Haier AB122ACERA Service Manual - Page 41

Trouble description, Display of, LED borad, LED 5-4-3-2-1, Analyze and diagnose, Flash times, of LED

Page 41 highlights

Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA Trouble description Display of LED borad Analyze and diagnose LED 5-4-3-2-1 IPM failure 00001 IPM failure Abnormal of DC moter Communication error between indoor and outdoor unit Compressor discharging temprerture protection Spdu / IPM module over current protection Abnormal of outdoor ambient sensor Abnormal of piping sensor High pressure protection Abnormal of compressor discharge sensor The power supply is not the 50Hz Module PWM select circuit error 00010 00011 00100 00101 00110 00111 01000 01001 01010 01011 Jam of DC motor or motor failure Communication fail over 4min Compressor discharging tempreature over 120 centigrade Current of spdu / ISPM module over limit Outdoor ambient sensor short-circuit or open-circuit last 60 sec Piping sensor short-circuit or open-circuit last 60 sec System high pressure over 4.5Mpa Compressor discharge sensor short-circuit or open-circuit last 60 sec The power supply is not the 50Hz Module PWM select wrong circuit Flash times of LED on mainborad 1 2 3 4 5 6 7 8 9 10 11 Detect PFC over-current 01100 The current of PFC circuit is too high 12 Module error 01101 Module error 13 Eeprom failure 01110 Outdoor main board eeprom fail 14 Compressor jam(only for spdu) 01111 Inner compressor is abnormal jamed 15 Compressor start-up abnormal 10001 Compressor start-up abnormal 17 Compressor parameter error 10010 Wrong compressor parameter is selected in the Eeprom 18 Circuit error detected by current 10011 Circuit damage detected by the current 19 Abnormal of Compressor suction sensor 10101 Compressor suction sensor short-circuit or open-circuit last 60 sec 21 SPDU Communication error 10110 Communication error send from SPDU 22 Communication error between main board and spdu module 10110 Communication fail over 4min 22 Low pressure protection 11000 System low pressure under 0.05Mpa 24 Condenser air inlet temp. sensor failure 11001 Condenser air inlet temp. sensor short-circuit or open-circuit last 60 sec 25 Module over-voltage protection (only for ISPM) 11010 Send from ISPM module 26 Module lack-voltage protection (only for ISPM) 11011 Send from ISPM module 27 Compressor phase loss 11110 U/V/W loss 30 PFC voltage abnormal 11111 Voltage of PFC circuit is abnormal 31 Compressor U-phase over-current Compressor V-phase over-current Compressor W-phase over-current 4-way valve reverse failure 00101 The current of compressor U-phase is too high 32 00101 The current of compressor V-phase is too high 33 00101 The current of compressor W-phase is too high 34 Alarm and stop if detect Td-Tci=25 last for 1min Lack off refrigerant or discharge side dirty 11101 after compressor has started for 10min in cooling mode, confirm the failure if it appears 3 times 29 in one hour 41

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63

Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
Trouble description
Display of
LED borad
LED 5-4-3-2-1
Analyze and diagnose
Flash times
of LED on
mainborad
01111
Eeprom failure
01110
Outdoor main board eeprom fail
14
IPM failure
00001
IPM failure
1
Compressor U-phase
over-current
00101
The current of compressor U-phase is too high
32
Communication error between
main board and spdu module
10110
Communication fail over 4min
22
High pressure protection
01000
System high pressure over 4.5Mpa
8
Module over-voltage protection
(only for ISPM)
11010
Send from ISPM module
26
Compressor start-up abnormal
10001
Compressor start-up abnormal
17
Compressor discharging
temprerture protection
00100
Compressor discharging tempreature over 120
centigrade
4
Abnormal of DC moter
00010
Jam of DC motor or motor failure
2
Abnormal of piping sensor
00111
Piping sensor short-circuit or open-circuit last
60 sec
7
Abnormal of Compressor
suction sensor
10101
Compressor suction sensor short-circuit or
open-circuit last 60 sec
21
Abnormal of outdoor
ambient
sensor
00110
Outdoor
ambient
sensor short-circuit or
open-circuit last 60 sec
6
Abnormal of compressor
discharge sensor
01001
Compressor discharge sensor short-circuit or
open-circuit last 60 sec
9
Spdu / IPM module over
current protection
00101
Current of spdu / ISPM module over limit
5
Communication error between
indoor and outdoor unit
00011
Communication fail over 4min
3
Compressor V-phase
over-current
00101
The current of compressor V-phase is too high
33
Compressor W-phase
over-current
00101
The current of compressor W-phase is too high
34
Compressor jam(only for spdu)
Inner compressor is
abnormal jamed
15
Compressor phase loss
11110
U/V/W loss
30
Module lack-voltage protection
(only for ISPM)
11011
Send from ISPM module
27
Module PWM select circuit error
01011
Module PWM select wrong circuit
11
Detect PFC over-current
01100
The current of PFC circuit is too high
12
Compressor parameter error
10010
Wrong compressor parameter is selected in the
Eeprom
18
SPDU
Communication error
10110
Communication error send from
SPDU
22
Circuit error detected by current
10011
Circuit damage detected by the current
19
PFC voltage abnormal
11111
Voltage of PFC circuit is abnormal
31
Module
error
01101
Module error
13
The power supply is not the
50Hz
01010
The power supply is not the 50Hz
10
Condenser air inlet temp. sensor
failure
11001
Condenser air inlet temp. sensor short-circuit or
open-circuit last 60 sec
25
Low pressure protection
11000
System low pressure
under
0.05Mpa
24
4-way valve reverse failure
11100
Alarm and stop if detect Td-Tci<=25 last for 1min
after compressor has started for 10min in heating
mode, confirm the failure if it appears 3 times
in one hour.
28
Lack off refrigerant or discharge
side dirty
11101
Alarm and stop if detect Td-Tci>=25 last for 1min
after compressor has started for 10min in cooling
mode, confirm the failure if it appears 3 times
in one hour
29
41