Operating Instructions Installation Instructions Safety Instructions Installing the water heater. Thermal Expansion Determine if a check valve exists in the inlet water line. It may have been installed in the cold water line as a separate back flow preventer, or it may be part of a pressure reducing valve, water meter or water softerner. A check valve located in the cold water inlet line can cause what is referred to as a "closed water system". A cold water inlet line with no check valve or back flow prevention device is referred to as an "open water system". As water is heated, it expands in volume and creates an increase in the pressure within the water system. This action is referred to as "thermal expansion". In an "open water system", expanding water which exceeds the capacity of the water heater flows back into the city main where the pressure is easily dissipated. A "closed water system", however, prevents the expanding water from flowing back into the main supply line, and the result of "thermal expansion" can create a rapid and dangerous pressure increase in the water heater and system piping. This rapid pressure increase can quickly reach the safety setting of the relief valve, causing it to operate during each heating cycle. Thermal expansion, and the resulting rapid and repeated expansion and contraction of components in the water heater and piping system can cause premature failure of the relief valve, and possibly the heater itself. Replacing the relief valve will not correct the problem. The suggested method of controlling thermal expansion is to install an expansion tank in the cold water line between the water heater and the check valve. The expansion tank is designed with an air cushion built in that compresses as the system pressure increases, thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve. Other methods of controlling thermal expansion are also available. Contact your installing contractor, water supplier or plumbing inspector for addition information regarding this subject. Care and Cleaning Troubleshooting Tips NOTICE: Do not apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to adapter before fitting adapter to the water connections on heater. Any heat applied to the water supply fittings will permanently damage the dip tube. Water Supply Connections Refer to the illustration below for suggested typical installation. The installation of unions or flexible copper connectors is recommended on the hot and cold water connections so that the water heater may be easily disconnected for servicing if necessary. The HOT and COLD water connections are clearly marked and are 3/4″ NPT on all models. Install a shut-off valve in the cold water line near the water heater. Typical Side Connect Installation Electrical junction box (use only copper conductors) Anode To electrical distribution panel Temperature & pressure relief valve Union Hot water outlet to fixtures Union Jacket access panel Shut-off valve To cold water supply Jacket access panel Relief valve 6 discharge line. Directed to under side of home. Drain valve Auxiliary catch pan Customer Service

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

Installing the water heater.
6
Thermal Expansion
Water Supply Connections
Typical Side Connect Installation
Anode
NOTICE: Do not apply heat
to the HOT or COLD water
connections. If sweat
connections are used,
sweat tubing to adapter
before fitting adapter to the
water connections on
heater. Any heat applied to
the water supply fittings
will permanently damage
the dip tube.
Customer Service
Troubleshooting Tips
Care and Cleaning
Operating Instructions
Installation Instructions
Safety Instructions
To electrical
distribution panel
Electrical junction box
(use only copper conductors)
Temperature & pressure relief
valve
Union
To cold water supply
Relief valve
discharge line.
Directed to under
side of home.
Union
Hot water outlet to fixtures
Jacket access
panel
Shut-off valve
Jacket access
panel
Auxiliary catch pan
Drain valve
Refer to the illustration below for suggested typical installation. The installation of
unions or flexible copper connectors is recommended on the hot and cold water
connections so that the water heater may be easily disconnected for servicing if
necessary. The HOT and COLD water connections are clearly marked and are 3/4
NPT on
all models. Install a shut-off valve in the cold water line near the water heater.
Determine if a check valve exists in
the inlet water line.
It may have been
installed in the cold water line as a
separate back flow preventer, or it may be
part of a pressure reducing valve, water
meter or water softerner. A check valve
located in the cold water inlet line can
cause what is referred to as a
“closed
water system”.
A cold water inlet line
with no check valve or back flow prevention
device is referred to as an
“open water
system”.
As water is heated, it expands in volume
and creates an increase in the pressure
within the water system. This action is
referred to as
“thermal expansion”.
In an
“open water system”,
expanding
water which exceeds the capacity of the
water heater flows back into the city main
where the pressure is easily dissipated.
A
“closed water system”,
however,
prevents the expanding water from flowing
back into the main supply line, and the
result of “thermal expansion” can create a
rapid and dangerous pressure increase in
the water heater and system piping. This
rapid pressure increase can quickly reach
the safety setting of the relief valve,
causing it to operate during each heating
cycle. Thermal expansion, and the resulting
rapid and repeated expansion and
contraction of components in the water
heater and piping system can cause
premature failure of the relief valve, and
possibly the heater itself. Replacing the
relief valve
will not
correct the problem.
The suggested method of controlling
thermal expansion is to install an
expansion tank in the cold water line
between the water heater and the check
valve. The expansion tank is designed with
an air cushion built in that compresses as
the system pressure increases, thereby
relieving the over pressure condition and
eliminating the repeated operation of the
relief valve. Other methods of controlling
thermal expansion are also available.
Contact your installing contractor, water
supplier or plumbing inspector for addition
information regarding this subject.