Haier AD182ALERA User Manual - Page 22
ÜÊÅÏ
View all Haier AD182ALERA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 22 highlights
Installation Manual For Indoor Unit Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.) Circuit breaker Power source Item Phase Switch breaker Overcurrent protector wire size (A) rated capacity (A) (minimum) For series 122 182 1 40 26 2.5mm2 Earth leakage breaker Switch breaker Leak current 40A 30mA For series 242 1 40 26 4.0mm2 40A 30mA (2) Wiring connection Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals. AD182ALERA AD242ALERA AD242ALEAA INDOOR UNIT 1 23 Y/G TERMINAL BLOCK OUTDOOR UNIT TERMINAL BLOCK LN 1 23 Y/G POWER SUPPLY: 1PH, 220-230V~, 50Hz Make wiring to supply power to the indoor unit, so that the power for the outdoor unit is supplied by terminals. AD122ALEAA AD122ALERA AD182ALEAA OUTDOOR UNIT 1 23 Y/G TERMINAL BLOCK INDOOR UNIT 1 23N L Y/G TERMINAL BLOCK POWER SUPPLY: 1PH, 220-230V~, 50Hz 21