1000 PPM
Accuracy
5
% or
±
2 PPM (whichever is
greater)
Sensor type
Stabilized electrochemical
Gas-specific (CO)
Typical sensor life
3 years
Temperature Coefficient
Add 0.4 % per °C > 25 °C
Add 0.6 % per °C < 20 °C
Self Test
< 20 seconds
Battery
9 V, NEDA 1604A or IEC 6LR61,
or equivalent.
Typical battery life
500 hours
Certification