GE AJCQ12ACD Use and Care Manual - Page 8

About the controls on the air conditioner, Fan Cycle/Continuous - Cool

Page 8 highlights

Consumer Support Troubleshooting Tips Installation Instructions Care and Cleaning Operating Instructions Safety Instructions About the controls on the air conditioner Vent Control The vent control is located behind the front grille on the right side of the air discharge area. When CLOSED, only the air inside the room will be circulated and conditioned. When OPEN, the vent allows outdoor fresh air exchange. To open or close the vent: 1. Remove the front grille. 2. Remove the vent card screw. 3. Remove vent card, turn it over and replace it by locating rear hole in card over locating pin inside air discharge and reattaching screw at front. The unit leaves the factory set at the CLOSE position. Locating hole Locating hole Screw hole OPEN position (Mesh end toward back) Screw hole CLOSE position (Mesh end toward front) Air Direction Horizontal louvers on the front grille let you control the air direction up and down. Remove the front grille to adjust the vertical louvers side-to-side to direct the air left or right. Auxiliary Controls - Dip Switches (location varies by model) The auxiliary dip switch controls are located behind the room cabinet-as shown in this figure. The owner is responsible for checking switches and ensuring they are in the desired position. Fan Cycle/Continuous - Cool Fan Cycle/Continuous - Heat (on some models) Class 2 (on some models) No function (reserved for future use) Fan Cycle/Continuous - Cool When this switch is enabled (UP), it allows the indoor fan to cycle on/off with the compressor. When this switch is disabled (DOWN), it allows the indoor fan to run continuously. The default setting is down (continuous). Fan Cycle/Continuous - Cool Fan Cycle/Continuous - Heat (on some models) When this switch is enabled (UP), it allows the indoor fan to run continuously with the heater operation. When this switch is disabled (DOWN), it allows the indoor fan to cycle on/off. The default setting is down (cyclic). Fan Cycle/Continuous - Heat (on some models) Class 2 - Remote Thermostat (on some models) When this switch is enabled (UP), it allows the unit to operate with a Class 2 Remote Control Wall Thermostat. The unit controls are disabled. 8 The default setting is down (disabled). Class 2 (on some models)

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72

No function (reserved
for future use)
8
Consumer Support
Troubleshooting Tips
Installation Instructions
Care and Cleaning
Operating Instructions
Safety Instructions
About the controls on the air conditioner
Auxiliary Controls – Dip Switches
(location varies by model)
Vent Control
The vent control is located behind the front grille on the
right side of the air discharge area. When
CLOSED
, only
the air inside the room will be circulated and conditioned.
When
OPEN,
the vent allows outdoor fresh air exchange.
To open or close the vent:
1. Remove the front grille.
2. Remove the vent card screw.
3. Remove vent card, turn it over and replace it by
locating rear hole in card over locating pin inside air
discharge and reattaching screw at front.
Horizontal louvers
on the front grille let
you control the air
direction up and down.
Remove the front grille
to adjust the vertical
louvers side-to-side
to direct the air left
or right.
Air Direction
Locating hole
Screw hole
OPEN position
(Mesh end toward back)
CLOSE position
(Mesh end toward front)
Locating hole
Screw hole
The unit leaves the factory set at the CLOSE position.
The auxiliary dip switch controls are located
behind the room cabinet—as shown in this figure.
The owner is responsible for checking switches
and ensuring they are in the desired position.
Fan Cycle/Continuous - Cool
Fan Cycle/Continuous - Heat (on some models)
Class 2 (on some models)
Fan Cycle/Continuous - Cool
When this switch is enabled
(UP)
, it allows the indoor
fan to cycle on/off with the compressor. When this
switch is disabled
(DOWN)
,
it allows the indoor fan to run
continuously. The default setting is down (continuous).
Fan Cycle/Continuous - Heat
(on some models)
When this switch is enabled
(UP)
, it allows the indoor fan
to run continuously with the heater operation. When this
switch is disabled
(DOWN)
,
it allows the indoor fan to
cycle on/off. The default setting is down (cyclic).
Class 2 - Remote Thermostat
(on some models)
When this switch is enabled
(UP)
, it allows the unit
to operate with a Class 2 Remote Control Wall
Thermostat. The unit controls are disabled.
The default setting is down (disabled).
Fan Cycle/Continuous - Cool
Fan Cycle/Continuous - Heat (on some models)
Class 2 (on some models)