Purging method the refrigerant is R407C
View all Haier AB122ACBHA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
Installation Procedures (4) Purging method ( the refrigerant is R407C) To use vacuum pump 1 Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump. 2 Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again. 3 Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 . 4 Open the valve rod for the 2-way valve to and angle of anticlockwise 90 degree. After 6 seconds later, close the 2-way valve and male the inspection of gas leakage. 5 No gas leakage? In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed 6 steps. 6 Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly. 7 To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for 2-way valve and 3-way's a lottle more than the point where the torque increases suddenly. 2-way valve Liquid pipe 6.35mm(1/4'') Gas pipe 12.7mm(1/2'') 3-way valve Gaugemanifold 2 Open Vacuum pump 3 Close 2-way valve 90 90 If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder. 3-way valve Service port 4 90 for 6 sec. 2-way valve 6 3-way valve 6 8 After attaching the each caps, check the gas leakage around the caps. 2-way valve 3-way valve CAUTION: If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate. 7 Valve rod cap 7 Valve rod cap 7 Service port cap 21